Product Model

IBS RL 400 MLR R DIO6/1 LK2MBD

In Stock
Last updated: 2025/4/23
Phoenix Contact IBS RL 400 MLR R DIO6/1 LK2MBD

Selling Points

  • 1Rugged Metal Housing: Durable and resistant to harsh environments with IP67 protection.
  • 2Fiber Optic Technology: High-speed transmission at 2 Mbaud for reliable communication.
  • 3Comprehensive Diagnostics: Real-time monitoring of motor current and error messages via E LED.
  • 4Integrated Motor Protection Relay: Safeguards against overcurrents and short circuits up to 440 V AC.
  • 5Versatile Connectivity: Supports 24 V DC inputs and M12 connectors for digital inputs and outputs.
Product Details
IBS RL 400 MLR R DIO6/1 LK2MBD
Phoenix Contact

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Width
185.1 mm
Height
193 mm
Depth
138 mm
Connection method
Fiber optics
Transmission speed
2 Mbps
ID code (dec.)
3
ID code (hex)
03
Length code (hex)
01
Length code (dec)
1
Process data channel
16 bit
Input address area
2 Byte
Output address area
2 Byte
Register length
2 Byte
Number of inputs
6
Connection method
M12 connector
Connection technology
3-, 4-conductor
Number of positions
5
Input voltage
24 V DC (DIN EN 61131-2)
Input voltage range "0" signal
0 V ... 5 V
Input voltage range "1" signal
11 V ... 30 V
Filter time
3 ms
Typical input current per channel
5 mA (for U
Product type
I/O component
Product family
Ruggedline
Type
Block design
Diagnostics messages
Mains failure, phase failure, blown fuse Error message in diagnostic code (bus) and display by means of the E LED on the motor starter Motor connector not plugged in, motor temperature exceeded, thermistor line short-circuited Error message in diagnostic code (bus) and display by means of the E LED on the motor starter Sensor supply failure Error message in diagnostic code (bus) and display by means of the E LED on the motor starter Failure of the actuator supply Error message in diagnostic code (bus) and display by means of the E LED on the motor starter Motor overcurrent Error message in diagnostic code (bus) and display by means of the E LED on the motor starter Output stage cannot be controlled Error message in diagnostic code (bus) and display by means of the E LED on the motor starter Module error during self test Message to the master
Supply voltage
24 V DC
Supply voltage range
18.5 V DC ... 32 V DC (including ripple)
Ripple
3.6 V
Connection method
M12 connector
Degree of protection
IP65/IP67
Ambient temperature (operation)
0 °C ... 55 °C
Air pressure (operation)
860 hPa ... 1080 hPa (up to 1500 m above sea level)
Air pressure (storage/transport)
660 hPa ... 1080 hPa (up to 3500 m above sea level)
Ambient temperature (storage/transport)
-25 °C ... 70 °C
Permissible humidity (operation)
100 %
Permissible humidity (storage/transport)
95 % (non-condensing)
Protection class
I (IEC 61140, EN 61140, VDE 0140-1)
Air clearances and creepage distances
in accordance with EN 50178: 1998
Mounting type
on mounting panel Wall mounting

Specifications may be subject to change without notice