Product Model

IOL MA8 PN DI8

In Stock
Last updated: 2025/4/20
Phoenix Contact IOL MA8 PN DI8

Selling Points

  • 1Eight-Channel IO-Link Master: Supports up to eight IO-Link sensors/actuators.
  • 2Web-Based Management: Convenient configuration of IO-Link devices using web-based management.
  • 3Robust Protection: Short-circuit and overload protection of the sensor supply.
  • 4Flexible Connectivity: Connects to PROFINET, MODBUS TCP, and OPC UA networks.
  • 5Compact Design: Dimensions: 45 mm x 114.5 mm x 99 mm, suitable for industrial use.
Product Details
IOL MA8 PN DI8
Phoenix Contact

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Width
45 mm
Height
114.5 mm
Depth
99 mm
Note on application
Only for industrial use
EMC note
EMC: class A product, see manufacturer's declaration in the download area
Housing material
Polyamide
Color
gray
No. of channels
2
Connection method
RJ45 jack
Transmission speed
10/100 Mbps (with auto negotiation)
Transmission physics
Ethernet in RJ45 twisted pair
Equipment type
PROFINET-Device
System-specific protocols
PROFINET protocols LLDP PROFINET protocols MRP client PROFINET protocols DCP DCE/RPC
Protocols supported
SNMP v1 HTTP TFTP FTP BootP DHCP SSH
Input name
Digital inputs
Description of the input
IEC 61131-2 type 1
Number of inputs
8
Connection method
Push-in / plug connection
Connection technology
3-conductor
Input voltage range "0" signal
0 V DC ... 5 V DC
Input voltage range "1" signal
15 V DC ... 30 V DC
Nominal input voltage U
24 V DC
Nominal input current at U
typ. 3.5 mA
Input frequency
0.5 kHz
Protective circuit
Overload protection Short-circuit protection for the sensor supply
Input name
Digital inputs
Description of the input
IO-Link ports in digital input (DI) mode
Number of inputs
max. 8 (EN 61131-2 types 1 and 3)
Connection method
Push-in / plug connection
Connection technology
3-conductor
Nominal input voltage U
24 V DC
Input voltage range "0" signal
8 V DC ... 11.5 V DC (for C/Q pin)
Input voltage range "1" signal
10.5 V DC ... 13 V DC
Sensor current per channel
max. 200 mA (from L+/L-)
Total sensor current
max. 1.6 A (from L+/L-)
Protective circuit
Overload protection; yes Short-circuit protection for the sensor supply; electronic
Description of the input
Digital inputs (DI)
Connection method
Push-in / plug connection
Nominal input voltage U
24 V DC
Input voltage range "0" signal
5.2 V DC ... 6.4 V DC
Input voltage range "1" signal
6.8 V DC ... 8 V DC
Nominal input current
typ. 3.5 mA
Sensor current per channel
max. 200 mA (from L+/L-)
Total sensor current
max. 1.6 A (from L+/L-)
Protective circuit
Overload protection; yes Short-circuit protection for the sensor supply; yes
Number of ports
8
Connection method
Push-in / plug connection
Connection technology
3-conductor
Cycle Time
min. 4 ms (IO-Link cycle time)
Maximum output current per channel
200 mA
Output description
IO-Link ports in digital output (DO) mode
Connection method
Push-in / plug connection
Connection technology
3-conductor
Number of outputs
max. 8
Nominal output voltage
24 V DC
Maximum output current per channel
200 mA
Maximum output current per module
1.6 A
Nominal load, ohmic
4.8 W (120 Ω, at nominal load)
Output voltage when switched off
max. 1 V
Output current when switched off
max. 400 µA
Protective circuit
Overload protection Short-circuit protection; yes
Behavior with overload
Shutdown with automatic restart
Product type
I/O component
Product family
Stand-Alone
Type
Stand-Alone
Article revision
02
Maximum power dissipation for nominal condition
4.4 W
Nominal voltage for I/O supply
24 V DC
Nominal current for every IO-Link port
max. 200 mA (at C/Q) max. 200 mA (at L+/L-)
Permissible cable length
< 20 m
Protective circuit
Overload protection; yes
Supply voltage
24 V DC
Supply voltage range
10.8 V DC ... 30 V DC
Current draw
155 mA
Supply voltage
24 V DC
Supply voltage range
18 V DC ... 30 V DC
Current consumption
3.7 A
Supply voltage
24 V DC
Supply voltage range
18 V DC ... 30 V DC
Current consumption
max. 3.7 A
Typical current consumption
155 mA (at 24 V DC)
Test voltage: 24 V supply/Ethernet
500 V AC, 50 Hz, 1 min
Test voltage: 24 V supply (US) / FE
500 V AC, 50 Hz, 1 min
Test voltage: Ethernet/FE
500 V AC, 50 Hz, 1 min
Test voltage: Ethernet/Ethernet
500 V AC, 50 Hz, 1 min
Connection method
Push-in connection
Conductor cross section rigid
0.2 mm² ... 2.5 mm²
Conductor cross section flexible
0.2 mm² ... 2.5 mm²
Conductor cross section AWG
24 ... 14
Stripping length
10 mm
Connection method
Push-in connection
Conductor cross section, rigid
0.2 mm² ... 2.5 mm²
Conductor cross section, flexible
0.2 mm² ... 2.5 mm²
Conductor cross section AWG
24 ... 14
Stripping length
10 mm
Ambient temperature (operation)
-25 °C ... 60 °C
Degree of protection
IP20
Ambient temperature (storage/transport)
-25 °C ... 85 °C
Permissible humidity (operation)
10 % ... 95 %
Permissible humidity (storage/transport)
10 % ... 95 %
Mounting type
DIN rail mounting

Specifications may be subject to change without notice