Product Model
IL PN BK DI8 DO4 2TX/NC

Selling Points
- 1Supports 100 Mbps transmission speed via RJ45 socket with auto negotiation.
- 2Acquires and outputs digital signals efficiently, ideal for automation environments.
- 3Connects up to 61 Inline devices, forming a single station with the bus coupler as the first local bus device.
- 4Operates within a 19.2 V DC to 30 V DC supply range, with a maximum current consumption of 8 A DC.
- 5Provides 4 digital outputs with a maximum current per channel of 500 mA and a signal delay of typically 1.2 ms.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Width | 80 mm | Height | 119.8 mm |
Depth | 71.5 mm | Note on dimensions | Specfications with connectors |
EMC note | EMC: class A product, see manufacturer's declaration in the download area | No. of channels | 2 |
Connection method | RJ45 socket, auto negotiation | Transmission speed | 100 Mbps |
Transmission physics | Copper | Connection method | Inline data jumper |
Transmission speed | 500 kbps / 2 Mbps (automatic detection, no combined system) | Connection method | 8-pos. Inline connector |
Max. number of local bus devices | 61 (The on-board I/Os are two devices) | Number of supported devices | max. 63 (per station) |
Number of local bus devices that can be connected | max. 61 (The on-board I/Os are two devices) | Number of devices with parameter channel | max. 16 |
Device function | PROFINET device | Specification | Version 2.0 |
Update rate | max. 1 ms | ID code (hex) | none |
Register length | 16 bit | Input name | Digital inputs |
Description of the input | EN 61131-2 type 1 | Number of inputs | 8 |
Connection method | Inline connector | Connection technology | 2-, 3-conductor |
Input voltage | 24 V DC | Input voltage range "1" signal | 15 V DC ... 30 V DC |
Typical input current per channel | typ. 3 mA | Delay at signal change from 0 to 1 | 5 ms |
Delay at signal change from 1 to 0 | 5 ms | Protective circuit | Reverse polarity protection; Suppressor diode |
Output name | Digital outputs | Connection method | Inline connector |
Connection technology | 2-, 3-conductor | Number of outputs | 4 |
Protective circuit | Short-circuit and overload protection; Free running circuit | Output voltage | 24 V DC -1 V (At nominal current) |
Maximum output current per module | max. 2 A | Nominal output voltage | 24 V DC |
Output current when switched off | 10 µA | Nominal load, inductive | 12 VA |
Nominal load, lamp | 12 W | Nominal load, ohmic | 12 W |
Signal delay | typ. 1.2 ms | Overcurrent shut-down | min. 0.7 A |
Product type | I/O component | Type | modular |
No. of channels | 12 | Supply voltage | 24 V DC (via Inline connector) |
Supply voltage range | 19.2 V DC ... 30 V DC (including all tolerances, including ripple) | Current draw | 0.91 A (no local bus devices connected) |
Supply voltage | 7.5 V DC (via voltage jumper) | Supply voltage | 24 V DC |
Supply voltage range | 19.2 V DC ... 30 V DC (including all tolerances, including ripple) | Supply voltage | 24 V DC |
Supply voltage range | 19.2 V DC ... 30 V DC (including all tolerances, including ripple) | Current draw | max. 8 A DC |
Supply voltage | 24 V DC | Supply voltage range | 19.2 V DC ... 30 V DC (including all tolerances, including ripple) |
Current draw | max. 8 A DC | Supply voltage | 24 V DC (via Inline connector) |
Supply voltage range | 19.2 V DC ... 30 V DC (including all tolerances, including ripple) | Supply current | 70 mA |
Current consumption | 0.91 A (no local bus devices connected) | Power dissipation | typ. 3 W (entire device) |
Connection method | Spring-cage connection | Degree of protection | IP20 |
Air pressure (operation) | 70 kPa ... 106 kPa (up to 3000 m above sea level) | Air pressure (storage/transport) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
Mounting type | DIN rail mounting |
Specifications may be subject to change without notice