Phoenix Contact MCR-SL-S-200-I-LP

Selling Points

  • 1Measures sinusoidal and non-sinusoidal alternating currents.
  • 2Loop-powered output with 4-20 mA signal.
  • 3Can be retrofitted with open-up Rogowski coil.
  • 4Measuring range selection via slide switch.
  • 5True r.m.s. value measurement up to 6000 Hz.
Product Details
MCR-SL-S-200-I-LP
Phoenix Contact

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Product type
Current transducer
Article revision
02
Overvoltage category
III
Pollution degree
2
Maximum power dissipation for nominal condition
1 W
Test voltage input/output
4.13 kV AC (50 Hz, 60 s)
Step response (10-90%)
< 340 ms
Maximum temperature coefficient
< 0.025 %/K
Maximum transmission error
< 1 % (of final value)
Rated insulation voltage
300 V AC (to earth)
Supply voltage range
loop-powered, no external supply necessary
Configurable/programmable
Yes
Current input signal
0 A ... 200 A
Input current range
0 A AC ... 100 A AC 0 A AC ... 150 A AC 0 A AC ... 200 A AC
Setting range for min. input current
0 A AC ... 100 A AC
Setting range for max. input current
0 A AC ... 200 A AC
Overload capacity
Depending on laid conductor
Surge strength
Depending on through connected conductor
Frequency measuring range
30 Hz ... 6000 Hz
Curve type
Sinusoidal and non-sinusoidal
Operate threshold
1 % (of final value)
Current output signal
4 mA ... 20 mA
Max. current output signal
< 25 mA
Load/output load current output
(U
Connection method
Screw connection
Stripping length
8 mm
Screw thread
M3
Conductor cross section rigid
0.2 mm² ... 2.5 mm²
Conductor cross section flexible
0.2 mm² ... 2.5 mm²
Conductor cross section AWG
24 ... 14
Tightening torque
0.5 Nm ... 0.6 Nm (4,4 ... 5,31 lbf-in.)
Connection method
Through connection
Width
55 mm
Height
85 mm
Depth
70.5 mm
Diameter
≤ 18.5 mm
Color
green (RAL 6021)
Housing material
Polyamide PA non-reinforced
Degree of protection
IP20
Ambient temperature (operation)
-20 °C ... 60 °C
Ambient temperature (storage/transport)
-40 °C ... 85 °C
Certificate
CE-compliant
Certificate
UKCA-compliant
Identification
UL/C-UL Listed UL 508 Class I, Div. 2, Groups A, B, C, D T4A Class I, Zone 2, Group IIC T4A Or Non-Hazardous Locations only
Mounting type
DIN rail mounting
Mounting position
any

Specifications may be subject to change without notice