Phoenix Contact MINI MCR-2-I-I-PT

Selling Points

  • 1Electrical Isolation: Safely isolate analog signals with reinforced insulation.
  • 2Plug-in Connection Technology: Easy push-in connections for solid conductors.
  • 3Versatile Signal Processing: Convert, amplify, and filter standard current signals.
  • 4Fault Monitoring & NFC: Supports fault monitoring and NFC communication.
  • 5Compact Design: Compact dimensions (6.2 mm x 110.5 mm x 120.5 mm) for space-saving installations.
Product Details
MINI MCR-2-I-I-PT
Phoenix Contact

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
EMC note
EMC: class A product, see manufacturer's declaration in the download area
Product type
Signal conditioner
Product family
MINI Analog Pro
No. of channels
1
Type
Signal conditioner
Article revision
12
Overvoltage category
II
Pollution degree
2
Electrical isolation
3-way isolation
Electrical isolation between input and output
yes
Limit frequency (3 dB)
 30 Hz
Protective circuit
Transient protection
Signal transmission behavior
In = Out
Step response (10-90%)
 10 ms
Maximum temperature coefficient
0.01 %/K
Temperature coefficient, typical
0.01 %/K
Maximum transmission error
0.1 % (of final value)
Rated insulation voltage
300 V
Test voltage
3 kV AC (50 Hz, 60 s)
Insulation
Reinforced insulation according to IEC/EN 61010-1
Nominal supply voltage
24 V DC
Supply voltage range
9.6 V DC ... 30 V DC (The DIN rail connector (ME 6,2 TBUS-2 1,5/5-ST-3,81 GN, item no. 2869728) can be used to bridge the supply voltage. It can be snapped onto a 35 mm DIN rail in accordance with EN 60715)
Typical current consumption
25 mA (24 V DC) 54 mA (12 V DC)
Power consumption
≤ 800 mW (at 9.6 V DC)
Number of inputs
1
Configurable/programmable
no
Current input signal
0 mA ... 20 mA 4 mA ... 20 mA
Input resistance current input
approx. 63 Ω (+0.7 V for test diode)
Number of outputs
1
Configurable/programmable
no
Non-load voltage
< 17 V
Current output signal
0 mA ... 20 mA 4 mA ... 20 mA
Max. current output signal
22 mA
Load/output load current output
≤ 600 Ω (at 20 mA)
Ripple
< 20 mV
Connection method
Push-in connection
Stripping length
10 mm
Conductor cross section rigid
0.2 mm² ... 2.5 mm² (with ferrule) 0.14 mm² ... 2.5 mm² (without ferrule)
Conductor cross section flexible
0.14 mm² ... 2.5 mm²
Conductor cross section AWG
24 ... 12 (flexible)
Ex installation (EPL)
Gc Div. 2
Status display
Green LED (supply voltage)
Width
6.2 mm
Height
109.81 mm
Depth
119.2 mm
Color
gray (RAL 7042)
Housing material
PBT
Fire protection for rail vehicles (DIN EN 45545-2) R22
HL 1 - HL 2
Fire protection for rail vehicles (DIN EN 45545-2) R23
HL 1 - HL 2
Fire protection for rail vehicles (DIN EN 45545-2) R24
HL 1 - HL 2
Degree of protection
IP20 (not assessed by UL)
Ambient temperature (operation)
-40 °C ... 70 °C
Ambient temperature (storage/transport)
-40 °C ... 85 °C
Permissible humidity (operation)
5 % ... 95 % (non-condensing)
Certificate
CE-compliant
Identification
 II 3 G Ex ec IIC T4 Gc
Certificate
BVS 19 ATEX E 047 X
Identification
 II 3 G Ex ec IIC T4 Gc
Certificate
PxCIF21UKEX2902000X
Identification
Ex ec IIC T4 Gc
Certificate
IECEx BVS 19.0041X
Identification
Ex nA IIC T4 Gc
Identification
UL 508 Listed Class I, Div. 2, Groups A, B, C, D T6 Class I, Zone 2, Group IIC T6
Certificate
DNV GL TAA00002UA
Identification
 2Ex ec IIC T4 Gc
Certificate
BY/112 02.01 TP012 103.01 00079
Temperature
B
Humidity
B
Vibration
A
EMC
A
Enclosure
Required protection according to the Rules shall be provided upon installation on board
Electromagnetic compatibility
Conformance with EMC directive
Noise immunity
EN 61000-6-2
Note
When being exposed to interference, there may be minimal deviations.
Noise emission
EN 61000-6-4
Standards/regulations
EN 61000-4-2
Comments
Safety measures must be taken to prevent electrostatic discharge.
Designation
Electromagnetic RF field
Standards/regulations
EN 61000-4-3
Designation
Fast transients (burst)
Standards/regulations
EN 61000-4-4
Standards/regulations
EN 61000-4-5
Designation
Conducted interferences
Standards/regulations
EN 61000-4-6
Electrical isolation
3-way isolation
Standards/regulations
GB 3836.1 GB 3836.8
Mounting type
DIN rail mounting
Assembly note
The DIN rail connector can be used for bridging the supply voltage. It can be snapped onto a 35 mm EN 60715 DIN rail.
Mounting position
any

Specifications may be subject to change without notice