Phoenix Contact MCR-S-20-100-UI-DCI

Selling Points

  • 1High Precision Measurement: Total error ≤ 1.5% across temperature range.
  • 2Surge Protection: Equipped with a protective circuit for reliable operation.
  • 3Industrial Grade: Designed for demanding industrial automation and control systems.
  • 4Low Power Dissipation: Maximum power dissipation for nominal conditions is 2.2 W.
  • 5Robust Construction: Measuring category III ensures robust performance under various conditions.
Product Details
MCR-S-20-100-UI-DCI
Phoenix Contact

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Product type
Current transducer
Article revision
02
Overvoltage category
III
Pollution degree
2
Total error
≤ 1.5 % (Temperature range)
Maximum power dissipation for nominal condition
2.2 W
Measuring category
III
Test voltage output/power supply
500 V AC (50 Hz, 60 s)
Test voltage input/output
4 kV AC (50 Hz, 60 s)
Test voltage input/power supply
4 kV AC (50 Hz, 60 s)
Protective circuit
Surge protection; 33 V suppressor diode
Step response (10-90%)
330 ms (AC) 40 ms (DC)
Temperature coefficient, typical
< 0.025 %/K
Maximum transmission error
< 0.5 % (of nominal range value under nominal conditions)
Rated insulation voltage
300 V AC (to earth)
Supply voltage range
20 V DC ... 30 V DC
Max. current consumption
< 40 mA (without load)
Configurable/programmable
Yes, unconfigured
Input current range
0 A AC/DC ... 100 A AC/DC (Permitted continuous overload: 120%)
Setting range for min. input current
0 A AC/DC ... 19 A AC/DC
Setting range for max. input current
0 A AC/DC ... 100 A AC/DC
LSB: Current
1 µA (1 A) 2 µA (2 A) 5 µA (5 A) 10 µA (10 A) 50 µA (50 A) 100 µA (100 A)
Overload capacity
Depending on through connected conductor
Surge strength
Depending on through connected conductor
Frequency measuring range
15 Hz ... 400 Hz
Curve type
AC, DC or distorted currents
Operate threshold
1 % (of measuring range nominal value 100 A)
Configurable/programmable
Yes, unconfigured
Voltage output signal
0 V ... 10 V 5 V ... 1 V 5 V ... -5 V 2 V ... 10 V -10 V ... 10 V 0 V ... 5 V 1 V ... 5 V -5 V ... 5 V 10 V ... 0 V 10 V ... 2 V 10 V ... -10 V 5 V ... 0 V
Current output signal
0 mA ... 20 mA 4 mA ... 20 mA 20 mA ... 0 mA 20 mA ... 4 mA
Load/output load voltage output
> 10 kΩ
Load/output load current output
< 500 Ω
Connection method
Screw connection
Stripping length
8 mm
Screw thread
M3
Conductor cross section rigid
0.2 mm² ... 2.5 mm²
Conductor cross section flexible
0.2 mm² ... 2.5 mm²
Conductor cross section AWG
24 ... 14
Connection method
Through connection
Status display
LED (green)
Width
22.5 mm
Height
99 mm
Depth
114.5 mm
Diameter
10.5 mm
Color
green (RAL 6021)
Housing material
Polyamide PA non-reinforced
Degree of protection
IP20
Ambient temperature (operation)
-20 °C ... 60 °C
Ambient temperature (storage/transport)
-40 °C ... 85 °C
Altitude
< 2000 m
Permissible humidity (operation)
10 % ... 95 % (non-condensing)
Certificate
CE-compliant
Identification
Class I, Zone 2, AEx nA nC IIC T4, Ex nA nC IIC T4 Gc X Class I, Div. 2, Groups A, B, C and D or Non-Hazardous Locations Only
Electromagnetic compatibility
Conformance with EMC directive
Low Voltage Directive
Conformance with Low Voltage Directive
Noise immunity
EN 61000-6-2
Noise emission
EN 61000-6-4
Standards/regulations
IEC 61010-2-030
Mounting type
DIN rail mounting
Mounting position
any

Specifications may be subject to change without notice