Phoenix Contact MINI MCR-EX-RPSS-I-I-PT

Selling Points

  • 1Electrically isolates input and output signals for safe and reliable operation.
  • 2Features overvoltage category II and pollution degree 2 for enhanced safety.
  • 3Achieves step response of ≤ 10 ms for quick signal transmission.
  • 4Compact dimensions (6.2 mm width, 109.81 mm height, 119.2 mm depth) for easy installation.
  • 5Meets IEC/EN 61010-1 and ATEX standards for industrial applications.
Product Details
MINI MCR-EX-RPSS-I-I-PT
Phoenix Contact

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Product type
Repeater power supply
Product family
MINI Analog Pro
Application
Analog IN
Type
Ex i signal conditioners with SIL functional safety
Article revision
02
Line monitoring
Line fault detection
Signal transmission behavior
In = Out
Step response (10-90%)
≤ 10 ms
Maximum temperature coefficient
≤ 0.01 %
Maximum transmission error
≤ 0.1 %
Reverse polarity protection
yes
Overvoltage category
II (≤ 5000 m)
Pollution degree
2 (≤ 5000 m)
Standards/regulations
IEC/EN 61010-1
Rated insulation voltage
300 V
Test voltage
2.5 kV AC (50 Hz, 60 s)
Insulation
Double/reinforced insulation
Standards/regulations
IEC/EN 60079-11
Rated insulation voltage
253 V
Standards/regulations
IEC/EN 60079-7
Rated insulation voltage
251 V
Nominal supply voltage
24 V DC
Supply voltage range
19.2 V DC ... 30 V DC
Power consumption
≤ 1.4 W
Description of the input
Active current input, intrinsically safe
Current input signal
4 mA ... 20 mA
Transmitter supply voltage
> 16 V (20 mA) > 15.75 V (21 mA)
Description of the input
Passive current input, intrinsically safe
Current input signal
4 mA ... 20 mA 0 mA ... 20 mA
Voltage drop
< 4 V DC (20 mA)
Output description
Current output
Number of outputs
1
Current output signal
4 mA ... 20 mA
Load/output load current output
≤ 450 Ω (20 mA) ≤ 420 Ω (21 mA)
Non-load voltage
≤ 15 V DC
Short-circuit-proof
yes
Output description
Current output
Number of outputs
1
Current output signal
4 mA ... 20 mA 0 mA ... 20 mA
Load/output load current output
≤ 450 Ω (20 mA) ≤ 420 Ω (21 mA)
Connection method
Push-in connection
Stripping length
10 mm
Conductor cross section rigid
0.2 mm² ... 2.5 mm² (with ferrule) 0.14 mm² ... 2.5 mm² (without ferrule)
Conductor cross section flexible
0.14 mm² ... 2.5 mm²
Conductor cross section AWG
24 ... 12 (flexible)
Ex installation (EPL)
Gc Div. 2
Ex i circuits (EPL)
Ga Da Ma Div. 1
Max. output voltage U
26.4 V
Max. output current I
98 mA
Max. output power P
647 mW
Safety-related maximum voltage U
253 V AC 125 V DC
IIA/I (simple circuit): Max. external inductivity L
10 mH / 2.48 µF
IIB/III (simple circuit): Max. external inductivity L
4 mH / 730 nF
IIC (simple circuit): Max. external inductivity L
2 mH / 92 nF
IIA/I (mixed circuit): Max. external inductivity L
10 mH / 496 nF, 1 mH / 556 nF, 500 µH / 656 nF, 200 µH / 836 nF, 100 µH / 996 nF
IIB/III (mixed circuit): Max. external inductivity L
4 mH / 306 nF, 1 mH / 386 nF, 500 µH / 466 nF, 200 µH / 616 nF, 100 µH / 736 nF
IIC (mixed circuit): Max. external inductivity L
1.4 mH / 45 nF, 1 mH / 52 nF, 500 µH / 69 nF, 200 µH / 92 nF
Input voltage U
30 V
Input current I
150 mA
Max. internal inductance L
