MINI MCR-SL-PT100-UI-200-SP-NC

Selling Points
- 1Supports 2, 3, or 4-wire Pt 100 sensors according to IEC 60751.
- 2Measures temperatures from -50°C to +200°C for increased accuracy.
- 3Features diagnostic LED and analog signal for error indication.
- 4Power supply possible via the foot element (TBUS) or DIN rail bus connector.
- 5Highly-compact design with dimensions of 6.2 mm wide, 93.1 mm high, and 102.5 mm deep.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Product type | Temperature transmitter | Product family | MINI Analog |
Article revision | 10 | Overvoltage category | II |
Pollution degree | 2 | Rated insulation voltage | 50 V AC/DC |
Electrical isolation | Basic insulation in accordance with EN 61010 | Maximum power dissipation for nominal condition | 235.5 mW |
Test voltage, input/output/supply | 1.5 kV AC (50 Hz, 60 s) | Protective circuit | Transient protection |
Step response (0–99%) | < 200 ms | Maximum temperature coefficient | < 0.02 %/K |
Transmission error in the set measuring range | ((50 K / Δ Temp)+ 0.05)% | Transmission error in the full measuring range | ≤ 0.25 % |
Nominal supply voltage | 24 V DC | Supply voltage range | 19.2 V DC ... 30 V DC (The DIN rail connector (ME 6,2 TBUS-2 1,5/5-ST-3,81 GN, item no. 2869728) can be used to bridge the supply voltage. It can be snapped onto a 35 mm DIN rail in accordance with EN 60715) |
Max. current consumption | < 21 mA (at 24 V DC) | Power consumption | < 500 mW |
Number of inputs | 1 | Input signal | Temperature |
Sensor types (RTD) that can be used | Pt 100 (IEC 60751/EN 60751) | Temperature measuring range | -50 °C ... 200 °C |
Temperature measuring range | min. 50 K | Sensor type: | -50 °C ... 200 °C (configurable) |
Sensor input current | 1 mA (constant) | Max. permissible overall conductor resistance | 10 Ω (Per cable) |
Connection technology | 2-, 3-, 4-conductor | Number of outputs | 1 |
Configurable/programmable | Yes | Voltage output signal | 0 V ... 10 V
10 V ... 0 V
0 V ... 5 V
1 V ... 5 V |
Max. voltage output signal | approx. 12.5 V | Non-load voltage | approx. 12.5 V |
Current output signal | 0 mA ... 20 mA
4 mA ... 20 mA
20 mA ... 0 mA
20 mA ... 4 mA | Max. current output signal | 23 mA |
Short-circuit current | approx. 10 mA | Load/output load voltage output | > 10 kΩ |
Load/output load current output | < 500 Ω (at 20 mA) | Ripple | < 20 mV
< 20 mV |
Connection method | Spring-cage connection | Stripping length | 8 mm |
Conductor cross section rigid | 0.2 mm² ... 2.5 mm² | Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
Conductor cross section AWG | 24 ... 12 | Width | 6.2 mm |
Height | 93.1 mm | Depth | 102.5 mm |
Color | green (RAL 6021) | Housing material | PBT |
Fire protection for rail vehicles (DIN EN 45545-2) R22 | HL 1 - HL 2 | Fire protection for rail vehicles (DIN EN 45545-2) R23 | HL 1 - HL 2 |
Fire protection for rail vehicles (DIN EN 45545-2) R24 | HL 1 - HL 2 | Degree of protection | IP20 |
Ambient temperature (operation) | -20 °C ... 65 °C | Ambient temperature (storage/transport) | -40 °C ... 85 °C |
Permissible humidity (operation) | 10 % ... 95 % (non-condensing) | Certificate | CE-compliant |
Identification | II 3 G Ex nA IIC T4 Gc X | Identification | UL 508 Recognized
Class I, Div. 2, Groups A, B, C, D T5 |
Identification | GL EMC 2 D | Electromagnetic compatibility | Conformance with EMC directive |
Noise immunity | EN 61000-6-2 | Note | When being exposed to interference, there may be minimal deviations. |
Noise emission | EN 61000-6-4 | Standards/regulations | EN 61000-4-2 |
Comments | Safety measures must be taken to prevent electrostatic discharge. | Designation | Electromagnetic RF field |
Standards/regulations | EN 61000-4-3 | Typical deviation from the measuring range final value | 10 % |
Designation | Fast transients (burst) | Standards/regulations | EN 61000-4-4 |
Typical deviation from the measuring range final value | 10 % | Standards/regulations | EN 61000-4-5 |
Comments | Criterion B | Designation | Conducted interferences |
Standards/regulations | EN 61000-4-6 | Typical deviation from the measuring range final value | 10 % |
Electrical isolation | Basic insulation in accordance with EN 61010 | Mounting type | DIN rail mounting |
Mounting position | any |
Specifications may be subject to change without notice