Phoenix Contact IOA REL 230V DO/BFI/NC/3.0A/EX

Selling Points

  • 1Safely couples 230V AC field devices to digital inputs.
  • 2Protected by a replaceable 3A fuse with LED indication for fuse failure.
  • 3Two-stage progressive release for voltage checks with field-powered devices.
  • 4Plug-in mounting on VIP I/O-Marshalling base elements, suitable for zone 2, “ec” type of protection.
  • 5IECEx, ATEX, CSA, and cUL Listed approvals for enhanced safety standards.
Product Details
IOA REL 230V DO/BFI/NC/3.0A/EX
Phoenix Contact

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Product type
Relay Module
Product family
VIP I/O-Marshalling
Application
Output function
Operating mode
100% operating factor
Mechanical service life
2x 10
Date of last data management
30.10.2024
Article revision
07
Nominal input voltage U
24 V DC
Input voltage range in reference to U
0.9 ... 1.1
Typical input current at U
13.5 mA
Typical response time
5 ms
Typical release time
8 ms
Protective circuit
Reverse polarity protection; Polarity protection diode Freewheeling diode; Freewheeling diode
Operating voltage display
Yellow LED
Contact switching type
1 N/C contact
Type of switch contact
Single contact
Contact connection type
Power contact
Contact material
AgSnO
Maximum switching voltage
230 V AC
Limiting continuous current
3 A (fuse limited)
Maximum inrush current
on request
Min. switching current
10 mA (at 12 V)
Interrupting rating (ohmic load) max.
23 W (at 110 V DC) 690 VA (230 V AC)
Connection method
Pin strip
Number of connections
1
Number of positions
11
Input voltage U
24 V DC
Input current I
13.5 mA
Width
10.3 mm
Height
64.2 mm
Depth
72.9 mm
Color
gray (RAL 7042)
Flammability rating according to UL 94
V0
Degree of protection
IP20
Ambient temperature (operation)
-40 °C ... 70 °C
Ambient temperature (storage/transport)
-40 °C ... 70 °C
Identification
II 3G Ex nA nC IIC T4 Gc
Identification
Ex nA nC IIC T4 Gc
Identification
FM 3600 FM 3611 FM 3810 Class I, Zone 2, Ex nA nC IIC T4 Gc
Identification
Class I, Zone 2, Ex nA nC IIC T4 Gc Nonincendive: Class I, Div. 2, Groups A, B, C, D T4 With connection to Class I, II, and III, Div. 2, Groups A, B, C, D, E, F, G
Identification
ISA S71.04.2013 G3 Harsh Group A
IECEx
Ex nA nC IIC T4 Gc
Standards/regulations
IEC 60664 DIN EN 50178
Mounting type
Plug-in mounting
Assembly note
Plugs into VIP/...BASE...
Mounting position
any

Specifications may be subject to change without notice