Phoenix Contact MINI MCR-2-UI-FRO-PT-C

Selling Points

  • 1Adjust settings easily using DIP switches or software for precise control.
  • 2Process current signals between 0 mA and 24 mA, and voltage signals between 0 V and 12 V.
  • 3Generate frequency signals up to 11 kHz and PWM signals with variable pulse-pause ratios.
  • 4Operate the output as an additional switching point for two independent switching outputs.
  • 5Withstand ambient temperatures from -40°C to 70°C and feature IP20 protection for reliable operation.
Product Details
MINI MCR-2-UI-FRO-PT-C
Phoenix Contact

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
EMC note
EMC: class A product, see manufacturer's declaration in the download area
Product type
Frequency value transformer
Product family
MINI Analog Pro
No. of channels
1
Type
Signal conditioner
Configuration
DIP switches Software App
Article revision
05
Overvoltage category
II
Pollution degree
2
Configuration
DIP switches Software App
Electrical isolation between input and output
yes
Step response (0–99%)
120 ms (15 Hz sample rate) 35 ms (60 Hz sample rate) 15 ms (240 Hz sample rate, can only be set via software) 130 ms (15 Hz sample rate) 40 ms (60 Hz sample rate) 20 ms (240 Hz sample rate, can only be set via software)
Maximum temperature coefficient
< 0.01 %/K
Temperature coefficient, typical
0.01 %/K
Rated insulation voltage
300 V
Test voltage
3 kV AC (50 Hz, 60 s)
Insulation
Reinforced insulation according to IEC/EN 61010-1
Nominal supply voltage
24 V DC
Supply voltage range
9.6 V DC ... 30 V DC (The DIN rail connector (ME 6,2 TBUS-2 1,5/5-ST-3,81 GN, item no. 2869728) can be used to bridge the supply voltage. It can be snapped onto a 35 mm DIN rail in accordance with EN 60715)
Typical current consumption
27 mA (12 V DC) 13.5 mA (24 V DC)
Power consumption
≤ 350 mW (9.6 V DC)
Number of inputs
1
Configurable/programmable
Yes
Voltage input signal
0 V ... 10 V (via DIP switch) 2 V ... 10 V (via DIP switch) 0 V ... 5 V (via DIP switch) 1 V ... 5 V (via DIP switch) 10 V ... 0 V (via DIP switch) 10 V ... 2 V (via DIP switch) 5 V ... 0 V (via DIP switch) 5 V ... 1 V (via DIP switch) 0 V ... 12 V (can be set via software)
Max. voltage input signal
12 V
Current input signal
0 mA ... 20 mA (via DIP switch) 4 mA ... 20 mA (via DIP switch) 0 mA ... 10 mA (via DIP switch) 2 mA ... 10 mA (via DIP switch) 20 mA ... 0 mA (via DIP switch) 20 mA ... 4 mA (via DIP switch) 10 mA ... 0 mA (via DIP switch) 10 mA ... 2 mA (via DIP switch) 0 mA ... 24 mA (can be set via software)
Max. current input signal
24 mA
Input resistance of voltage input
> 120 kΩ
Input resistance current input
approx. 50 Ω (+0.7 V for test diode)
Frequency output
0 Hz ... 10 kHz (via DIP switch) 0 Hz ... 5 kHz (via DIP switch) 0 Hz ... 2.5 kHz (via DIP switch) 0 Hz ... 1 kHz (via DIP switch) 0 Hz ... 500 Hz (via DIP switch) 0 Hz ... 250 Hz (via DIP switch) 0 Hz ... 100 Hz (via DIP switch) 0 Hz ... 50 Hz (via DIP switch) 0 Hz ... 10.5 kHz (can be set via software)
Load min.
4 mA ≤ (U
Maximum transmission error
≤ 0.1 % (> 7 kHz ≤ 0.2 %)
Output signal PWM
15.6 kHz (10 bits, via DIP switch) 1.9 kHz (10 bits, via DIP switch) 3.9 kHz (12 bits, via DIP switch) 488 Hz (12 bits, via DIP switch) 977 Hz (14 bits, via DIP switch) 122 Hz (14 bits, via DIP switch) 244 Hz (16 bits, via DIP switch) 31 Hz (16 bits, via DIP switch) 31 Hz ... 15.6 kHz (can be set via software)
Load min.
12 mA ≤ (U
Maximum transmission error
< 0.2 % (PWM frequency  500 Hz) < 0.5 % (500 Hz < PWM frequency  2000 Hz) < 1 % (2000 Hz < PWM frequency  4000 Hz) < 2 % (4000 Hz < PWM frequency  8000 Hz) < 3 % (8000 Hz < PWM frequency  16000 Hz)
Load current maximum
100 mA
Maximum switching voltage
30 V DC
Overrange/underrange
can be set (via software)
Number of outputs
1
Contact switching type
1 N/O contact
Minimum switching voltage
1 V DC
Maximum switching voltage
30 V DC
Min. switching current
100 µA
Max. switching current
100 mA (30 V DC)
Number of outputs
1
Connection method
Push-in connection
Stripping length
10 mm
Conductor cross section rigid
0.2 mm² ... 2.5 mm² (with ferrule) 0.14 mm² ... 2.5 mm² (without ferrule)
Conductor cross section flexible
0.14 mm² ... 2.5 mm²
Conductor cross section AWG
24 ... 12 (flexible)
Ex installation (EPL)
Gc Div. 2
Connection method
Micro USB type B
Error indication
Red LED
Width
6.2 mm
Height
109.81 mm
Depth
119.2 mm
Color
gray (RAL 7042)
Housing material
PBT
Fire protection for rail vehicles (DIN EN 45545-2) R22
HL 1 - HL 2
Fire protection for rail vehicles (DIN EN 45545-2) R23
HL 1 - HL 2
Fire protection for rail vehicles (DIN EN 45545-2) R24
HL 1 - HL 2
Degree of protection
IP20 (not assessed by UL)
Ambient temperature (operation)
-40 °C ... 70 °C
Ambient temperature (storage/transport)
-40 °C ... 85 °C
Altitude
≤ 2000 m
Permissible humidity (operation)
5 % ... 95 % (non-condensing)
Certificate
CE-compliant
Identification
 II 3 G Ex ec IIC T4 Gc
Certificate
BVS 19 ATEX E 083 X
Identification
 II 3 G Ex ec IIC T4 Gc
Certificate
PxCIF21UKEX2905026X
Identification
Ex ec IIC T4 Gc
Certificate
IECEx BVS 19.0072X
Identification
Ex nA IIC T4 Gc
Certificate
NEPSI GYJ20.1318X
Identification
UL 508 Listed Class I, Div. 2, Groups A, B, C, D T6 Class I, Zone 2, Group IIC T6
Certificate
DNV GL TAA000021E Rev. 1
Identification
 2Ex ec IIC T4 Gc
Certificate
BY/112 02.01 TP012 103.01 00081
Temperature
B
Humidity
B
Vibration
A
EMC
A
Enclosure
Required protection according to the Rules shall be provided upon installation on board
Electromagnetic compatibility
Conformance with EMC directive
Noise immunity
EN 61000-6-2
Note
When being exposed to interference, there may be minimal deviations.
Noise emission
EN 61000-6-4
Mounting type
DIN rail mounting
Assembly note
The DIN rail connector can be used for bridging the supply voltage. It can be snapped onto a 35 mm EN 60715 DIN rail.
Mounting position
any

Specifications may be subject to change without notice