Product Model

ILB BT ADIO MUX-OMNI

In Stock
Last updated: 2025/4/18
Phoenix Contact ILB BT ADIO MUX-OMNI

Selling Points

  • 1Transmits 16 digital and 2 analog signals bidirectionally.
  • 2Supplied ready to use; unpack, connect, switch on, and start.
  • 3Designed for industrial use with robust EMC compliance (Class A).
  • 4MTTF (Mean Time To Failure) of 219 years at 40°C with 34.25% operating cycle.
  • 5Includes diagnostic LEDs for short-circuit detection, link quality, and more.
Product Details
ILB BT ADIO MUX-OMNI
Phoenix Contact

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Note on application
Only for industrial use
EMC note
EMC: class A product, see manufacturer's declaration in the download area
Product type
Wireless module
Product family
Inline
Application
I/O
Type
Block design
MTTF
1458 Years (SN 29500 standard, temperature 25°C, operating cycle 21%) 557 Years (SN 29500 standard, temperature 40°C, operating cycle 34.25%) 219 Years (SN 29500 standard, temperature 40°C, operating cycle 100%)
MTBF
465 Years (Telcordia standard, 25°C temperature, 21% operating cycle (5 days a week, 8 hours a day)) 140 Years (Telcordia standard, 40°C temperature, 34.25% operating cycle (5 days a week, 12 hours a day))
Diagnostics messages
Short-circuit or overload of the digital outputs LED Wireless connection FS LED Logic and actuator voltage LED Link quality of the wireless connection 4 LEDs
Article revision
12
Overvoltage category
II
Pollution degree
2
Switch-on time
≤ 3 s (Until the wireless connection is established)
Delay time
≤ 10 ms (Latency, typical) ≤ 800 ms (Failsafe function for wireless interruption)
Maximum power dissipation for nominal condition
2.4 W
Connection method
Inline connector
Supply voltage
24 V DC
Supply voltage range
19.2 V DC ... 30.5 V DC (via power connector)
Current consumption
60 mA (Communications power at 24 V DC, 25 °C) 25 mA (Actuator supply, +load current Digital OUT (8 A))
Protective circuit
Polarity protection, surge protection
Input name
Analog inputs
Description of the input
Single ended
Number of inputs
2
Current input signal
0 mA ... 20 mA
Input resistance current input
50 Ω
Voltage input signal
0 V ... 10 V
Input resistance of voltage input
130 kΩ
Measured value resolution
12 bits
Protective circuit
Surge voltage; Suppressor diodes in the analog inputs, current limitation via internal protective circuit
Input name
Digital inputs
Number of inputs
16
Connection method
Spring-cage connection
Connection technology
1-conductor
Input voltage range "0" signal
< 5 V
Input voltage range "1" signal
> 15 V
Nominal input voltage U
24 V DC
Typical input current per channel
2.3 mA
Input frequency
≤ 10 Hz
Output name
Analog outputs
Number of outputs
2
Protective circuit
Transient protection
DAC resolution
12 bit
Current output signal
0 mA ... 20 mA
Load/output load current output
≤ 500 Ω
Voltage output signal
0 V ... 10 V
Load/output load voltage output
≥ 2 kΩ
Output name
Digital outputs
Connection method
Spring-cage connection
Connection technology
1-conductor
Number of outputs
16
Protective circuit
Short-circuit protection, overload protection, protected against reverse voltages
Output current
8 A (Total)
Maximum output current per channel
500 mA
Nominal output voltage
24 V DC
Output current when switched off
≤ 10 µA (When not loaded, a voltage can be measured even at an output that is not set.)
Nominal load, inductive
12 VA (1.2 H, 50 Ω)
Nominal load, lamp
12 W
Nominal load, ohmic
12 W (48 Ω)
Reverse voltage resistance to short pulses
Reverse voltage proof
Behavior with overload
Auto restart
Behavior with inductive overload
Output can be destroyed
Behavior at voltage switch-off
The output follows the power supply without delay
Overcurrent shut-down
≥ 0.7 A
Conductor cross section, rigid
0.2 mm² ... 1.5 mm²
Conductor cross section, flexible
0.2 mm² ... 1.5 mm²
Conductor cross section, flexible [AWG]
... 16
Stripping length
8 mm
Wireless licenses
Europe, USA, Canada, additional countries in the e-shop
Modulation type
GFSK (Gaussian Frequency Shift Keying)
Antenna connection method
RSMA (female)
No. of channels
40
Frequency range
2.402 GHz ... 2.48 GHz (ISM bandwidth)
Frequency band
2.4 GHz
Wireless standard
Bluetooth
Transmission power
5 dBm
Receiver sensitivity
-95.00 dBm
Diagnostics
Short-circuit or overload of the digital outputs
Message
LED
Diagnostics
Wireless connection
Message
FS LED
Diagnostics
Logic and actuator voltage
Message
LED
Diagnostics
Link quality of the wireless connection
Message
4 LEDs
Width
95 mm
Height
123.4 mm
Depth
57 mm
Note on dimensions
with connectors
Color (Housing)
green (RAL 6021)
Material (Housing)
PA 6.6-FR
Ambient temperature (operation)
-25 °C ... 60 °C
Degree of protection
IP20
Air pressure (operation)
795 hPa ... 1080 hPa (up to 2000 m above sea level)
Air pressure (storage/transport)
66 kPa ... 108 kPa (up to 3500 m above sea level)
Ambient temperature (storage/transport)
-25 °C ... 85 °C
Permissible humidity (operation)
95 % (non-condensing)
Permissible humidity (storage/transport)
95 %
Certificate
CE-compliant
Identification
508 Listed
Note
RED 2014/53/EU
Identification
YG3ADIOMUX
Note
FCC directive, part 15.247
Certificate
NR-ETA/5957
Identification
Japan MIC (RF) ID:202-LSF002
Certificate
4720B-ADIOMUX
Note
ISC directive RSS 210
Certificate
IFT RCPPHIL19-2130
Certificate
TA-2006/032
Certificate
MSIP-CRI-PCK-2884208
Electromagnetic compatibility
Conformance with EMC Directive 2014/30/EU
Standards/regulations
EN 61000-4-2
Contact discharge
± 6 kV (Test Level 3)
Discharge in air
± 8 kV (Test Level 3)
Indirect discharge
± 6 kV
Comments
Criterion B
Standards/regulations
EN 61000-4-3
Frequency range
26 MHz ... 3 GHz (Test Level 3)
Field intensity
10 V/m
Comments
Criterion A
Standards/regulations
EN 61000-4-4
Input
± 2 kV (Test Level 3)
Signal
± 2 kV (Signal line)
Comments
Criterion B
Standards/regulations
EN 61000-4-5
Input
± 0.5 kV (symmetrical) ± 1 kV (asymmetrical)
Signal
± 1 kV (Signal line, asymmetrical)
Comments
Criterion B
Standards/regulations
EN 61000-4-6
Frequency range
0.15 MHz ... 80 MHz
Comments
Criterion A
Voltage
10 V
Emitted radio interference in acc. with EN 55011
EN 55016-2-3 Class A industrial applications
Criterion A
Normal operating behavior within the specified limits.
Criterion B
Temporary impairment to operational behavior that is corrected by the device itself.
Protection class
III
Free from substances that could impair the application of coating
VDMA 24364:2018-05
Standard designation
RED directive 2014/53/EU
Standards/specifications
EN 300328 EN 61000-6-4 EN 61000-6-2 EN 62311 EN 60950
Mounting type
DIN rail mounting

Specifications may be subject to change without notice