Phoenix Contact MINI MCR-2-TC-UI-C

Selling Points

  • 1Configurable via DIP switches or software for customizable settings.
  • 2Supports 15 default thermocouple types and additional user-defined curves.
  • 33-way isolated design ensures high electrical safety and reliability.
  • 4NFC communication for easy configuration using the MINI Analog Pro app.
  • 5Fault monitoring and transient protection for robust performance in demanding environments.
Product Details
MINI MCR-2-TC-UI-C
Phoenix Contact

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
EMC note
EMC: class A product, see manufacturer's declaration in the download area
Product type
Temperature transmitter
Product family
MINI Analog Pro
Type
Signal conditioner
Configuration
DIP switches Software App
Article revision
15
Overvoltage category
II
Pollution degree
2
Electrical isolation
3-way isolation
Typical cold point errors
2 K (2 K + (0.2 K * ΔT))
Protective circuit
Transient protection
Step response (0–99%)
300 ms 570 ms
Maximum temperature coefficient
≤ 0.01 %/K
Transmission error thermocouples
0.1% * 600 K / set measuring range; 0.1% > 600 K (C, E, J, K, N, T, L, U, M Gost, L Gost) 0.2 % * 600 K / set measuring range; 0.2 % > 600 K (B, R, S, A1, A2, A3) 0.2% * 600 K / set measuring range; 0.2% > 600 K (E, J, K, N, T, L, U, M Gost, L Gost); Highspeed Mode 0.4% * 600 K / set measuring range; 0.4% > 600 K (B, R, S, A1, A2, A3); Highspeed Mode
Rated insulation voltage
300 V
Test voltage
3 kV AC (50 Hz, 60 s)
Insulation
Reinforced insulation according to IEC/EN 61010-1
Supply voltage range
9.6 V DC ... 30 V DC (The DIN rail connector (ME 6,2 TBUS-2 1,5/5-ST-3,81 GN, item no. 2869728) can be used to bridge the supply voltage. It can be snapped onto a 35 mm DIN rail in accordance with EN 60715)
Typical current consumption
32.7 mA (24 V DC) 66.8 mA (12 V DC)
Power consumption
≤ 850 mW (at I
Number of inputs
1
Number of inputs
1
Configurable/programmable
Yes
Input voltage range
- 500 mV ... 500 mV (can be set via software)
Sensor types that can be used (TC)
B, C, E, J, K, N, R, S, T, L, U, A-1, A-2, A-3, M, L
Temperature measuring range
-250 °C ... 2500 °C (Range depends on sensor type, range can be set freely via software or in increments from -150°C to 1350°C via DIP switches)
Temperature measuring range
≥ 50 K
Voltage measuring range
3 mV
Sensor type:
500 °C ... 1820 °C -230 °C ... 1000 °C -210 °C ... 1200 °C -250 °C ... 1372 °C -200 °C ... 1300 °C -50 °C ... 1768 °C -50 °C ... 1768 °C -200 °C ... 400 °C -200 °C ... 900 °C -200 °C ... 600 °C 0 °C ... 2500 °C 0 °C ... 1800 °C 0 °C ... 1800 °C -200 °C ... 100 °C -200 °C ... 800 °C
Number of outputs
1
Configurable/programmable
Yes
Voltage output signal
0 V ... 5 V (via DIP switch) 1 V ... 5 V (via DIP switch) 0 V ... 10 V (via DIP switch) 10 V ... 0 V (via DIP switch) 0 V ... 10.5 V (can be set via software)
Max. voltage output signal
 12.3 V
Non-load voltage
< 17.5 V
Current output signal
0 mA ... 20 mA (via DIP switch) 4 mA ... 20 mA (via DIP switch) 20 mA ... 0 mA (via DIP switch) 20 mA ... 4 mA (via DIP switch) 0 mA ... 21 mA (can be set via software)
Max. current output signal
24.6 mA
Short-circuit current
< 31.5 mA
Load/output load voltage output
≥ 10 kΩ
Load/output load current output
≤ 600 Ω (20 mA)
Ripple
< 10 mV < 10 mV
Resolution, outputs (voltage)
1 mV
Resolution, outputs (current)
2 µA
Connection method
Screw connection
Stripping length
10 mm
Screw thread
M3
Conductor cross section rigid
0.2 mm² ... 1.5 mm² (with ferrule) 0.14 mm² ... 2.5 mm² (without ferrule)
Conductor cross section flexible
0.14 mm² ... 2.5 mm²
Conductor cross section AWG
24 ... 12 (flexible)
Tightening torque
0.5 Nm ... 0.6 Nm
Ex installation (EPL)
Gc Div. 2
Connection method
Micro USB type B
Status display
Green LED (supply voltage)
Error indication
Red LED
Width
6.2 mm
Height
109.81 mm
Depth
119.2 mm
Color
gray (RAL 7042)
Housing material
PBT
Fire protection for rail vehicles (DIN EN 45545-2) R22
HL 1 - HL 2
Fire protection for rail vehicles (DIN EN 45545-2) R23
HL 1 - HL 2
Fire protection for rail vehicles (DIN EN 45545-2) R24
HL 1 - HL 2
Degree of protection
IP20 (not assessed by UL)
Ambient temperature (operation)
-40 °C ... 70 °C
Ambient temperature (storage/transport)
-40 °C ... 85 °C
Altitude
≤ 2000 m
Permissible humidity (operation)
5 % ... 95 % (non-condensing)
Certificate
CE-compliant
Identification
 II 3 G Ex ec IIC T4 Gc
Certificate
BVS 20 ATEX E 024 X
Identification
Ex ec IIC T4 Gc
Certificate
IECEx BVS 20.0017X
Identification
UL 508 Listed Class I, Div. 2, Groups A, B, C, D T6 Class I, Zone 2, Group IIC T6
Certificate
DNV GL TAA00002UA
Identification
 2Ex ec IIC T4 Gc
Certificate
BY/112 02.01 TP012 103.01 00079
Temperature
B
Humidity
B
Vibration
A
EMC
A
Enclosure
Required protection according to the Rules shall be provided upon installation on board
Electromagnetic compatibility
Conformance with EMC directive
Noise immunity
EN 61000-6-2
Note
When being exposed to interference, there may be minimal deviations.
Noise emission
EN 61000-6-4
Standards/regulations
EN 61000-4-2
Comments
Safety measures must be taken to prevent electrostatic discharge.
Designation
Electromagnetic RF field
Standards/regulations
EN 61000-4-3
Typical deviation from the measuring range final value
0.06 %
Designation
Fast transients (burst)
Standards/regulations
EN 61000-4-4
Typical deviation from the measuring range final value
0.1 %
Standards/regulations
EN 61000-4-5
Designation
Conducted interferences
Standards/regulations
EN 61000-4-6
Typical deviation from the measuring range final value
0.05 %
Electrical isolation
3-way isolation
Mounting type
DIN rail mounting
Assembly note
The DIN rail connector can be used for bridging the supply voltage. It can be snapped onto a 35 mm EN 60715 DIN rail.
Mounting position
any

Specifications may be subject to change without notice