Selling Points

  • 116 Digital Inputs & Outputs: The module offers 16 digital inputs and 16 digital outputs, making it versatile for various industrial applications.
  • 224V DC Operation: Operates at 24V DC, ensuring reliable performance in industrial environments.
  • 33-Wire Connection Technology: Supports both 2 and 3-wire connection technologies for flexible sensor and actuator connections.
  • 4IP20 Protection: Compliant with IP20 protection standards, ensuring safety in harsh industrial conditions.
  • 5Diagnostic Capabilities: Includes diagnostic and status indicators for easy monitoring and troubleshooting.
Product Details
ILB PB 24 DI16 DO16
Phoenix Contact

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Width
156 mm
Height
141 mm
Depth
57 mm
Note on dimensions
Specfications with connectors
CCCex note
Use in potentially explosive areas is not permitted in China.
Connection method
D-SUB-9 female connector
Number of positions
9
Transmission speed
9.6 kbps ... 12 Mbps
Input name
Digital inputs
Description of the input
EN 61131-2 type 1
Number of inputs
16
Connection method
Spring-cage connection
Connection technology
3-conductor
Input voltage
24 V DC
Input voltage range "0" signal
-30 V DC ... 5 V DC
Input voltage range "1" signal
15 V DC ... 30 V DC
Nominal input voltage U
24 V DC
Nominal input current at U
5 mA
Total sensor current
max. 2 A
Typical response time
approx. 500 µs
Protective circuit
Short-circuit protection, overload protection of the sensor supply
Output name
Digital outputs
Connection method
Spring-cage connection
Connection technology
3-conductor
Number of outputs
16
Protective circuit
Short-circuit and overload protection
Output voltage
24 V DC
Maximum output current per channel
500 mA
Maximum output current per module / terminal block
8 A
Maximum output current per module
8 A
Nominal output voltage
24 V DC
Nominal load, inductive
12 VA
Nominal load, lamp
12 W
Nominal load, ohmic
12 W
Product type
I/O component
Product family
Inline
Type
Block design
Scope of delivery
including Inline connector
No. of channels
32
Diagnostics messages
Short-circuit or overload of the digital outputs Message in the diagnostics register Short-circuit, sensor supply Message in the diagnostics register Undervoltage Power supply for sensors Message in the diagnostics register
Supply voltage
24 V DC
Supply voltage range
19.2 V DC ... 30 V DC (including all tolerances, including ripple)
Current draw
70 mA
Current draw
2 A
Supply voltage
24 V DC
Supply voltage range
19.2 V DC ... 30 V DC (including all tolerances, including ripple)
Current draw
4 A
Supply voltage
24 V DC
Supply voltage range
19.2 V DC ... 30 V DC (including all tolerances, including ripple)
Current draw
4 A
Current draw
70 mA
Current draw
2 A
Test voltage: I/Os / PROFIBUS
500 V AC, 50 Hz, 1 min
Test voltage: I/O area / FE
500 V AC, 50 Hz, 1 min
Test voltage: PROFIBUS / FE
500 V AC, 50 Hz, 1 min
Connection name
Inline connector
Connection method
Spring-cage connection
Conductor cross section rigid
0.08 mm² ... 1.5 mm²
Conductor cross section flexible
0.08 mm² ... 1.5 mm²
Conductor cross section AWG
28 ... 16
Stripping length
8 mm
Connection method
Spring-cage connection
Conductor cross section, rigid
0.08 mm² ... 1.5 mm²
Conductor cross section, flexible
0.08 mm² ... 1.5 mm²
Conductor cross section AWG
28 ... 16
Stripping length
8 mm
Ambient temperature (operation)
-25 °C ... 60 °C
Degree of protection
IP20
Air pressure (operation)
80 kPa ... 108 kPa (up to 2000 m above sea level)
Air pressure (storage/transport)
66 kPa ... 108 kPa (up to 3500 m above sea level)
Ambient temperature (storage/transport)
-25 °C ... 85 °C
Permissible humidity (operation)
85 % (non-condensing)
Permissible humidity (storage/transport)
95 % (non-condensing)
Noise emission
Industrial environment
Mounting type
NS 35/7,5 DIN rail mounting

Specifications may be subject to change without notice