Product Model
IBS IP 400 ME-MLR 2-8A DI4F

Selling Points
- 1Highly Reliable Performance: Designed for consistent and reliable operation in industrial environments.
- 2Compact Design: Electronic module without lower part of housing for space-saving installations.
- 3Versatile Applications: Suitable for a wide range of industrial applications requiring direct starters.
- 4Easy Installation: Simple integration with existing systems due to standard terminal strip connections.
- 5Durable Construction: Built with high-quality materials to withstand harsh industrial conditions.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
EMC note | EMC: class A product, see manufacturer's declaration in the download area | Type | Stand-Alone |
Type | Electromechanical motor starter | Diagnostics messages | Mains failure, phase failure Error message in the diagnostic code (bus) and display via the LED ERR on the module
Motor connector not plugged in, motor temperature exceeded, thermistor line short-circuited Error message in the diagnostic code (bus) and display via the LED ERR on the module
Sensor supply failure Error message in the diagnostic code (bus) and display via the LED ERR on the module
Overcurrent Error message in the diagnostic code (bus) and display via the LED ERR on the module
Output stage cannot be controlled Error message in the diagnostic code (bus) and display via the LED ERR on the module
Module error during self test Message to the master |
Connection method | POWER-COMBICON | Designation | Terminal strip X13 and X15 |
Number of positions | 2 | Pg screw connection | Pg11 |
Supply voltage | 24 V DC (U | Supply voltage range | 20 V DC ... 30 V DC (including ripple) |
Supply current | typ. 0.11 A (at U | Ripple | Permissible ripple 3.6 V |
Max. current carrying capacity | 16 A | Derating | Above 30°C: 0.1 A/ K (at 4 mm²), above 30°C: 0.3 A/ K (at 1.5 mm²) |
Test voltage: Incoming/outgoing remote bus | 350 V AC, 50 Hz, 1 min | Test voltage: Remote bus / supply voltage U | 350 V AC, 50 Hz, 1 min |
Test voltage: Between supply voltages | 350 V AC, 50 Hz, 1 min | Number of inputs | 4 |
Connection method | MINI COMBICON | Connection technology | 3-, 4-conductor |
Number of positions | 10 | Input voltage | 24 V DC (U |
Input voltage range "0" signal | -30 V ... 5 V (binary "0") | Input voltage range "1" signal | 13 V ... 30 V (binary "1") |
Filter time | 3 ms | Typical input current per channel | approx. 5 mA (for U |
Connection method | MINI COMBICON | Designation connection point | X30 (IN) and X31 (OUT) |
Number of positions | 10 | Permissible conductor cross section | max. 1.5 mm² |
Diagnostics | Mains failure, phase failure | Message | Error message in the diagnostic code (bus) and display via the LED ERR on the module |
Diagnostics | Motor connector not plugged in, motor temperature exceeded, thermistor line short-circuited | Message | Error message in the diagnostic code (bus) and display via the LED ERR on the module |
Diagnostics | Sensor supply failure | Message | Error message in the diagnostic code (bus) and display via the LED ERR on the module |
Diagnostics | Overcurrent | Message | Error message in the diagnostic code (bus) and display via the LED ERR on the module |
Diagnostics | Output stage cannot be controlled | Message | Error message in the diagnostic code (bus) and display via the LED ERR on the module |
Diagnostics | Module error during self test | Message | Message to the master |
Width | 384 mm | Height | 182 mm |
Depth | 100 mm | Drill hole spacing | 360 mm |
Note on dimensions | Module electronics without lower part | Drill hole spacing | 360 mm |
Degree of protection | IP67 | Ambient temperature (operation) | -20 °C ... 55 °C (non-condensing) |
Note | Notes on operation Line protection for the network supply line, max. 20 A. Observe derating of the POWER-COMBICON connector
Notes on operation Permitted network type TN network, TT network, IT network available on request | Air pressure (operation) | 86 kPa ... 106 kPa (up to 2000 m above sea level) |
Air pressure (storage/transport) | 86 kPa ... 106 kPa (up to 2000 m above sea level) | Ambient temperature (storage/transport) | -25 °C ... 75 °C |
Permissible humidity (operation) | 4 % ... 100 % (non-condensing) | Permissible humidity (storage/transport) | 75 % (slight temporary condensation may sometimes appear on the housing) |
Protection class | I (IEC 61140, EN 61140, VDE 0140-1) | Noise emission | Test of emitted interference, housing, in acc. with EN 50081-2:1993 EN 55011:1991 class A |
Air clearances and creepage distances | in accordance with EN 50178: 1998 | Mounting type | Wall mounting |
Specifications may be subject to change without notice