Product Model

MCR-FL-TS-LP-I-EX-200

In Stock
Last updated: 2025/4/18
Phoenix Contact MCR-FL-TS-LP-I-EX-200

Selling Points

  • 1Preconfigured to 200°C: Ideal for high-temperature applications.
  • 22-way Electrical Isolation: Ensures safe and reliable operation.
  • 3HART Compatibility: Supports advanced communication protocols for efficient data transfer.
  • 4Loop-Powered: Reduces wiring complexity and saves power.
  • 5Preconfigured for Zone 1 Installation: Suitable for hazardous environments.
Product Details
MCR-FL-TS-LP-I-EX-200
Phoenix Contact

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Product type
Temperature transmitter
Application
Temperature
Article revision
07
Switch-on delay
4 s
Line monitoring
NE 43
Test voltage input/output
2 kV AC (50 Hz, 60 s)
Step response (10-90%)
< 2 s
Transmission error voltage sensor
±20 µV (-10 mV ... 100 mV)
Transmission error thermocouples
typ. 0.5 K (K, J, T, E, L, U), 1.0 K (N, C, D), 2.0 K (S, B, R)
Transmission error resistance-type sensor
±0.1 Ω (10 ... 400 Ω), ±1.5 Ω (10 ... 2000 Ω)
Transmission error resistance thermometer
0.2 K (Pt 100, Ni 100), 0.5 K (Pt 500, Ni 500), 0.3 K (Pt 1000, Ni 1000)
Designation
Loop-powered
Supply voltage range
12 V DC ... 30 V DC
Max. current consumption
< 3.5 mA
Input signal
Temperature
Configurable/programmable
no, preconfigured
Sensor types (RTD) that can be used
Pt, Ni (100, 500, 1000); min. measurement range 10 K
Sensor types that can be used (TC)
B, C, D, E, J, K, L, N, R, S, T, U; min. measurement range 50 K/500 K
Temperature measuring range
-25 °C ... 200 °C
Linear resistance measuring range
10 Ω ... 400 Ω (min. measurement range 10 Ω)
Linear mV signal range
-10 mV ... 100 mV (min. measurement range 5 mV)
Configurable/programmable
no
Output description
Current output
Configurable/programmable
no
Current output signal
4 mA ... 20 mA 20 mA ... 4 mA
Max. current output signal
≤ 23 mA
Output current with short-circuit
≤ 3.6 mA or ≥ 21 mA (adjustable, not for thermocouples)
Output current with wire break
≤ 3.6 mA or ≥ 21 mA (adjustable)
Output current range with overrange/underrange
3.8 mA ... 20.5 mA
Load/output load current output
≤ 520 Ω (At U
Connection method
Pluggable screw connection
Stripping length
8 mm
Screw thread
M3
Conductor cross section rigid
0.2 mm² ... 2.5 mm²
Conductor cross section flexible
0.2 mm² ... 2.5 mm²
Conductor cross section AWG
24 ... 14
Tightening torque
0.5 Nm ... 0.6 Nm
Width
12.5 mm
Height
99 mm
Depth
114.5 mm
Color
green (RAL 6021)
Flammability rating according to UL 94
V0
Housing material
Polyamide PA non-reinforced
Degree of protection
IP20
Ambient temperature (operation)
-40 °C ... 55 °C
Certificate
CE-compliant
Standards/regulations
NAMUR recommendation NE 21
Mounting type
DIN rail mounting
Mounting position
any

Specifications may be subject to change without notice