Product Model
MINI MCR-2-UI-I-OLP-PT

Selling Points
- 1Electrical Isolation: Reinforced insulation in accordance with IEC 61010-1 for reliable signal isolation.
- 2Configurable via DIP Switches: Set 74 input ranges using DIP switches for versatile configuration.
- 3Loop-Powered Design: Powered via the current loop of the controller, eliminating the need for a separate power supply.
- 4Wide Signal Range: Supports input signals from 0 mA to 40 mA and voltages up to 30 V.
- 5Compact Design: Dimensions are 6.2 mm x 110.5 mm x 120.5 mm, making it a space-efficient solution.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
EMC note | EMC: class A product, see manufacturer's declaration in the download area | Product type | Signal conditioner |
Product family | MINI Analog Pro | No. of channels | 1 |
Type | Signal conditioner | Configuration | DIP switches |
Article revision | 04 | Overvoltage category | II |
Pollution degree | 2 | Electrical isolation | 2-way isolation |
Electrical isolation between input and output | yes | Limit frequency (3 dB) | approx. 30 Hz |
Step response (10-90%) | 20 ms | Maximum temperature coefficient | 0.01 %/K |
Temperature coefficient, typical | 0.005 %/K | Maximum transmission error | ≤ 0.1 % (of final value) |
Rated insulation voltage | 300 V | Test voltage | 3 kV AC (50 Hz, 60 s) |
Insulation | Reinforced insulation according to IEC/EN 61010-1 | Supply voltage range | 8 V DC ... 30 V DC (loop-powered, no external supply necessary) |
Typical current consumption | ≤ 20 mA | Power consumption | ≤ 600 mW |
Number of inputs | 1 | Configurable/programmable | Yes |
Voltage input signal | 0 mV ... 1000 mV
0 mV ... 750 mV
0 mV ... 500 mV
0 mV ... 300 mV
0 mV ... 250 mV
0 mV ... 200 mV
0 mV ... 125 mV
0 mV ... 120 mV
0 mV ... 150 mV
0 mV ... 100 mV
0 mV ... 75 mV
0 mV ... 60 mV
0 mV ... 50 mV
0 V ... 10 V
0 V ... 7.5 V
0 V ... 5 V
0 V ... 3 V
0 V ... 2.5 V
0 V ... 2 V
0 V ... 1.5 V
0 V ... 1.25 V
0 V ... 1.2 V
0 V ... 30 V
0 V ... 25 V
0 V ... 20 V
0 V ... 12.5 V
0 V ... 12 V
0 V ... 15 V
-1000 mV ... 1000 mV
-750 mV ... 750 mV
-500 mV ... 500 mV
-300 mV ... 300 mV
-250 mV ... 250 mV
-200 mV ... 200 mV
-125 mV ... 125 mV
-120 mV ... 120 mV
-150 mV ... 150 mV
-100 mV ... 100 mV
-75 mV ... 75 mV
-60 mV ... 60 mV
-50 mV ... 50 mV
-10 V ... 10 V
-7.5 V ... 7.5 V
-5 V ... 5 V
-3 V ... 3 V
-2.5 V ... 2.5 V
-2 V ... 2 V
-1.25 V ... 1.25 V
-1.2 V ... 1.2 V
-1.5 V ... 1.5 V
-30 V ... 30 V
-25 V ... 25 V
-20 V ... 20 V
-12.5 V ... 12.5 V
-12 V ... 12 V
-15 V ... 15 V
2 V ... 10 V (additional areas can be configured, see table)
1 V ... 5 V (additional areas can be configured, see table) | Max. voltage input signal | < 30 V |
Current input signal | 0 mA ... 40 mA
0 mA ... 30 mA
0 mA ... 20 mA
0 mA ... 12 mA
0 mA ... 10 mA
0 mA ... 8 mA
0 mA ... 7.5 mA
0 mA ... 6 mA
0 mA ... 5 mA
0 mA ... 4 mA
0 mA ... 3 mA
0 mA ... 2.5 mA
0 mA ... 2 mA
4 mA ... 20 mA
2 mA ... 10 mA
1 mA ... 5 mA | Max. current input signal | 50 mA (Dielectric strength up to 30 V) |
Input resistance of voltage input | 100 kΩ (≤ 1 V)
1 MΩ (≥ 1 V) | Input resistance current input | 25 Ω (+0.7 V for test diode) |
Number of outputs | 1 | Current output signal | 4 mA ... 20 mA |
Max. current output signal | 32 mA | Load/output load current output | < 1000 Ω ((U |
Ripple | < 10 mV | Connection method | Push-in connection |
Stripping length | 10 mm | Conductor cross section rigid | 0.2 mm² ... 2.5 mm² (with ferrule)
0.14 mm² ... 2.5 mm² (without ferrule) |
Conductor cross section flexible | 0.14 mm² ... 2.5 mm² | Conductor cross section AWG | 24 ... 12 (flexible) |
Ex installation (EPL) | Gc
Div. 2 | Status display | Green LED (supply voltage) |
Width | 6.2 mm | Height | 109.81 mm |
Depth | 119.2 mm | Color | gray (RAL 7042) |
Housing material | PBT | Fire protection for rail vehicles (DIN EN 45545-2) R22 | HL 1 - HL 2 |
Fire protection for rail vehicles (DIN EN 45545-2) R23 | HL 1 - HL 2 | Fire protection for rail vehicles (DIN EN 45545-2) R24 | HL 1 - HL 2 |
Degree of protection | IP20 (not assessed by UL) | Ambient temperature (operation) | -40 °C ... 70 °C |
Ambient temperature (storage/transport) | -40 °C ... 85 °C | Altitude | ≤ 2000 m |
Permissible humidity (operation) | 5 % ... 95 % (non-condensing) | Certificate | CE-compliant |
Identification | II 3 G Ex ec IIC T4 Gc | Certificate | BVS 19 ATEX E 079 X |
Identification | II 3 G Ex ec IIC T4 Gc | Certificate | PxCIF21UKEX2901994X |
Identification | Ex ec IIC T4 Gc | Certificate | IECEx BVS 19.0068X |
Identification | Ex nA IIC T4 Gc | Identification | UL 508 Listed
Class I, Div. 2, Groups A, B, C, D T5
Class I, Zone 2, Group IIC T5 |
Certificate | DNV GL TAA000021E Rev. 1 | Identification | 2Ex ec IIC T4 Gc |
Certificate | BY/112 02.01 TP012 103.01 00081 | Temperature | B |
Humidity | B | Vibration | A |
EMC | A | Enclosure | Required protection according to the Rules shall be provided upon installation on board |
Electromagnetic compatibility | Conformance with EMC directive | Noise immunity | EN 61000-6-2 |
Note | When being exposed to interference, there may be minimal deviations. | Noise emission | EN 61000-6-4 |
Electrical isolation | 2-way isolation | Standards/regulations | GB 3836.1
GB 3836.8 |
Mounting type | DIN rail mounting | Mounting position | any |
Specifications may be subject to change without notice