Product Model
MINI MCR-SL-I-U-0

Selling Points
- 1Compact Design: 6.2 mm wide, ideal for space-constrained applications.
- 2Low Power Consumption: Efficient operation with minimal power requirements.
- 3High-Isolation Performance: 3-way electrical isolation for secure signal processing.
- 4Versatile Input/Output: Supports input signals from 0 mA to 20 mA and output signals from 0 V to 10 V.
- 5Durable and Reliable: Compliant with EMC Directive 2004/108/EC and rated for ambient temperatures from -20°C to 65°C.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
EMC note | EMC: class A product, see manufacturer's declaration in the download area | Product type | Signal conditioner |
Product family | MINI Analog | No. of channels | 1 |
Article revision | 11 | Overvoltage category | II |
Pollution degree | 2 | Electrical isolation | Basic insulation in accordance with EN 61010 |
Electrical isolation between input and output | yes | Limit frequency (3 dB) | approx. 100 Hz |
Step response (10-90%) | 3.5 ms | Maximum temperature coefficient | < 0.01 %/K |
Temperature coefficient, typical | < 0.002 %/K | Maximum transmission error | ≤ 0.1 % (of final value) |
Rated insulation voltage | 30 V AC
50 V DC | Test voltage | 1.5 kV AC (50 Hz, 60 s) |
Nominal supply voltage | 24 V DC | Supply voltage range | 19.2 V DC ... 30 V DC (The DIN rail connector (ME 6,2 TBUS-2 1,5/5-ST-3,81 GN, item no. 2869728) can be used to bridge the supply voltage. It can be snapped onto a 35 mm DIN rail in accordance with EN 60715) |
Max. current consumption | < 9 mA | Power consumption | < 200 mW |
Number of inputs | 1 | Configurable/programmable | no |
Current input signal | 0 mA ... 20 mA | Max. current input signal | 50 mA |
Input resistance current input | approx. 50 Ω | Number of outputs | 1 |
Configurable/programmable | no | Voltage output signal | 0 V ... 10 V |
Max. voltage output signal | 12.5 V | Short-circuit current | approx. 2 mA |
Load/output load voltage output | ≥ 10 kΩ | Ripple | < 20 mV |
Connection method | Screw connection | Stripping length | 12 mm |
Screw thread | M3 | Conductor cross section rigid | 0.2 mm² ... 2.5 mm² |
Conductor cross section flexible | 0.2 mm² ... 2.5 mm² | Conductor cross section AWG | 26 ... 12 |
Width | 6.2 mm | Height | 93.1 mm |
Depth | 101.2 mm | Color | green (RAL 6021) |
Housing material | PBT | Fire protection for rail vehicles (DIN EN 45545-2) R22 | HL 1 - HL 2 |
Fire protection for rail vehicles (DIN EN 45545-2) R23 | HL 1 - HL 2 | Fire protection for rail vehicles (DIN EN 45545-2) R24 | HL 1 - HL 2 |
Degree of protection | IP20 | Ambient temperature (operation) | -20 °C ... 65 °C |
Ambient temperature (storage/transport) | -40 °C ... 85 °C | Altitude | ≤ 2000 m |
Permissible humidity (operation) | 5 % ... 95 % (non-condensing) | Certificate | CE-compliant |
Certificate | UKCA-compliant | Identification | UL 508 Recognized
Class I, Div. 2, Groups A, B, C, D T4 |
Certificate | DNV GL TAA000020N | Temperature | B |
Humidity | B | Vibration | B |
EMC | A | Enclosure | Required protection according to the Rules shall be provided upon installation on board |
Electromagnetic compatibility | Conformance with EMC directive | Noise immunity | EN 61000-6-2 |
Note | When being exposed to interference, there may be minimal deviations. | Noise emission | EN 61000-6-4 |
Standards/regulations | EN 61000-4-2 | Comments | Safety measures must be taken to prevent electrostatic discharge. |
Designation | Electromagnetic RF field | Standards/regulations | EN 61000-4-3 |
Typical deviation from the measuring range final value | 5 % | Designation | Fast transients (burst) |
Standards/regulations | EN 61000-4-4 | Typical deviation from the measuring range final value | 5 % |
Standards/regulations | EN 61000-4-5 | Comments | Criterion B |
Designation | Conducted interferences | Standards/regulations | EN 61000-4-6 |
Typical deviation from the measuring range final value | 5 % | Electrical isolation | Basic insulation in accordance with EN 61010 |
Mounting type | DIN rail mounting | Assembly note | The DIN rail connector can be used for bridging the supply voltage. It can be snapped onto a 35 mm EN 60715 DIN rail. |
Mounting position | any |
Specifications may be subject to change without notice