Product Model
MCR-SL-S-1/5-I-DCI-230

Selling Points
- 1Measures sinusoidal alternating currents up to 1 A AC/5 A AC.
- 2Compatible with supply voltages of 85...230 V AC/DC.
- 3Output signal range: 0(4)...20 mA.
- 4High transmission accuracy: 0.5 % (Class 0.5).
- 5Fast step response: < 300 ms (10-90%).
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Product type | Current transducer | Overvoltage category | III |
Pollution degree | 2 | Test voltage output/power supply | 4 kV (50 Hz, 1 min.) |
Test voltage input/output | 4 kV (50 Hz, 1 min.) | Test voltage input/power supply | 4 kV (50 Hz, 1 min.) |
Step response (10-90%) | < 300 ms | Maximum transmission error | 0.5 % |
Transmission error, typical | 0.5 % (Class 0.5) | Supply voltage range | 85 V AC/DC ... 230 V AC/DC |
Description of the input | Current measuring input 1 A | Input current range | 0 A AC ... 1 A |
Overload capacity | 1.2 x I | Surge strength | 20 x I |
Nominal frequency f | 50 Hz
60 Hz | Curve type | Sine |
Description of the input | Current measuring input 5 A | Input current range | 0 A AC ... 5 A |
Impulse form | Sine | Overload capacity | 1.2 x I |
Surge strength | 20 x I | Nominal frequency f | 50 Hz
60 Hz |
Frequency measuring range | 50 Hz ... 60 Hz | Connection method | Screw connection |
Current output signal | 0 mA ... 20 mA
4 mA ... 20 mA | Max. current output signal | approx. 30 mA |
Load/output load current output | < 750 Ω | Connection method | Pluggable screw connection |
Stripping length | 8 mm | Screw thread | M3 |
Conductor cross section rigid | 0.2 mm² ... 2.5 mm² | Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
Conductor cross section AWG | 24 ... 14 | Width | 22.5 mm |
Height | 99 mm | Depth | 114.5 mm |
Color | green (RAL 6021) | Housing material | Polyamide PA non-reinforced |
Degree of protection (Housing) | IP40 (Housing) | Degree of protection (Connections) | IP20 (Connection terminal blocks) |
Ambient temperature (operation) | -10 °C ... 55 °C | Electromagnetic compatibility | Conformance with EMC directive |
Mounting position | any |
Specifications may be subject to change without notice