Product Model

MCR-FL-TS-LP-I-EX-400

In Stock
Last updated: 2025/4/22
Phoenix Contact MCR-FL-TS-LP-I-EX-400

Selling Points

  • 1High Precision Measurement: Measures temperature with accuracy, suitable for a wide range of industrial applications.
  • 2HART Compatibility: Configurable via software with HART protocol for easy integration and control.
  • 3Robust Safety Features: Designed for Ex ia IIC environments, ensuring safe operation in hazardous zones.
  • 4Loop-Powered Design: Self-powered, reducing the need for external power sources and simplifying installation.
  • 5Versatile Sensor Support: Compatible with resistance thermometers, thermocouples, and linear mV signals, offering flexibility in sensor choice.
Product Details
MCR-FL-TS-LP-I-EX-400
Phoenix Contact

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Product type
Temperature transmitter
Application
Temperature
Article revision
07
Switch-on delay
4 s
Line monitoring
NE 43
Test voltage input/output
2 kV AC (50 Hz, 60 s)
Step response (10-90%)
< 2 s
Transmission error voltage sensor
±20 µV (-10 mV ... 100 mV)
Transmission error thermocouples
typ. 0.5 K (K, J, T, E, L, U), 1.0 K (N, C, D), 2.0 K (S, B, R)
Transmission error resistance-type sensor
±0.1 Ω (10 ... 400 Ω), ±1.5 Ω (10 ... 2000 Ω)
Transmission error resistance thermometer
0.2 K (Pt 100, Ni 100), 0.5 K (Pt 500, Ni 500), 0.3 K (Pt 1000, Ni 1000)
Input signal
Temperature
Configurable/programmable
no, preconfigured
Sensor types (RTD) that can be used
Pt, Ni (100, 500, 1000); min. measurement range 10 K
Sensor types that can be used (TC)
B, C, D, E, J, K, L, N, R, S, T, U; min. measurement range 50 K/500 K
Temperature measuring range
-25 °C ... 400 °C
Linear resistance measuring range
10 Ω ... 400 Ω (min. measurement range 10 Ω)
Linear mV signal range
-10 mV ... 100 mV (min. measurement range 5 mV)
Configurable/programmable
no
Output description
Current output
Configurable/programmable
no
Current output signal
4 mA ... 20 mA 20 mA ... 4 mA
Max. current output signal
≤ 23 mA
Output current with short-circuit
≤ 3.6 mA or ≥ 21 mA (adjustable, not for thermocouples)
Output current with wire break
≤ 3.6 mA or ≥ 21 mA (adjustable)
Output current range with overrange/underrange
3.8 mA ... 20.5 mA
Load/output load current output
≤ 520 Ω (At U
Connection method
Pluggable screw connection
Stripping length
8 mm
Screw thread
M3
Conductor cross section rigid
0.2 mm² ... 2.5 mm²
Conductor cross section flexible
0.2 mm² ... 2.5 mm²
Conductor cross section AWG
24 ... 14
Tightening torque
0.5 Nm ... 0.6 Nm
Width
12.5 mm
Height
99 mm
Depth
114.5 mm
Color
green (RAL 6021)
Flammability rating according to UL 94
V0
Housing material
Polyamide PA non-reinforced
Degree of protection
IP20
Ambient temperature (operation)
-40 °C ... 55 °C
Certificate
CE-compliant
Standards/regulations
NAMUR recommendation NE 21
Mounting type
DIN rail mounting
Mounting position
any

Specifications may be subject to change without notice