Product Model

MINI MCR-SL-PT100-UI-200-SP-NC

In Stock
Last updated: 2025/4/27
Phoenix Contact MINI MCR-SL-PT100-UI-200-SP-NC

Selling Points

  • 1Supports 2, 3, or 4-wire Pt 100 sensors according to IEC 60751.
  • 2Measures temperatures from -50°C to +200°C for increased accuracy.
  • 3Features diagnostic LED and analog signal for error indication.
  • 4Power supply possible via the foot element (TBUS) or DIN rail bus connector.
  • 5Highly-compact design with dimensions of 6.2 mm wide, 93.1 mm high, and 102.5 mm deep.
Product Details
MINI MCR-SL-PT100-UI-200-SP-NC
Phoenix Contact

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Product type
Temperature transmitter
Product family
MINI Analog
Article revision
10
Overvoltage category
II
Pollution degree
2
Rated insulation voltage
50 V AC/DC
Electrical isolation
Basic insulation in accordance with EN 61010
Maximum power dissipation for nominal condition
235.5 mW
Test voltage, input/output/supply
1.5 kV AC (50 Hz, 60 s)
Protective circuit
Transient protection
Step response (0–99%)
< 200 ms
Maximum temperature coefficient
< 0.02 %/K
Transmission error in the set measuring range
((50 K / Δ Temp)+ 0.05)%
Transmission error in the full measuring range
≤ 0.25 %
Nominal supply voltage
24 V DC
Supply voltage range
19.2 V DC ... 30 V DC (The DIN rail connector (ME 6,2 TBUS-2 1,5/5-ST-3,81 GN, item no. 2869728) can be used to bridge the supply voltage. It can be snapped onto a 35 mm DIN rail in accordance with EN 60715)
Max. current consumption
< 21 mA (at 24 V DC)
Power consumption
< 500 mW
Number of inputs
1
Input signal
Temperature
Sensor types (RTD) that can be used
Pt 100 (IEC 60751/EN 60751)
Temperature measuring range
-50 °C ... 200 °C
Temperature measuring range
min. 50 K
Sensor type:
-50 °C ... 200 °C (configurable)
Sensor input current
1 mA (constant)
Max. permissible overall conductor resistance
10 Ω (Per cable)
Connection technology
2-, 3-, 4-conductor
Number of outputs
1
Configurable/programmable
Yes
Voltage output signal
0 V ... 10 V 10 V ... 0 V 0 V ... 5 V 1 V ... 5 V
Max. voltage output signal
approx. 12.5 V
Non-load voltage
approx. 12.5 V
Current output signal
0 mA ... 20 mA 4 mA ... 20 mA 20 mA ... 0 mA 20 mA ... 4 mA
Max. current output signal
23 mA
Short-circuit current
approx. 10 mA
Load/output load voltage output
> 10 kΩ
Load/output load current output
< 500 Ω (at 20 mA)
Ripple
< 20 mV < 20 mV
Connection method
Spring-cage connection
Stripping length
8 mm
Conductor cross section rigid
0.2 mm² ... 2.5 mm²
Conductor cross section flexible
0.2 mm² ... 2.5 mm²
Conductor cross section AWG
24 ... 12
Width
6.2 mm
Height
93.1 mm
Depth
102.5 mm
Color
green (RAL 6021)
Housing material
PBT
Fire protection for rail vehicles (DIN EN 45545-2) R22
HL 1 - HL 2
Fire protection for rail vehicles (DIN EN 45545-2) R23
HL 1 - HL 2
Fire protection for rail vehicles (DIN EN 45545-2) R24
HL 1 - HL 2
Degree of protection
IP20
Ambient temperature (operation)
-20 °C ... 65 °C
Ambient temperature (storage/transport)
-40 °C ... 85 °C
Permissible humidity (operation)
10 % ... 95 % (non-condensing)
Certificate
CE-compliant
Identification
 II 3 G Ex nA IIC T4 Gc X
Identification
UL 508 Recognized Class I, Div. 2, Groups A, B, C, D T5
Identification
GL EMC 2 D
Electromagnetic compatibility
Conformance with EMC directive
Noise immunity
EN 61000-6-2
Note
When being exposed to interference, there may be minimal deviations.
Noise emission
EN 61000-6-4
Standards/regulations
EN 61000-4-2
Comments
Safety measures must be taken to prevent electrostatic discharge.
Designation
Electromagnetic RF field
Standards/regulations
EN 61000-4-3
Typical deviation from the measuring range final value
10 %
Designation
Fast transients (burst)
Standards/regulations
EN 61000-4-4
Typical deviation from the measuring range final value
10 %
Standards/regulations
EN 61000-4-5
Comments
Criterion B
Designation
Conducted interferences
Standards/regulations
EN 61000-4-6
Typical deviation from the measuring range final value
10 %
Electrical isolation
Basic insulation in accordance with EN 61010
Mounting type
DIN rail mounting
Mounting position
any

Specifications may be subject to change without notice