negligible
Max. internal capacitance C
4 µF
Safety-related maximum voltage U
253 V AC 125 V DC
IIA/I (simple circuit): Max. external inductivity L
10 mH / 2.48 µF
IIB/III (simple circuit): Max. external inductivity L
4 mH / 730 nF
IIC (simple circuit): Max. external inductivity L
2 mH / 92 nF
IIA/I (mixed circuit): Max. external inductivity L
10 mH / 496 nF, 1 mH / 556 nF, 500 µH / 656 nF, 200 µH / 836 nF, 100 µH / 996 nF
IIB/III (mixed circuit): Max. external inductivity L
4 mH / 306 nF, 1 mH / 386 nF, 500 µH / 466 nF, 200 µH / 616 nF, 100 µH / 736 nF
IIC (mixed circuit): Max. external inductivity L
1.4 mH / 45 nF, 1 mH / 52 nF, 500 µH / 69 nF, 200 µH / 92 nF
Connection method
S-PORT
Protocols supported
HART-transparent
Limit frequency (3 dB)
≥ 1.75 kHz
Status display
Green LED (supply voltage)
Width
6.2 mm
Height
109.81 mm
Depth
119.2 mm
Color
gray (RAL 7042)
Housing material
PBT
Ambient temperature (operation)
-40 °C ... 70 °C (Any mounting position)
Ambient temperature (storage/transport)
-40 °C ... 85 °C
Permissible humidity (operation)
5 % ... 95 % (at 25 °C, non-condensing)
Shock (operation)
15g (DIN EN 60068-2-27)
Vibration (operation)
5g (DIN EN 60068-2-6)
Height range
> 2000 m ... 3000 m
Ambient temperature (operation)
-40 °C ... 63 °C
Rated insulation voltage
300 V
Insulation
Double/reinforced insulation
Height range
> 3000 m ... 4000 m
Ambient temperature (operation)
-40 °C ... 56 °C
Rated insulation voltage
300 V
Insulation
Double/reinforced insulation
Height range
> 4000 m ... 5000 m
Ambient temperature (operation)
-40 °C ... 49 °C
Rated insulation voltage
150 V
Insulation
Double/reinforced insulation
Height range
> 2000 m ... 3000 m
Ambient temperature (operation)
-40 °C ... 63 °C
Safety-related maximum voltage U
121 V AC 110 V DC
Rated insulation voltage
150 V
Height range
> 3000 m ... 4000 m
Ambient temperature (operation)
-40 °C ... 56 °C
Safety-related maximum voltage U
33 V AC/DC
Rated insulation voltage
60 V
Height range
> 4000 m ... 5000 m
Ambient temperature (operation)
-40 °C ... 49 °C
Safety-related maximum voltage U
33 V AC/DC
Rated insulation voltage
60 V
Height range
> 2000 m ... 3000 m
Ambient temperature (operation)
-40 °C ... 63 °C
Rated insulation voltage
162 V
Height range
> 3000 m ... 4000 m
Ambient temperature (operation)
-40 °C ... 56 °C
Rated insulation voltage
60 V
Height range
> 4000 m ... 5000 m
Ambient temperature (operation)
-40 °C ... 49 °C
Rated insulation voltage
60 V
Certificate
CE-compliant
Identification
 II (1) G [Ex ia Ga] IIC  II (1) D [Ex ia Da] IIIC  II 3 (1) G Ex ec [ia Ga] IIC T4 Gc  I (M1) [Ex ia Ma] I
Certificate
BVS 23 ATEX 006 X
Identification
[Ex ia Ga] IIC [Ex ia Da] IIIC Ex ec [ia Ga] IIC T4 Gc [Ex ia Ma] I
Certificate
IECEx BVS 23.0003X
Identification
UL 61010-2-201
Identification
3
Note
Single-channel
Electromagnetic compatibility
Tested in accordance with the following standards and regulations: EN 61326-1 For industrial use, NAMUR NE 21
Low Voltage Directive
Conformance with Low Voltage Directive
Noise immunity
EN 61000-6-2 EN 61326-3-2
Noise emission
EN 61000-6-4
Mounting type
DIN rail mounting
Mounting position
any

Specifications may be subject to change without notice