Product Model
IL PB BK DI8 DO4/EF-XC-PAC

Selling Points
- 1Integrated I/Os: Connects up to 61 Inline devices within a PROFIBUS network.
- 2D-SUB Connector: PROFIBUS connection via 9-pos. D-SUB socket for easy integration.
- 3Extreme Conditions: Operates under extreme ambient conditions, from -40°C to +70°C.
- 4Diagnostic Functions: Includes diagnostic and status indicators for I&M functions.
- 5IO-Link Compatibility: Supports IO-Link call for firmware version 2.0 or later.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Width | 80 mm | Height | 119.8 mm |
Depth | 71.5 mm | Note on dimensions | Specfications with connectors |
Color | green | No. of channels | 1 |
Connection method | D-SUB-9 female connector | Number of positions | 9 |
Transmission speed | 9.6 kbps ... 12 Mbps | Connection method | Inline data jumper |
Transmission speed | 500 kbps / 2 Mbps (automatic detection, no combined system) | Max. number of local bus devices | 61 (The on-board I/Os are two devices) |
Number of supported devices | max. 63 (per station) | Number of local bus devices that can be connected | max. 61 (The on-board I/Os are two devices) |
Number of devices with parameter channel | max. 16 | Number of supported branch terminals with remote bus branch | 0 |
Response time of I/Os | typ. 4 ms (aligned I/Os; transmission speed: PROFIBUS 1.5 Mbps, local bus 500 kbps) | ID code (hex) | 0B50 |
Input address area | 8 bit (or 1 byte, selection in the GSD file) | Output address area | 4 bit (or 1 byte, selection in the GSD file) |
Register length | 16 bit | Input name | Digital inputs |
Description of the input | EN 61131-2 type 1 | Number of inputs | 8 |
Connection method | Inline connector | Connection technology | 3-conductor |
Input voltage | 24 V DC | Input voltage range "0" signal | -30 V DC ... 5 V DC |
Input voltage range "1" signal | 15 V DC ... 30 V DC | Nominal input voltage U | 24 V DC |
Nominal input current at U | typ. 3 mA | Typical input current per channel | typ. 3 mA |
Typical response time | approx. 500 µs | Delay at signal change from 0 to 1 | 2.9 ms |
Delay at signal change from 1 to 0 | 2.9 ms | Protective circuit | Reverse polarity protection; Suppressor diode |
Output name | Digital outputs | Connection method | Inline connector |
Connection technology | 3-conductor | Number of outputs | 4 |
Protective circuit | Short-circuit and overload protection; Freewheeling circuit in the output driver | Output voltage | 24 V DC -1 V (At nominal current) |
Maximum output current per module | max. 2 A | Nominal output voltage | 24 V DC |
Output current when switched off | max. 10 µA (When not loaded, a voltage can be measured even at an output that is not set.) | Nominal load, inductive | 12 VA (1.2 H, 48 Ω) |
Nominal load, lamp | 12 W | Nominal load, ohmic | 12 W |
Reverse voltage resistance to short pulses | Reverse voltage proof | Behavior with overload | Auto restart |
Behavior with inductive overload | Output can be destroyed | Behavior at voltage switch-off | The output follows the power supply without delay |
Signal delay | typ. 2.9 ms | Overcurrent shut-down | min. 0.7 A |
Product type | I/O component | Product family | Inline |
Type | modular
Inline | Scope of delivery | including Inline connectors and marking fields |
No. of channels | 12 | Special properties | Extreme conditions version |
Diagnostics messages | Short-circuit or overload of the digital outputs yes
Sensor supply failure yes
Failure of the actuator supply yes | Article revision | 02 |
Power dissipation | typ. 1.7 W (entire device) | Supply voltage | 24 V DC (via Inline connector) |
Supply voltage range | 19.2 V DC ... 30 V DC (including all tolerances, including ripple) | Current draw | max. 0.98 A (with max. number of connected I/O terminal blocks)
min. 80 mA (without connected I/O terminal blocks) |
Supply voltage | 7.5 V DC | Supply voltage | 24 V DC |
Supply voltage range | 19.2 V DC ... 30 V DC (including all tolerances, including ripple) | Supply voltage | 24 V DC (via Inline connector) |
Supply voltage range | 19.2 V DC ... 30 V DC (including all tolerances, including ripple) | Current draw | max. 8 A DC
min. 3 mA (without connected peripherals) |
Supply voltage | 24 V DC (via Inline connector) | Supply voltage range | 19.2 V DC ... 30 V DC (including all tolerances, including ripple) |
Current draw | max. 8 A DC
min. 6 mA (without connected peripherals) | Connection name | Inline connector |
Connection method | Spring-cage connection | Conductor cross section rigid | 0.08 mm² ... 1.5 mm² |
Conductor cross section flexible | 0.08 mm² ... 1.5 mm² | Conductor cross section AWG | 28 ... 16 |
Stripping length | 8 mm | Connection method | Spring-cage connection |
Conductor cross section, rigid | 0.08 mm² ... 1.5 mm² | Conductor cross section, flexible | 0.08 mm² ... 1.5 mm² |
Conductor cross section AWG | 28 ... 16 | Stripping length | 8 mm |
Ambient temperature (operation) | -25 °C ... 55 °C
-40 °C ... 70 °C (Extended, see section “Tested successfully: use under extreme ambient conditions” in the data sheet.) | Degree of protection | IP20 |
Air pressure (operation) | 70 kPa ... 106 kPa (up to 3000 m above sea level) | Air pressure (storage/transport) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
Ambient temperature (storage/transport) | -40 °C ... 85 °C | Permissible humidity (operation) | 10 % ... 95 % (non-condensing) |
Permissible humidity (storage/transport) | 10 % ... 95 % (according to DIN EN 61131-2) | Protection class | III (IEC 61140, EN 61140, VDE 0140-1) |
Mounting type | DIN rail mounting |
Specifications may be subject to change without notice