Product Model

MCR-CLP-UI-I-4

In Stock
Last updated: 2025/4/18
Phoenix Contact MCR-CLP-UI-I-4

Selling Points

  • 1Set over 25 different signal ranges using DIP switches.
  • 2Operates in a 4…20 mA current loop, providing power for signal conversion.
  • 3± 2% zero/span adjustment for precise signal matching.
  • 4Safely isolate active PLC input board cards with robust electrical isolation.
  • 5Operates from -25 °C to +65 °C, suitable for various industrial environments.
Product Details
MCR-CLP-UI-I-4
Phoenix Contact

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Product type
Passive separator
No. of channels
1
Alignment span
± 2 % (of final value)
Alignment zero
± 2 % (of final value)
Limit frequency (3 dB)
30 Hz
Maximum power dissipation for nominal condition
160 mW
Test voltage input/output
1.5 kV AC (50 Hz, 60 s)
Step response (10-90%)
11 ms
Maximum temperature coefficient
≤ 0.01 %/K
Temperature coefficient, typical
0.005 %/K
Maximum transmission error
≤ 0.1 % (of final value)
Transmission error, typical
0.05 %
Designation
Loop-powered
Supply voltage range
8 V DC ... 30 V DC
Description of the input
Current input
Configurable/programmable
Yes
Max. voltage input signal
30 V
Current input signal
4 mA ... 20 mA (please indicate if different setting when ordering)
Max. current input signal
50 mA
Input resistance of voltage input
1 MΩ
Input resistance current input
50 Ω
Configurable/programmable
no
Current output signal
4 mA ... 20 mA
Max. current output signal
35 mA
Load/output load current output
≤ 800 Ω (at U
Connection method
Pluggable screw connection
Stripping length
8 mm
Screw thread
M3
Conductor cross section rigid
0.2 mm² ... 2.5 mm²
Conductor cross section flexible
0.2 mm² ... 2.5 mm²
Conductor cross section AWG
24 ... 14
Limit frequency (3 dB)
30 Hz
Width
17.5 mm
Height
99 mm
Depth
114.5 mm
Color
green (RAL 6021)
Housing material
Polyamide PA non-reinforced
Ambient temperature (operation)
-25 °C ... 65 °C
Certificate
CE-compliant
Identification
Class I, Div. 2, Groups A, B, C, D or Non-Hazardous Locations
Mounting position
any

Specifications may be subject to change without notice