Product Model

MCR-PT100-I-DC-NC

In Stock
Last updated: 2025/4/22
Phoenix Contact MCR-PT100-I-DC-NC

Selling Points

  • 1Converts Pt100 sensor signals to 4-20mA analog output.
  • 2High precision for accurate temperature measurement.
  • 3DIN rail mountable for easy installation in control panels.
  • 4Provides electrical isolation between input, output, and power supply.
  • 5Features overvoltage and overcurrent protection for connected devices.
Product Details
MCR-PT100-I-DC-NC
Phoenix Contact

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
EMC note
EMC: class A product, see manufacturer's declaration in the download area
Product type
Temperature transmitter
Alignment span
± 5 %
Alignment zero
± 5 %
Test voltage power supply/signal
750 V AC (50 Hz, 60 s)
Step response (10-90%)
11 ms
Maximum temperature coefficient
≤ 0.02 %/K
Maximum transmission error
≤ 0.4 % (of final value)
Supply voltage range
20 V DC ... 30 V DC
Max. current consumption
60 mA
Configurable/programmable
Yes, unconfigured
Sensor types (RTD) that can be used
Pt 100 (IEC 60751/EN 60751)
Temperature measuring range
0 °C ... 300 °C (0 ... 100/150/200/300) -50 °C ... 250 °C (-50 ... 50/100/150/250)
Sensor type:
-50 °C ... 50 °C -50 °C ... 100 °C -50 °C ... 150 °C -50 °C ... 250 °C 0 °C ... 100 °C 0 °C ... 150 °C 0 °C ... 200 °C 0 °C ... 300 °C
Sensor input current
approx. 1 mA
Connection technology
2-, 3-, 4-conductor
Connection method
Pluggable screw connection
Current output signal
4 mA ... 20 mA 0 mA ... 20 mA
Max. current output signal
30 mA
Output current with wire break
> 22 mA
Load/output load current output
≤ 500 Ω
Connection method
Screw connection
Stripping length
8 mm
Screw thread
M3
Conductor cross section rigid
0.2 mm² ... 2.5 mm²
Conductor cross section flexible
0.2 mm² ... 2.5 mm²
Conductor cross section AWG
24 ... 14
Width
17.5 mm
Height
99 mm
Depth
114.5 mm
Color
green (RAL 6021)
Housing material
Polyamide PA non-reinforced
Degree of protection
IP20
Ambient temperature (operation)
-20 °C ... 65 °C
Certificate
CE-compliant
Identification
cULus
Mounting position
any

Specifications may be subject to change without notice