IL PB BK DP/V1
Phoenix Contact

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Type
modular
Number of devices with parameter channel
max. 16
ID code (hex)
none
Protective circuit
Reverse polarity protection
Supply voltage
24 V DC
Supply voltage range
19.2 V DC ... 30 V DC (via Inline connector)
Current draw
max. 1.25 A (with max. number of connected I/O terminal blocks) typ. 100 mA (no local bus devices connected)
Supply voltage
7.5 V DC ±5 %
Supply voltage
24 V DC
Supply voltage range
19.2 V DC ... 30 V DC (including all tolerances, including ripple)
Supply voltage
24 V DC
Supply voltage range
19.2 V DC ... 30 V DC (including all tolerances, including ripple)
Supply voltage
24 V DC
Supply voltage range
19.2 V DC ... 30 V DC (including all tolerances, including ripple)
Test voltage: RS-485 interface / supply voltage
500 V
Test voltage: RS-485 interface / local bus
500 V
Connection method
Spring-cage connection
Conductor cross section, rigid
0.08 mm² ... 1.5 mm²
Conductor cross section, flexible
0.08 mm² ... 1.5 mm²
Conductor cross section AWG
28 ... 16
Connection method
D-SUB-9 female connector
Number of positions
9
Transmission speed
9.6 kbps ... 12 Mbps
Connection method
Inline data jumper
Max. number of local bus devices
63 (The on-board I/Os are two devices)
Width
85 mm
Height
119.8 mm
Depth
71.5 mm
Color
green
Ambient temperature (operation)
0 °C ... 55 °C
Degree of protection
IP20
Air pressure (operation)
80 kPa ... 106 kPa (up to 3000 m above sea level)
Air pressure (storage/transport)
70 kPa ... 106 kPa (up to 3000 m above sea level)
Permissible humidity (operation)
85 % (non-condensing)
Permissible humidity (storage/transport)
85 % (non-condensing)
Protection class
III (IEC 61140, EN 61140, VDE 0140-1)
Mounting type
DIN rail mounting

Specifications may be subject to change without notice