Product Model

IBS IL 24 BK-T/U-2MBD

In Stock
Last updated: 2025/4/23
Phoenix Contact IBS IL 24 BK-T/U-2MBD

Selling Points

  • 1Ensures seamless data transmission with a transmission speed of 2 Mbps.
  • 2Designed for harsh environments with IP20 protection.
  • 3Mounts easily on DIN rail for quick setup.
  • 4Meets WEEE/RoHS compliance and is UL listed.
  • 5Supports 24 V DC with a maximum current consumption of 1.25 A.
Product Details
IBS IL 24 BK-T/U-2MBD
Phoenix Contact

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Type
modular
Number of devices with parameter channel
63
Number of supported branch terminals with remote bus branch
max. 15
ID code (dec.)
04
ID code (hex)
04
Length code (hex)
00
Input address area
0 Byte
Output address area
0 Byte
Register length
0 bit
Protective circuit
Reverse polarity protection
Supply voltage
24 V DC (via Inline connector)
Supply voltage range
19.2 V DC ... 30 V DC (including all tolerances, including ripple)
Current draw
max. 1.25 A (with max. number of connected I/O terminal blocks) typ. 100 mA (without connected Inline I/O terminals)
Supply voltage
7.5 V DC ±5 %
Supply voltage
24 V DC
Supply voltage range
19.2 V DC ... 30 V DC (including all tolerances, including ripple)
Supply voltage
24 V DC
Supply voltage range
19.2 V DC ... 30 V DC (including all tolerances, including ripple)
Supply voltage
24 V DC -15 % / +20 % (in accordance with EN 61131-2)
Supply voltage range
19.2 V DC ... 30 V DC (including all tolerances, including ripple)
Test voltage: 5 V supply, incoming remote bus / 5 V supply outgoing remote bus
500 V AC, 50 Hz, 1 min
Test voltage: 5 V supply incoming remote bus / 7.5 V communications power, 24 V analog supply, 24 V bus coupler supply
500 V AC, 50 Hz, 1 min
Test voltage: 5 V supply, incoming remote bus / 24 V main supply, 24 V segment supply
500 V AC, 50 Hz, 1 min
Test voltage: 5 V supply incoming remote bus / functional ground
500 V AC, 50 Hz, 1 min
Test voltage: 5 V supply outgoing remote bus / I/O (U
500 V AC, 50 Hz, 1 min
Test voltage: 5 V supply outgoing remote bus / communications power (U
500 V AC, 50 Hz, 1 min
Test voltage: 5 V supply outgoing remote bus / functional ground
500 V AC, 50 Hz, 1 min
Test voltage: 7.5 V communications power, 24 V analog supply, 24 V bus coupler supply/functional ground
500 V AC, 50 Hz, 1 min
Test voltage: Communications power (U
500 V AC, 50 Hz, 1 min
Test voltage: 24 V main supply, 24 V segment supply/functional ground
500 V AC, 50 Hz, 1 min
Connection method
Spring-cage connection
Conductor cross section, rigid
0.08 mm² ... 1.5 mm²
Conductor cross section, flexible
0.08 mm² ... 1.5 mm²
Conductor cross section AWG
28 ... 16
No. of channels
2 (Connected to functional ground with a capacitor)
Connection method
Inline shield connector
Number of positions
6
Transmission speed
2 Mbps
Transmission physics
Copper
Connection method
Inline data jumper
Connection method
8-pos. Inline connector
Width
48.8 mm
Height
119.8 mm
Depth
71.5 mm
Color
green
Ambient temperature (operation)
-25 °C ... 55 °C
Degree of protection
IP20
Air pressure (operation)
80 kPa ... 106 kPa (up to 3000 m above sea level)
Air pressure (storage/transport)
70 kPa ... 106 kPa (up to 3000 m above sea level)
Ambient temperature (storage/transport)
-25 °C ... 85 °C
Permissible humidity (operation)
75 % ... 85 % (in the range of -25°C ... +55°C, appropriate measures against increased humidity (> 85%) must be taken.)
Permissible humidity (storage/transport)
75 % ... 85 % (Slight temporary condensation may sometimes appear on the housing, e.g. when the terminal block is brought out of a vehicle into an enclosed room.)
Mounting type
DIN rail mounting

Specifications may be subject to change without notice