Product Model

IBS IP 400 ME-MLR 2-8A DI4F

In Stock
Last updated: 2025/4/22
Phoenix Contact IBS IP 400 ME-MLR 2-8A DI4F

Selling Points

  • 1Highly Reliable Performance: Designed for consistent and reliable operation in industrial environments.
  • 2Compact Design: Electronic module without lower part of housing for space-saving installations.
  • 3Versatile Applications: Suitable for a wide range of industrial applications requiring direct starters.
  • 4Easy Installation: Simple integration with existing systems due to standard terminal strip connections.
  • 5Durable Construction: Built with high-quality materials to withstand harsh industrial conditions.
Product Details
IBS IP 400 ME-MLR 2-8A DI4F
Phoenix Contact

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
EMC note
EMC: class A product, see manufacturer's declaration in the download area
Type
Stand-Alone
Type
Electromechanical motor starter
Diagnostics messages
Mains failure, phase failure Error message in the diagnostic code (bus) and display via the LED ERR on the module Motor connector not plugged in, motor temperature exceeded, thermistor line short-circuited Error message in the diagnostic code (bus) and display via the LED ERR on the module Sensor supply failure Error message in the diagnostic code (bus) and display via the LED ERR on the module Overcurrent Error message in the diagnostic code (bus) and display via the LED ERR on the module Output stage cannot be controlled Error message in the diagnostic code (bus) and display via the LED ERR on the module Module error during self test Message to the master
Connection method
POWER-COMBICON
Designation
Terminal strip X13 and X15
Number of positions
2
Pg screw connection
Pg11
Supply voltage
24 V DC (U
Supply voltage range
20 V DC ... 30 V DC (including ripple)
Supply current
typ. 0.11 A (at U
Ripple
Permissible ripple 3.6 V
Max. current carrying capacity
16 A
Derating
Above 30°C: 0.1 A/ K (at 4 mm²), above 30°C: 0.3 A/ K (at 1.5 mm²)
Test voltage: Incoming/outgoing remote bus
350 V AC, 50 Hz, 1 min
Test voltage: Remote bus / supply voltage U
350 V AC, 50 Hz, 1 min
Test voltage: Between supply voltages
350 V AC, 50 Hz, 1 min
Number of inputs
4
Connection method
MINI COMBICON
Connection technology
3-, 4-conductor
Number of positions
10
Input voltage
24 V DC (U
Input voltage range "0" signal
-30 V ... 5 V (binary "0")
Input voltage range "1" signal
13 V ... 30 V (binary "1")
Filter time
3 ms
Typical input current per channel
approx. 5 mA (for U
Connection method
MINI COMBICON
Designation connection point
X30 (IN) and X31 (OUT)
Number of positions
10
Permissible conductor cross section
max. 1.5 mm²
Diagnostics
Mains failure, phase failure
Message
Error message in the diagnostic code (bus) and display via the LED ERR on the module
Diagnostics
Motor connector not plugged in, motor temperature exceeded, thermistor line short-circuited
Message
Error message in the diagnostic code (bus) and display via the LED ERR on the module
Diagnostics
Sensor supply failure
Message
Error message in the diagnostic code (bus) and display via the LED ERR on the module
Diagnostics
Overcurrent
Message
Error message in the diagnostic code (bus) and display via the LED ERR on the module
Diagnostics
Output stage cannot be controlled
Message
Error message in the diagnostic code (bus) and display via the LED ERR on the module
Diagnostics
Module error during self test
Message
Message to the master
Width
384 mm
Height
182 mm
Depth
100 mm
Drill hole spacing
360 mm
Note on dimensions
Module electronics without lower part
Drill hole spacing
360 mm
Degree of protection
IP67
Ambient temperature (operation)
-20 °C ... 55 °C (non-condensing)
Note
Notes on operation Line protection for the network supply line, max. 20 A. Observe derating of the POWER-COMBICON connector Notes on operation Permitted network type TN network, TT network, IT network available on request
Air pressure (operation)
86 kPa ... 106 kPa (up to 2000 m above sea level)
Air pressure (storage/transport)
86 kPa ... 106 kPa (up to 2000 m above sea level)
Ambient temperature (storage/transport)
-25 °C ... 75 °C
Permissible humidity (operation)
4 % ... 100 % (non-condensing)
Permissible humidity (storage/transport)
75 % (slight temporary condensation may sometimes appear on the housing)
Protection class
I (IEC 61140, EN 61140, VDE 0140-1)
Noise emission
Test of emitted interference, housing, in acc. with EN 50081-2:1993 EN 55011:1991 class A
Air clearances and creepage distances
in accordance with EN 50178: 1998
Mounting type
Wall mounting

Specifications may be subject to change without notice