Phoenix Contact MINI MCR-2-UNI-UI-2UI

Selling Points

  • 1Adjust settings easily using DIP switches or advanced software configurations.
  • 2Process current signals between 0-24 mA and voltage signals between 0-12 V on the input side.
  • 3Set both output signals independently, allowing for precise control over duplicated signals.
  • 4Reinforced insulation according to IEC 61010-1 and approval for Ex-zone 2 (nA) ensure safe operation.
  • 5Use the MINI Analog Pro Smartphone app via NFC for easy configuration and monitoring.
Product Details
MINI MCR-2-UNI-UI-2UI
Phoenix Contact

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
EMC note
EMC: class A product, see manufacturer's declaration in the download area
Product type
Signal duplicator
Product family
MINI Analog Pro
No. of channels
2
Type
Signal conditioner
Configuration
DIP switches Software App
Article revision
05
Overvoltage category
II
Pollution degree
2
Configuration
DIP switches Software App
Electrical isolation
4-way isolation
Step response (0–99%)
140 ms (15 Hz sample rate) 45 ms (60 Hz sample rate) 25 ms (240 Hz sample rate, can only be set via software)
Maximum temperature coefficient
0.01 %/K
Maximum transmission error
0.05 % (of final value)
Rated insulation voltage
300 V
Test voltage
3 kV AC (50 Hz, 60 s)
Insulation
Reinforced insulation according to IEC/EN 61010-1
Nominal supply voltage
24 V DC
Supply voltage range
9.6 V DC ... 30 V DC (The DIN rail connector (ME 6,2 TBUS-2 1,5/5-ST-3,81 GN, item no. 2869728) can be used to bridge the supply voltage. It can be snapped onto a 35 mm DIN rail in accordance with EN 60715)
Typical current consumption
55 mA (24 V DC) 110 mA (12 V DC)
Power consumption
1.5 W (at I
Number of inputs
1
Configurable/programmable
Yes
Voltage input signal
0 V ... 10 V (via DIP switch) 2 V ... 10 V (via DIP switch) 0 V ... 5 V (via DIP switch) 1 V ... 5 V (via DIP switch) 0 V ... 12 V (can be set via software)
Max. voltage input signal
12 V
Current input signal
0 mA ... 20 mA (via DIP switch) 4 mA ... 20 mA (via DIP switch) 0 mA ... 10 mA (via DIP switch) 20 mA ... 0 mA (via DIP switch) 0 mA ... 24 mA (can be set via software)
Max. current input signal
24 mA
Input resistance of voltage input
> 120 kΩ
Input resistance current input
~ 50 Ω (+0.7 V for test diode)
Number of outputs
2
Voltage output signal
0 V ... 10 V (via DIP switch) 2 V ... 10 V (via DIP switch) 0 V ... 5 V (via DIP switch) 1 V ... 5 V (via DIP switch) 0 V ... 10.5 V (can be set via software)
Max. voltage output signal
~ 12.3 V
Non-load voltage
≤ 18.5 V
Current output signal
0 mA ... 20 mA (via DIP switch) 4 mA ... 20 mA (via DIP switch) 0 mA ... 10 mA (via DIP switch) 20 mA ... 0 mA (via DIP switch) 0 mA ... 21 mA (can be set via software)
Max. current output signal
24.6 mA
Short-circuit current
≤ 25 mA
Load/output load voltage output
≥ 10 kΩ
Load/output load current output
≤ 600 Ω (per channel)
Ripple
< 20 mV < 20 mV
Connection method
Screw connection
Stripping length
10 mm
Screw thread
M3
Conductor cross section rigid
0.2 mm² ... 1.5 mm² (with ferrule) 0.14 mm² ... 2.5 mm² (without ferrule)
Conductor cross section flexible
0.14 mm² ... 2.5 mm²
Conductor cross section AWG
24 ... 12 (flexible)
Tightening torque
0.5 Nm ... 0.6 Nm
Ex installation (EPL)
Gc Div. 2
Connection method
Micro USB type B
Status display
Green LED (supply voltage)
Error indication
Red LED
Width
6.2 mm
Height
109.81 mm
Depth
119.2 mm
Color
gray (RAL 7042)
Housing material
PBT
Fire protection for rail vehicles (DIN EN 45545-2) R22
HL 1 - HL 2
Fire protection for rail vehicles (DIN EN 45545-2) R23
HL 1 - HL 2
Fire protection for rail vehicles (DIN EN 45545-2) R24
HL 1 - HL 2
Degree of protection
IP20 (not assessed by UL)
Ambient temperature (operation)
-40 °C ... 70 °C
Ambient temperature (storage/transport)
-40 °C ... 85 °C
Altitude
≤ 2000 m
Permissible humidity (operation)
5 % ... 95 % (non-condensing)
Certificate
CE-compliant
Identification
 II 3 G Ex ec IIC T4 Gc
Certificate
BVS 19 ATEX E 083 X
Identification
Ex ec IIC T4 Gc
Certificate
IECEx BVS 19.0072X
Identification
Ex ec IIC T4 Gc
Certificate
2022122310115962
Identification
UL 508 Listed Class I, Div. 2, Groups A, B, C, D T6 Class I, Zone 2, Group IIC T6
Certificate
DNV GL TAA000021E Rev. 1
Identification
 2Ex ec IIC T4 Gc
Certificate
BY/112 02.01 TP012 103.01 00081
Temperature
B
Humidity
B
Vibration
A
EMC
A
Enclosure
Required protection according to the Rules shall be provided upon installation on board
Electromagnetic compatibility
Conformance with EMC directive
Noise immunity
EN 61000-6-2
Note
When being exposed to interference, there may be minimal deviations.
Noise emission
EN 61000-6-4
Standards/regulations
EN 61000-4-2
Comments
Safety measures must be taken to prevent electrostatic discharge.
Designation
Electromagnetic RF field
Standards/regulations
EN 61000-4-3
Typical deviation from the measuring range final value
0.2 %
Designation
Fast transients (burst)
Standards/regulations
EN 61000-4-4
Typical deviation from the measuring range final value
0.1 %
Standards/regulations
EN 61000-4-5
Designation
Conducted interferences
Standards/regulations
EN 61000-4-6
Typical deviation from the measuring range final value
2.8 %
Electrical isolation
4-way isolation
Standards/regulations
GB/T 3836.1 GB/T 3836.3
Mounting type
DIN rail mounting
Assembly note
The DIN rail connector can be used for bridging the supply voltage. It can be snapped onto a 35 mm EN 60715 DIN rail.
Mounting position
any

Specifications may be subject to change without notice