Product Model

IL PN BK-PAC

In Stock
Last updated: 2025/4/18
Phoenix Contact IL PN BK-PAC

Selling Points

  • 1Conforms to PROFINET specification V2.3 for seamless integration into industrial automation systems.
  • 2Supports up to 63 Inline devices at any point in the existing PROFINET network.
  • 3Automatic baud rate detection ensures optimal performance with speeds of 500 kbps or 2 Mbps.
  • 4Comprehensive electrical isolation between Ethernet interface and logic protects equipment from electrical interference.
  • 5IP20 protection rating ensures reliable operation in industrial environments with controlled temperature conditions.
Product Details
IL PN BK-PAC
Phoenix Contact

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Width
40 mm
Height
119.4 mm
Depth
71.5 mm
Note on dimensions
Housing dimensions
Note on application
Only for industrial use
Number of interfaces
2
Connection method
RJ45 jack
Note on the connection method
Auto negotiation and autocrossing
Transmission speed
100 Mbps (acc. to PROFINET standard)
Transmission physics
Ethernet in RJ45 twisted pair
Number of interfaces
1
Connection method
Inline data jumper
Transmission speed
500 kbps / 2 Mbps (automatic detection, no combined system)
Number of supported devices
max. 63 (per station)
Number of local bus devices that can be connected
max. 63
Number of devices with parameter channel
max. 16
Number of supported branch terminals with remote bus branch
3
Device function
PROFINET device
Specification
Version 2.3
Conformance Class
Conformance-Class C
Device ID
0140
Vendor ID
00B0
ID code (hex)
none
Register length
16 bit
Product type
I/O component
Product family
Inline
Type
modular
Mounting position
any
Scope of delivery
including Inline connector
No. of channels
12
Article revision
11
Overvoltage category
II (IEC 60664-1, EN 60664-1)
Pollution degree
2 (IEC 60664-1, EN 60664-1)
Maximum power dissipation for nominal condition
3.9 W
Supply voltage
24 V DC (via Inline connector)
Supply voltage range
19.2 V DC ... 30 V DC (including all tolerances, including ripple)
Current draw
max. 0.91 A DC (with max. number of connected I/O terminal blocks) typ. 85 mA (no local bus devices connected)
Supply voltage
7.5 V DC
Supply voltage
24 V DC
Supply voltage range
19.2 V DC ... 30 V DC (including all tolerances, including ripple)
Supply voltage
24 V DC (via Inline connector)
Supply voltage range
19.2 V DC ... 30 V DC (including all tolerances, including ripple)
Supply voltage
24 V DC (via Inline connector)
Supply voltage range
19.2 V DC ... 30 V DC (including all tolerances, including ripple)
Test voltage: PROFINET interface 1 / PROFINET interface 2
1500 V AC, 50 Hz, 1 min
Test voltage: PROFINET interface 1 / communications power (U
1500 V AC, 50 Hz, 1 min
Test voltage: PROFINET interface 1 / I/O (U
1500 V AC, 50 Hz, 1 min
Test voltage: PROFINET interface 1 / functional ground
1500 V AC, 50 Hz, 1 min
Test voltage: PROFINET interface 2 / communications power (U
1500 V AC, 50 Hz, 1 min
Test voltage: PROFINET interface 2 / I/O (U
1500 V AC, 50 Hz, 1 min
Test voltage: PROFINET interface 2 / functional ground
1500 V AC, 50 Hz, 1 min
Test voltage: Communications power (U
500 V AC, 50 Hz, 1 min
Test voltage: Communications power (U
500 V AC, 50 Hz, 1 min
Test voltage: I/O (U
500 V AC, 50 Hz, 1 min
Connection name
Inline connector
Connection method
Spring-cage connection
Conductor cross section rigid
0.08 mm² ... 1.5 mm²
Conductor cross section flexible
0.08 mm² ... 1.5 mm²
Conductor cross section AWG
28 ... 16
Stripping length
8 mm
Connection method
Spring-cage connection
Conductor cross section, rigid
0.08 mm² ... 1.5 mm²
Conductor cross section, flexible
0.08 mm² ... 1.5 mm²
Conductor cross section AWG
28 ... 16
Stripping length
8 mm
Ambient temperature (operation)
-25 °C ... 55 °C
Degree of protection
IP20
Air pressure (operation)
70 kPa ... 106 kPa (up to 3000 m above sea level)
Air pressure (storage/transport)
70 kPa ... 106 kPa (up to 3000 m above sea level)
Ambient temperature (storage/transport)
-40 °C ... 85 °C
Permissible humidity (operation)
10 % ... 95 % (non-condensing)
Permissible humidity (storage/transport)
10 % ... 95 % (non-condensing)
Protection class
III (IEC 61140, EN 61140, VDE 0140-1)
Mounting type
DIN rail mounting
Mounting position
any

Specifications may be subject to change without notice