Product Model
ILC 350 ETH

Selling Points
- 1Highly modular design for flexible application adaptation.
- 2Integrated Ethernet interface for parameterization and programming using PC WorX.
- 3Supports numerous protocols including HTTP, FTP, SNTP, SNMP, SMTP, SQL, and MySQL.
- 4Complete fieldbus master with 8192 I/O points and FTP server.
- 5Maritime approval and GL approval for diverse application environments.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Product type | Controller | Product family | Inline |
Type | Inline format with alignable I/Os | Diagnostics display | no |
Retentive data storage | 64 kByte (NVRAM) | Program memory | typ. 1 Mbyte |
Data storage system | 2 Mbyte | Number of control tasks | 16 |
Amount of process data | max. 8192 bit (INTERBUS) | Number of supported devices | max. 512 (in total, of which 254 are remote bus devices/bus segments) |
Number of local bus devices that can be connected | max. 63 (observe current consumption) | Number of devices with parameter channel | max. 62 |
Number of supported branch terminals with remote bus branch | 15 | Diagnostics display | no |
Controller redundancy | no | Designation | LNK, ACT, 100 |
Monitored function | Higher-level network | Optical representation | LED |
Engineering tool | PC Worx | Diagnostics tool | DIAG+ from version 1.14 |
Local diagnostics | LNK, ACT, 100 Higher-level network LED
FC RUN, FAIL IEC 61131 runtime system LED
RDY/RUN, BSA, FAIL, PF INTERBUS master LED | Transmission medium | Copper |
Maximum power dissipation for nominal condition | max. 6 W | Supply voltage | 24 V DC ±5 % |
Supply voltage range | 20.4 V DC ... 30 V DC | Residual ripple | ± 5 % |
Typical current consumption | 250 mA (no local bus device connected during idling, bus inactive) | Realtime clock | Integrated (battery backup) |
Supply voltage | 7.5 V DC ±5 % | Supply voltage | 24 V DC -15 % / +20 % |
Supply voltage | 24 V DC -15 % / +20 % (in accordance with EN 61131-2) | Current draw | max. 8 A DC |
Supply voltage | 24 V DC -15 % / +20 % (in accordance with EN 61131-2) | Current draw | max. 5 A |
Input name | Digital inputs | Description of the input | Eight fast inputs, interrupt input |
Number of inputs | 12 | Connection method | Inline potential distributor |
Connection technology | 2-, 3-, 4-conductor | Output name | Digital outputs |
Connection method | Spring-cage connection | Connection technology | 2-, 3-, 4-conductor |
Number of outputs | 4 | Output voltage | 24 V DC |
Maximum output current per channel | 500 mA | Connection method | Spring-cage connection |
Conductor cross section, rigid | 0.08 mm² ... 1.5 mm² | Conductor cross section, flexible | 0.08 mm² ... 1.5 mm² |
Conductor cross section AWG | 28 ... 16 | Number of interfaces | 1 |
Connection method | Inline data jumper | Transmission speed | 500 kBaud / 2 MBaud (can be switched) |
Bus system | RS-232 | Connection method | 6-pos. MINI DIN socket (PS/2) |
Transmission speed | max. 38.4 kbps | Transmission physics | Copper |
No. of channels | 1 | Bus system | RJ45 |
Number of interfaces | 1 | Connection method | RJ45 jack |
Transmission speed | 10/100 Mbps | No. of channels | 1 |
Width | 182 mm | Height | 140.5 mm |
Depth | 71.5 mm | Color | green (RAL 6021) |
Degree of protection | IP20 | Ambient temperature (operation) | -25 °C ... 55 °C |
Ambient temperature (storage/transport) | -25 °C ... 85 °C | Permissible humidity (operation) | 10 % ... 95 % (non-condensing) |
Permissible humidity (storage/transport) | 10 % ... 95 % (non-condensing) | Shock | 25g, Criterion 1, according to IEC 60068-2-27 |
Vibration (operation) | 5g, accordance to IEC 60068-2-6 | Air pressure (operation) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
Air pressure (storage/transport) | 70 kPa ... 106 kPa (up to 3000 m above sea level) | Mounting type | DIN rail mounting |
Specifications may be subject to change without notice