Phoenix Contact MCR-S-1-5-UI-DCI

Selling Points

  • 1Accurate Measurement: Measures currents from 0 A to 11 A (AC/DC) with an operate threshold of 2% of the nominal value.
  • 2Configurable & Programmable: Unconfigured inputs allow for customization to suit specific measurement needs.
  • 3Robust Design: IP20 degree of protection and a maximum transmission error of <0.5% ensure reliable operation.
  • 4Versatile Input Range: Handles AC, DC, and distorted currents, making it suitable for diverse applications.
  • 5Easy Installation: Screw connection with a stripping length of 8 mm and conductor cross section ranging from 0.2 mm² to 2.5 mm².
Product Details
MCR-S-1-5-UI-DCI
Phoenix Contact

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
EMC note
EMC: class A product, see manufacturer's declaration in the download area
Product type
Current transducer
Article revision
18
Overvoltage category
III
Pollution degree
2
Total error
≤ 1.5 % (Temperature range)
Maximum power dissipation for nominal condition
2.2 W
Measuring category
III
Test voltage output/power supply
500 V AC (50 Hz, 60 s)
Test voltage input/output
4 kV AC (50 Hz, 60 s)
Test voltage input/power supply
4 kV AC (50 Hz, 60 s)
Protective circuit
Surge protection; 33 V suppressor diode
Step response (10-90%)
330 ms (AC) 40 ms (DC)
Temperature coefficient, typical
< 0.025 %/K
Maximum transmission error
< 0.5 % (of nominal range value under nominal conditions)
Rated insulation voltage
300 V AC (to earth)
Supply voltage range
20 V DC ... 30 V DC
Max. current consumption
< 40 mA (without load)
Number of inputs
3
Configurable/programmable
Yes, preconfigured
Input current range
0 A AC/DC ... 11 A AC/DC (Permitted continuous overload: 120%)
Measuring range
0 A AC/DC ... 1 A AC/DC 0 A AC/DC ... 5 A AC/DC 0 A AC/DC ... 10 A AC/DC
Setting range for min. input current
0 mA AC/DC ... 200 mA AC/DC
Setting range for max. input current
0 A AC/DC ... 11 A AC/DC
LSB: Current
1 µA (1 A) 2 µA (2 A) 5 µA (5 A) 10 µA (10 A) 50 µA (50 A) 100 µA (100 A)
Overload capacity
2 x I
Surge strength
20 x I
Frequency measuring range
15 Hz ... 400 Hz
Curve type
AC, DC or distorted currents
Operate threshold
2 % (of measuring range nominal value 1/5/10 A)
Configurable/programmable
Yes, preconfigured
Voltage output signal
0 V ... 5 V 1 V ... 5 V 0 V ... 10 V 2 V ... 10 V -5 V ... 5 V -10 V ... 10 V 10 V ... 0 V 10 V ... 2 V 10 V ... -10 V 5 V ... 0 V 5 V ... 1 V 5 V ... -5 V
Current output signal
0 mA ... 20 mA 4 mA ... 20 mA 20 mA ... 0 mA 20 mA ... 4 mA
Load/output load voltage output
> 10 kΩ
Load/output load current output
< 500 Ω
Connection method
Screw connection
Stripping length
8 mm
Screw thread
M3
Conductor cross section rigid
0.2 mm² ... 2.5 mm²
Conductor cross section flexible
0.2 mm² ... 2.5 mm²
Conductor cross section AWG
24 ... 14
Status display
LED (green)
Width
22.5 mm
Height
99 mm
Depth
114.5 mm
Color
green (RAL 6021)
Housing material
Polyamide PA non-reinforced
Degree of protection
IP20
Ambient temperature (operation)
-20 °C ... 60 °C
Ambient temperature (storage/transport)
-40 °C ... 85 °C
Altitude
< 2000 m
Permissible humidity (operation)
10 % ... 95 % (non-condensing)
Certificate
CE-compliant
Identification
Class I, Zone 2, AEx nA nC IIC T4, Ex nA nC IIC T4 Gc X Class I, Div. 2, Groups A, B, C and D or Non-Hazardous Locations Only
Electromagnetic compatibility
Conformance with EMC directive
Low Voltage Directive
Conformance with Low Voltage Directive
Noise immunity
EN 61000-6-2
Noise emission
EN 61000-6-4
Standards/regulations
IEC 61010-2-030
Mounting type
DIN rail mounting
Mounting position
any

Specifications may be subject to change without notice