Product Model
ILB IB 24 DI32

Selling Points
- 1High-Reliability Design: Built with robust components for long-lasting performance in harsh industrial environments.
- 232 Digital Inputs: Supports up to 32 digital inputs for comprehensive data collection and processing.
- 324 V DC Power Supply: Operates on a stable 24 V DC power supply, ensuring consistent performance.
- 4Wide Operating Temperature Range: Functions between -25 °C and 60 °C, suitable for various industrial settings.
- 5IP20 Protection Class: Ensures protection against solid particles and water spray, meeting industrial standards.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Width | 156 mm | Height | 141 mm |
Depth | 57 mm | Note on dimensions | Specfications with connectors |
Color | green | Connection method | Inline shield connector |
Transmission speed | 500 kbps | Input name | Digital inputs |
Description of the input | EN 61131-2 type 1 | Number of inputs | 32 |
Connection method | Spring-cage connection | Connection technology | 3-conductor |
Input voltage | 24 V DC | Input voltage range "0" signal | -30 V DC ... 5 V DC |
Input voltage range "1" signal | 15 V DC ... 30 V DC | Nominal input voltage U | 24 V DC |
Nominal input current at U | 5 mA | Total sensor current | max. 4 A |
Typical response time | approx. 500 µs | Protective circuit | Short-circuit protection, overload protection of the sensor supply |
Product type | I/O component | Product family | Inline |
Type | Block design | Scope of delivery | including Inline connector |
No. of channels | 32 | Supply voltage | 24 V DC |
Supply voltage range | 19.2 V DC ... 30 V DC (including all tolerances, including ripple) | Current draw | 60 mA |
Supply voltage | 24 V DC | Supply voltage range | 19.2 V DC ... 30 V DC (including all tolerances, including ripple) |
Current draw | 2 A | Supply voltage | 24 V DC |
Supply voltage range | 19.2 V DC ... 30 V DC (including all tolerances, including ripple) | Current draw | 2 A |
Current draw | 60 mA | Test voltage: I/Os / incoming remote bus | 500 V AC, 50 Hz, 1 min |
Test voltage: I/Os / outgoing remote bus | 500 V AC, 50 Hz, 1 min | Test voltage: I/O area / FE | 500 V AC, 50 Hz, 1 min |
Test voltage: Incoming remote bus / FE | 500 V AC, 50 Hz, 1 min | Test voltage: Outgoing remote bus / FE | 500 V AC, 50 Hz, 1 min |
Test voltage: Incoming remote bus / outgoing remote bus | 500 V AC, 50 Hz, 1 min | Connection name | Inline connector |
Connection method | Spring-cage connection | Conductor cross section rigid | 0.08 mm² ... 1.5 mm² |
Conductor cross section flexible | 0.08 mm² ... 1.5 mm² | Conductor cross section AWG | 28 ... 16 |
Stripping length | 8 mm | Connection method | Spring-cage connection |
Conductor cross section, rigid | 0.08 mm² ... 1.5 mm² | Conductor cross section, flexible | 0.08 mm² ... 1.5 mm² |
Conductor cross section AWG | 28 ... 16 | Stripping length | 8 mm |
Ambient temperature (operation) | -25 °C ... 60 °C | Degree of protection | IP20 |
Air pressure (operation) | 80 kPa ... 108 kPa (up to 2000 m above sea level) | Air pressure (storage/transport) | 66 kPa ... 108 kPa (up to 3500 m above sea level) |
Ambient temperature (storage/transport) | -25 °C ... 85 °C | Permissible humidity (operation) | max. 85 % (non-condensing) |
Permissible humidity (storage/transport) | 95 % (non-condensing) | Protection class | III (IEC 61140, EN 61140, VDE 0140-1) |
Noise emission | Class B (residential) | Mounting type | DIN rail mounting |
Specifications may be subject to change without notice