Selling Points

  • 1Convert frequency and PWM signals into standard signals with DIP switch configuration.
  • 2Measuring range of 0.002 Hz to 200 kHz with a maximum transmission error of 0.1% for frequency.
  • 3Adjustable voltage output signals (0 V to 10 V, 2 V to 10 V, etc.) via DIP switch.
  • 4Operating temperature range of -40 °C to 85 °C and humidity tolerance of 5% to 95% non-condensing.
  • 5Highly compact design with pluggable connection technology for simple installation in confined spaces.
Product Details
MINI MCR-2-F-UI-C
Phoenix Contact

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Product type
Frequency value transformer
Product family
MINI Analog Pro
No. of channels
1
Type
Signal conditioner
Configuration
DIP switches Software App
Article revision
05
Overvoltage category
II
Pollution degree
2
Configuration
DIP switches Software App
Step response (0–99%)
< 35 ms (f > 500 Hz)
Maximum temperature coefficient
0.01 %/K
Maximum transmission error
0.1 % (Frequency (Hz/rpm)) 1 % (PWM signal)
Rated insulation voltage
300 V
Test voltage
3 kV AC (50 Hz, 60 s)
Insulation
Reinforced insulation according to IEC/EN 61010-1
Nominal supply voltage
24 V DC
Supply voltage range
9.6 V DC ... 30 V DC (The DIN rail connector (ME 6,2 TBUS-2 1,5/5-ST-3,81 GN, item no. 2869728) can be used to bridge the supply voltage. It can be snapped onto a 35 mm DIN rail in accordance with EN 60715)
Typical current consumption
32 mA (24 V DC) 63 mA (12 V DC)
Power consumption
≤ 1 W (at I
Available input sources
NAMUR initiators NPN/PNP transistor outputs Floating contact (dry contact) Frequency generator Incremental encoder (speed only) HTL encoders TTL rotary transducer S0 signal
Max. voltage input signal
30 V (incl. DC voltage)
Voltage measuring range
≥ 2 V
Frequency measuring range
0.002 Hz ... 200 kHz
PWM (range)
0.002 Hz ... 60 Hz (Duty cycle 2 ... 98 %) 60 Hz ... 300 Hz (Duty cycle: 5 ... 95 %) 300 Hz ... 600 Hz (Duty cycle: 10 ... 90 %) 600 Hz ... 1000 Hz (Duty cycle 20 ... 80 %)
Number of inputs
1
Input signal
Frequency
Number of outputs
1
Contact switching type
1 N/O contact
Minimum switching voltage
1 V
Maximum switching voltage
30 V DC
Min. switching current
100 µA
Max. switching current
100 mA (30 V)
Number of outputs
1
Configurable/programmable
Yes
Voltage output signal
0 V ... 10 V (via DIP switch) 2 V ... 10 V (via DIP switch) 0 V ... 5 V (via DIP switch) 1 V ... 5 V (via DIP switch) 0 V ... 10.5 V (can be set via software)
Max. voltage output signal
12.3 V
Current output signal
0 mA ... 20 mA (via DIP switch) 4 mA ... 20 mA (via DIP switch) 0 mA ... 10 mA (via DIP switch) 2 mA ... 10 mA (via DIP switch) 0 mA ... 21 mA (can be set via software)
Max. current output signal
24.6 mA
Load/output load voltage output
≥ 10 kΩ
Load/output load current output
≤ 600 Ω (20 mA)
Ripple
< 20 mV < 20 mV
Connection method
Screw connection
Stripping length
10 mm
Screw thread
M3
Conductor cross section rigid
0.2 mm² ... 1.5 mm² (with ferrule) 0.14 mm² ... 2.5 mm² (without ferrule)
Conductor cross section flexible
0.14 mm² ... 2.5 mm²
Conductor cross section AWG
24 ... 12 (flexible)
Tightening torque
0.5 Nm ... 0.6 Nm
Ex installation (EPL)
Gc Div. 2
Status display
Green LED (supply voltage) Yellow LED (switching output)
Error indication
Red LED
Width
6.2 mm
Height
109.81 mm
Depth
119.2 mm
Color
gray (RAL 7042)
Housing material
PBT
Fire protection for rail vehicles (DIN EN 45545-2) R22
HL 1 - HL 2
Fire protection for rail vehicles (DIN EN 45545-2) R23
HL 1 - HL 2
Fire protection for rail vehicles (DIN EN 45545-2) R24
HL 1 - HL 2
Degree of protection
IP20 (not assessed by UL)
Ambient temperature (operation)
-40 °C ... 70 °C
Ambient temperature (storage/transport)
-40 °C ... 85 °C
Altitude
≤ 2000 m
Permissible humidity (operation)
5 % ... 95 % (non-condensing)
Certificate
CE-compliant
Identification
 II 3 G Ex ec IIC T4 Gc
Certificate
BVS 20 ATEX E 024 X
Identification
 II 3 G Ex ec IIC T4 Gc
Certificate
PxCIF21UKEX2902049X
Identification
Ex ec IIC T4 Gc
Certificate
IECEx BVS 20.0017X
Identification
UL 508 Listed Class I, Div. 2, Groups A, B, C, D T5 Class I, Zone 2, Group IIC T5
Certificate
DNV GL TAA000021E Rev. 1
Identification
 2Ex ec IIC T4 Gc
Certificate
BY/112 02.01 TP012 103.01 00081
Temperature
B
Humidity
B
Vibration
A
EMC
A
Enclosure
Required protection according to the Rules shall be provided upon installation on board
Electromagnetic compatibility
Conformance with EMC directive
Noise immunity
EN 61000-6-2
Note
When being exposed to interference, there may be minimal deviations.
Noise emission
EN 61000-6-4
Standards/regulations
EN 61000-4-2
Comments
Safety measures must be taken to prevent electrostatic discharge.
Designation
Electromagnetic RF field
Standards/regulations
EN 61000-4-3
Typical deviation from the measuring range final value
0.2 %
Designation
Fast transients (burst)
Standards/regulations
EN 61000-4-4
Typical deviation from the measuring range final value
0.1 %
Standards/regulations
EN 61000-4-5
Designation
Conducted interferences
Standards/regulations
EN 61000-4-6
Typical deviation from the measuring range final value
2.8 %
Mounting type
DIN rail mounting
Assembly note
The DIN rail connector can be used for bridging the supply voltage. It can be snapped onto a 35 mm EN 60715 DIN rail.
Mounting position
any

Specifications may be subject to change without notice