Phoenix Contact MCR-S10-50-UI-SW-DCI-NC

Selling Points

  • 1Accurately measures a wide range of current types.
  • 2Freely adjustable input current from 0 A to 55 A.
  • 3Features hard gold-plated relay contacts for high reliability.
  • 4Provides precise measurements of true RMS values.
  • 5Can be set via DIP switches or MCR/PI-CONF-WIN configuration software.
Product Details
MCR-S10-50-UI-SW-DCI-NC
Phoenix Contact

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
EMC note
EMC: class A product, see manufacturer's declaration in the download area
Product type
Current transducer
Article revision
16
Overvoltage category
III
Pollution degree
2
Total error
≤ 1.5 % (Temperature range)
Maximum power dissipation for nominal condition
2.2 W
Measuring category
III
Test voltage output/power supply
500 V AC (50 Hz, 60 s)
Test voltage input/output
4 kV AC (50 Hz, 60 s)
Test voltage input/power supply
4 kV AC (50 Hz, 60 s)
Protective circuit
Surge protection; 33 V suppressor diode
Step response (10-90%)
330 ms (AC) 40 ms (DC)
Temperature coefficient, typical
< 0.025 %/K
Maximum transmission error
< 0.5 % (of nominal range value under nominal conditions)
Rated insulation voltage
300 V AC (to earth)
Supply voltage range
20 V DC ... 30 V DC
Max. current consumption
< 50 mA (without load)
Configurable/programmable
Yes, unconfigured
Input current range
0 A AC/DC ... 55 A AC/DC (Permitted continuous overload: 120%)
Measuring range
0 A AC/DC ... 50 A AC/DC
Setting range for min. input current
0 A AC/DC ... 9.5 A AC/DC
Setting range for max. input current
0 A AC/DC ... 55 A AC/DC
LSB: Current
1 µA (1 A) 2 µA (2 A) 5 µA (5 A) 10 µA (10 A) 50 µA (50 A) 100 µA (100 A)
Overload capacity
Depending on through connected conductor
Surge strength
Depending on through connected conductor
Frequency measuring range
15 Hz ... 400 Hz
Curve type
AC, DC or distorted currents
Operate threshold
0.8 % (of measuring range nominal value 50 A)
Contact switching type
1 changeover contact
Contact material
AgSnO, hard gold-plated
Maximum switching voltage
30 V AC 36 V DC 250 V AC
Limiting continuous current
50 mA (for gold layer, 30 V AC/ 36 V DC) 2 A (in case of a destroyed gold layer, 250 V AC)
Continuous load current
80 mA (Not short-circuit proof)
Output voltage range
19 V ... 29 V (supply voltage - 1 V)
Setting range of the threshold value
1 % ... 110 %
Setting range of the response delay
0.1 s ... 20 s
Status display
LED (yellow)
Configurable/programmable
Yes, unconfigured
Voltage output signal
0 V ... 5 V 1 V ... 5 V 0 V ... 10 V 2 V ... 10 V -5 V ... 5 V -10 V ... 10 V 10 V ... 0 V 10 V ... 2 V 10 V ... -10 V 5 V ... 0 V 5 V ... 1 V 5 V ... -5 V
Current output signal
0 mA ... 20 mA 4 mA ... 20 mA 20 mA ... 0 mA 20 mA ... 4 mA
Load/output load voltage output
> 10 kΩ
Load/output load current output
< 500 Ω
Connection method
Screw connection
Stripping length
8 mm
Screw thread
M3
Conductor cross section rigid
0.2 mm² ... 2.5 mm²
Conductor cross section flexible
0.2 mm² ... 2.5 mm²
Conductor cross section AWG
24 ... 14
Connection method
Through connection
Status display
LED (green)
Width
22.5 mm
Height
99 mm
Depth
114.5 mm
Diameter
10.5 mm
Color
green (RAL 6021)
Housing material
Polyamide PA non-reinforced
Degree of protection
IP20
Ambient temperature (operation)
-20 °C ... 60 °C
Ambient temperature (storage/transport)
-40 °C ... 85 °C
Altitude
< 2000 m
Permissible humidity (operation)
10 % ... 95 % (non-condensing)
Certificate
CE-compliant
Identification
Class I, Zone 2, AEx nA nC IIC T4, Ex nA nC IIC T4 Gc X Class I, Div. 2, Groups A, B, C and D or Non-Hazardous Locations Only
Electromagnetic compatibility
Conformance with EMC directive
Low Voltage Directive
Conformance with Low Voltage Directive
Noise immunity
EN 61000-6-2
Noise emission
EN 61000-6-4
Standards/regulations
IEC 61010-2-030
Mounting type
DIN rail mounting
Mounting position
any

Specifications may be subject to change without notice