Phoenix Contact MINI MCR-EX-SD-16-50-LFD-PT

Selling Points

  • 1Compact design with a width of 6.2 mm for space-saving installations.
  • 2Output voltage ≥ 10.7 V DC (50 mA) for precise control.
  • 3Internal resistance ≥ 103 Ω for efficient current limitation.
  • 4Line fault detection ensures safe operation with current limitation > 50 mA.
  • 5Red LED for error indication and easy troubleshooting.
Product Details
MINI MCR-EX-SD-16-50-LFD-PT
Phoenix Contact

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Product type
Solenoid driver
Product family
MINI Analog Pro
Article revision
02
Switch-on time
< 50 ms
Line monitoring
Line fault detection
Overvoltage category
II (≤ 5000 m)
Pollution degree
2 (≤ 5000 m)
Standards/regulations
IEC/EN 61010-1
Rated insulation voltage
250 V
Test voltage
2.5 kV AC (50 Hz, 60 s)
Insulation
Double/reinforced insulation
Standards/regulations
IEC/EN 61010-1
Rated insulation voltage
300 V
Test voltage
2.5 kV AC (50 Hz, 60 s)
Insulation
Double/reinforced insulation
Standards/regulations
IEC/EN 60079-11
Rated insulation voltage
265 V
Standards/regulations
IEC/EN 60079-7
Rated insulation voltage
251 V
Nominal supply voltage
24 V DC
Supply voltage range
19.2 V DC ... 30 V DC (24 V DC, -20 % ... +25 %)
Power consumption
< 1.4 W
Number of inputs
1
Switching level "0" signal
0 V DC ... 5 V DC
Switching level "1" signal
15 V DC ... 30 V DC
Input current
< 3 mA
Input impedance
> 1 MΩ (high-resistance in the event of a line fault at the output)
Line fault detection
< 25 Ω (Short circuit) > 10 kΩ (Line break)
Type of output signal
Transistor output via T-BUS
Output description
intrinsically safe
Number of outputs
1
Output voltage
≥ 10.7 V DC (50 mA)
Output resistor
≥ 103 Ω (Internal resistance R
Current limitation
> 50 mA (with line fault detection)
Response time
< 20 ms
Non-load voltage
> 16 V DC
Short-circuit-proof
yes
Line fault detection
> 10 kΩ (Line break) < 25 Ω (Short circuit) Activated /deactivated via DIP switch
Connection method
Push-in connection
Stripping length
10 mm
Conductor cross section rigid
0.2 mm² ... 2.5 mm² (with ferrule) 0.14 mm² ... 2.5 mm² (without ferrule)
Conductor cross section flexible
0.14 mm² ... 2.5 mm²
Conductor cross section AWG
24 ... 12 (flexible)
Ex installation (EPL)
Gc Div. 2
Ex i circuits (EPL)
Ga Da Ma Div. 1
Max. internal inductance L
negligible
Max. internal capacitance C
11 nF
Max. output voltage U
19.2 V
Max. output current I
185 mA
Max. output power P
888 mW
Safety-related maximum voltage U
253 V AC 125 V DC
IIA (simple circuit): Max. external inductivity L
7 mH / 6.1 µF
IIB/IIIC (simple circuit): Max. external inductivity L
4 mH / 1.53 µF
IIC (simple circuit): Max. external inductivity L
0.8 mH / 240 nF
I (simple circuit): Max. external inductivity L
10 mH / 8.7 µF
Error indication
Red LED
Width
6.2 mm
Height
109.81 mm
Depth
119.2 mm
Color
gray (RAL 7042)
Degree of protection
IP20
Ambient temperature (operation)
-40 °C ... 70 °C
Ambient temperature (storage/transport)
-40 °C ... 85 °C
Permissible humidity (operation)
5 % ... 95 % (non-condensing)
Height range
> 2000 m ... 3000 m
Ambient temperature (operation)
-40 °C ... 63 °C
Rated insulation voltage
300 V 250 V
Insulation
Double/reinforced insulation
Height range
> 3000 m ... 4000 m
Ambient temperature (operation)
-40 °C ... 56 °C
Rated insulation voltage
300 V 250 V
Insulation
Double/reinforced insulation
Height range
> 4000 m ... 5000 m
Ambient temperature (operation)
-40 °C ... 49 °C
Rated insulation voltage
150 V
Insulation
Double/reinforced insulation
Height range
> 2000 m ... 3000 m
Ambient temperature (operation)
-40 °C ... 63 °C
Safety-related maximum voltage U
121 V AC 110 V DC
Rated insulation voltage
150 V
Height range
> 3000 m ... 4000 m
Ambient temperature (operation)
-40 °C ... 56 °C
Safety-related maximum voltage U
33 V AC/DC
Rated insulation voltage
60 V
Height range
> 4000 m ... 5000 m
Ambient temperature (operation)
-40 °C ... 49 °C
Safety-related maximum voltage U
33 V AC/DC
Rated insulation voltage
60 V
Height range
> 2000 m ... 3000 m
Ambient temperature (operation)
-40 °C ... 63 °C
Rated insulation voltage
162 V
Height range
> 3000 m ... 4000 m
Ambient temperature (operation)
-40 °C ... 56 °C
Rated insulation voltage
60 V
Height range
> 4000 m ... 5000 m
Ambient temperature (operation)
-40 °C ... 49 °C
Rated insulation voltage
60 V
Certificate
CE-compliant
Identification
 II (1) G [Ex ia Ga] IIC  II (1) D [Ex ia Da] IIIC  II 3 (1) G Ex ec [ia Ga] IIC T4 Gc  I (M1) [Ex ia Ma] I
Certificate
TÜV 21 ATEX 8651 X
Identification
[Ex ia Ga] IIC [Ex ia Da] IIIC Ex ec [ia Ga] IIC T4 Gc [Ex ia Ma] I
Certificate
IECEx TUR 21.0043 X
Identification
 II (1) G [Ex ia Ga] IIC  II (1) D [Ex ia Da] IIIC  II 3 (1) G Ex ec [ia Ga] IIC T4 Gc  I (M1) [Ex ia Ma] I
Certificate
TÜV 21 UKEX 7021 X
Identification
[Ex ia Ga] IIC [Ex ia Da] IIIC Ex ec [ia Ga] IIC T4 Gc
Certificate
2023122310116238
Identification
UL 61010-2-201
Identification
3
Electromagnetic compatibility
Tested in accordance with the following standards and regulations: EN 61326-1 For industrial use, NAMUR NE 21
Noise immunity
IEC/EN 61000-6-2 IEC/EN 61326-3-2
Noise emission
IEC/EN 61000-6-4
Standards/regulations
GB/T 3836.1 GB/T 3836.3 GB/T 3836.4

Specifications may be subject to change without notice