Product Model

IBS RL 24 DO 8/8-2A-LK-2MBD

In Stock
Last updated: 2025/4/27
Phoenix Contact IBS RL 24 DO 8/8-2A-LK-2MBD

Selling Points

  • 1Rugged metal housing with IP67 protection for harsh ambient conditions.
  • 2Fiber optic technology with 2 Mbaud transmission speed.
  • 3Extended diagnostic functions for clear fault localization.
  • 45-pos. M12 female connectors for sensor/actuator connections.
  • 58 outputs with 24V DC, 2A each, suitable for various applications.
Product Details
IBS RL 24 DO 8/8-2A-LK-2MBD
Phoenix Contact

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Width
179 mm
Height
67 mm
Depth
71 mm
Note on dimensions
with bus connection plugs and mounting panel
Connection method
Optic fiber (polymer fiber 980/1000 µm)
Transmission speed
2 Mbps
Transmission physics
FO
Output name
Digital outputs
Connection technology
2-, 3-conductor
Number of outputs
8
Protective circuit
Electronic short-circuit/overload protection for each channel
Output voltage
24 V DC
Maximum output current per channel
2 A
Maximum output current per module
4 A
Nominal output voltage
24 V DC
Output voltage when switched off
max. 500 mV
Output current when switched off
0 mA
Nominal load, inductive
48 VA (1,2 H, 12 Ω)
Nominal load, lamp
48 W
Nominal load, ohmic
48 W
Reverse voltage resistance to short pulses
Limited protection against reverse voltages up to 3 A DC
Behavior with overload
Auto restart
Behavior with inductive overload
Output can be destroyed
Overcurrent shut-down
min. 2.6 A
Output current with ground connection interrupt when switched off
0 mA
Product type
I/O component
Product family
Ruggedline
Type
Block design
No. of channels
8
Supply voltage
24 V DC
Supply voltage range
18.5 V DC ... 32 V DC (including ripple)
Supply current
typ. 120 mA
Ripple
Max 3.6 V
Test voltage: Between bus logic and outputs
500 V AC, 50 Hz, 1 min
Connection method
Fiber optic
Ambient temperature (operation)
-20 °C ... 55 °C
Degree of protection
IP65/IP67
Note
Seal unused slots/connections to ensure the degree of protection.
Air pressure (operation)
860 hPa ... 1080 hPa (up to 1500 m above sea level)
Air pressure (storage/transport)
660 hPa ... 1080 hPa (up to 3500 m above sea level)
Ambient temperature (storage/transport)
-25 °C ... 70 °C
Permissible humidity (operation)
100 %
Permissible humidity (storage/transport)
95 % (non-condensing)
Mounting type
Wall mounting

Specifications may be subject to change without notice