Selling Points

  • 1High-Performance Digital I/O: 8 digital inputs and 8 digital outputs for seamless data transfer.
  • 2Versatile Connectivity: Compatible with screw-cage terminal blocks and FLK connectors for flexible installation.
  • 3Robust Design: IP20 protection ensures reliable operation in harsh environments.
  • 4Fast Response Time: Typical response time of ≥ 1 ms for efficient data processing.
  • 5Durable Construction: Built to withstand ambient temperatures from 0°C to 55°C and humidity levels up to 85%.
Product Details
IBS ST 24 BK DIO 8/8/3-T
Phoenix Contact

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Width
118 mm
Height
117 mm
Depth
116 mm
Color
green
Connection method
9-pos. D-SUB plug/socket
Designation connection point
Incoming/Outgoing Remote Bus
Number of positions
9
Connection method
ST local bus connector
Transmission speed
500 kbps
Max. number of local bus devices
max. 4
Input name
Digital inputs
Number of inputs
8
Connection method
Screw-cage terminal blocks or FLK connectors
Connection technology
3-conductor
Input voltage
24 V DC
Input voltage range "0" signal
-30 V DC ... 5 V DC
Input voltage range "1" signal
13 V DC ... 30 V DC
Nominal input current at U
typ. 5 mA (per channel)
Typical response time
≥ 1 ms (typical)
Protective circuit
Overload protection; Fuse in header
Output name
Digital outputs
Connection method
Screw-cage terminal blocks or FLK connectors
Connection technology
3-conductor
Number of outputs
8
Protective circuit
Short-circuit protection; electronic Overload protection; Fuse in header
Maximum output current per group
2 A
Maximum output current per channel
500 mA
Maximum output current per module / terminal block
4 A
Maximum operating frequency with ohmic nominal load
max. 150 Hz (48 Ω)
Product type
I/O component
Product family
Smart Terminal ST
Type
modular INTERBUS Smart Terminal
Mounting position
Horizontal DIN rail
No. of channels
16
Supply voltage
24 V DC
Supply voltage range
18.5 V DC ... 30.5 V DC (including ripple)
Current consumption
typ. 150 mA
Ripple
3.6 V
Test voltage: Incoming remote bus / Outgoing remote bus
500 V AC, 50 Hz, 1 min
Test voltage: Incoming remote bus / I/O interface
500 V AC, 50 Hz, 1 min
Test voltage: Incoming remote bus/ST interface
500 V AC, 50 Hz, 1 min
Connection name
Terminal block
Connection method
Screw connection
Conductor cross section rigid
0.2 mm² ... 2.5 mm²
Conductor cross section flexible
0.2 mm² ... 2.5 mm²
Conductor cross section AWG
24 ... 12
Stripping length
8 mm
Connection method
Screw connection
Conductor cross section, rigid
0.2 mm² ... 2.5 mm²
Conductor cross section, flexible
0.2 mm² ... 2.5 mm²
Conductor cross section AWG
24 ... 12
Stripping length
8 mm
Ambient temperature (operation)
0 °C ... 55 °C
Degree of protection
IP20
Air pressure (operation)
80 kPa ... 106 kPa (up to 2000 m above sea level)
Air pressure (storage/transport)
80 kPa ... 106 kPa (up to 2000 m above sea level)
Ambient temperature (storage/transport)
-25 °C ... 70 °C
Permissible humidity (operation)
75 % (on average, 85% infrequently, non-condensing)
Permissible humidity (storage/transport)
75 % (on average, 85% infrequently, non-condensing)
Protection class
III (IEC 61140, EN 61140, VDE 0140-1)
Mounting type
DIN rail mounting
Mounting position
Horizontal DIN rail

Specifications may be subject to change without notice