Product Model

IL IB BK-PAC

In Stock
Last updated: 2025/4/19
Phoenix Contact IL IB BK-PAC

Selling Points

  • 1Efficient Inline Connectivity: Connects up to 63 Inline devices seamlessly.
  • 2High-Speed Transmission: Supports transmission speeds of 500 kbps.
  • 3Robust Protection: Features IP20 degree of protection for reliable operation.
  • 4Versatile Power Supply: Supplies 24 V DC voltage range (19.2 V DC to 30 V DC) for various applications.
  • 5Diagnostic Indicators: Includes diagnostic and status indicators for easy monitoring and troubleshooting.
Product Details
IL IB BK-PAC
Phoenix Contact

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Width
48.8 mm
Height
135 mm
Depth
71.5 mm
Note on dimensions
Housing dimensions
Color
green
No. of channels
2
Connection method
Inline shield connector
Transmission speed
500 kbps
Transmission physics
Copper
Connection method
Inline data jumper
Transmission speed
500 kbps
Number of local bus devices that can be connected
63
Number of devices with parameter channel
62
Number of supported branch terminals with remote bus branch
0 (A terminal with remote bus branch cannot be used.)
ID code (dec.)
04
ID code (hex)
04
Length code (hex)
00
Length code (dec)
00
Process data channel
0 bit
Input address area
0 Byte
Output address area
0 Byte
Register length
0 bit
Product type
I/O component
Product family
Inline
Type
modular
Scope of delivery
including Inline connectors and marking fields
Supply voltage
24 V DC (via Inline connector)
Supply voltage range
19.2 V DC ... 30 V DC (including all tolerances, including ripple)
Current draw
max. 1.25 A (with max. number of connected I/O terminal blocks) typ. 100 mA (no local bus devices connected)
Supply voltage
7.5 V DC
Supply voltage
24 V DC
Supply voltage range
19.2 V DC ... 30 V DC (including all tolerances, including ripple)
Supply voltage
24 V DC (via Inline connector)
Supply voltage range
19.2 V DC ... 30 V DC (including all tolerances, including ripple)
Supply voltage
24 V DC (via Inline connector)
Supply voltage range
19.2 V DC ... 30 V DC (including all tolerances, including ripple)
Test voltage: 5 V supply, incoming remote bus / 5 V supply outgoing remote bus
500 V AC, 50 Hz, 1 min
Test voltage: 5 V supply incoming remote bus / 7.5 V communications power, 24 V analog supply, 24 V bus coupler supply
500 V AC, 50 Hz, 1 min
Test voltage: 5 V supply, incoming remote bus / 24 V main supply, 24 V segment supply
500 V AC, 50 Hz, 1 min
Test voltage: 5 V supply incoming remote bus / functional ground
500 V AC, 50 Hz, 1 min
Test voltage: 5 V supply outgoing remote bus / I/O (U
500 V AC, 50 Hz, 1 min
Test voltage: 5 V supply outgoing remote bus / communications power (U
500 V AC, 50 Hz, 1 min
Test voltage: 5 V supply outgoing remote bus / functional ground
500 V AC, 50 Hz, 1 min
Test voltage: 7.5 V communications power, 24 V analog supply, 24 V bus coupler supply/functional ground
500 V AC, 50 Hz, 1 min
Test voltage: Communications power (U
500 V AC, 50 Hz, 1 min
Test voltage: 24 V main supply, 24 V segment supply/functional ground
500 V AC, 50 Hz, 1 min
Connection name
Inline connector
Connection method
Spring-cage connection
Conductor cross section rigid
0.09 mm² ... 1.5 mm²
Conductor cross section flexible
0.09 mm² ... 1.5 mm²
Conductor cross section AWG
28 ... 16
Stripping length
8 mm
Connection method
Spring-cage connection
Conductor cross section, rigid
0.09 mm² ... 1.5 mm²
Conductor cross section, flexible
0.09 mm² ... 1.5 mm²
Conductor cross section AWG
28 ... 16
Stripping length
8 mm
Ambient temperature (operation)
-25 °C ... 55 °C
Degree of protection
IP20
Air pressure (operation)
80 kPa ... 106 kPa (up to 3000 m above sea level)
Air pressure (storage/transport)
70 kPa ... 106 kPa (up to 3000 m above sea level)
Ambient temperature (storage/transport)
-25 °C ... 85 °C
Permissible humidity (operation)
75 % ... 85 % (in the range of -25°C ... +55°C, appropriate measures against increased humidity (> 85%) must be taken.)
Permissible humidity (storage/transport)
75 % ... 85 % (Slight temporary condensation may sometimes appear on the housing, e.g. when the terminal block is brought out of a vehicle into an enclosed room.)
Protection class
III (IEC 61140, EN 61140, VDE 0140-1)
Mounting type
DIN rail mounting

Specifications may be subject to change without notice