Product Model

MINI MCR-SL-UI-2I

In Stock
Last updated: 2025/4/20
Phoenix Contact MINI MCR-SL-UI-2I

Selling Points

  • 1Configurable 4-way isolating amplifier for electrical isolation and signal duplication.
  • 2Customizable input/output signal ranges via DIP switches for precise control.
  • 3Highly compact design with dimensions 6.2 mm wide, 93.1 mm high, and 102.5 mm deep.
  • 4Power supply via terminal blocks or DIN rail connector, with a range of 19.2 V DC to 30 V DC.
  • 5Factory calibration certificate available, ensuring precise performance and reliability.
Product Details
MINI MCR-SL-UI-2I
Phoenix Contact

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Product type
Signal duplicator
Product family
MINI Analog
No. of channels
2
Article revision
10
Overvoltage category
II
Pollution degree
2
Rated insulation voltage
50 V AC/DC
Electrical isolation
Basic insulation in accordance with EN 61010
Electrical isolation between input and output
yes
Limit frequency (3 dB)
approx. 35 Hz
Maximum power dissipation for nominal condition
500 mW
Test voltage, input/output/supply
1.5 kV AC (50 Hz, 60 s)
Protective circuit
Transient protection
Step response (0–99%)
 10 ms
Maximum temperature coefficient
< 0.01 %/K
Temperature coefficient, typical
< 0.004 %/K
Maximum transmission error
≤ 0.2 % (of final value)
Transmission error, typical
< 0.1 %
Nominal supply voltage
24 V DC
Supply voltage range
19.2 V DC ... 30 V DC (The DIN rail connector (ME 6,2 TBUS-2 1,5/5-ST-3,81 GN, item no. 2869728) can be used to bridge the supply voltage. It can be snapped onto a 35 mm DIN rail in accordance with EN 60715)
Max. current consumption
< 30 mA (at 24 V DC incl. load)
Power consumption
< 600 mW
Number of inputs
1
Configurable/programmable
Yes, preconfigured
Voltage input signal
0 V ... 10 V 1 V ... 5 V
Max. voltage input signal
30 V
Current input signal
0 mA ... 20 mA 4 mA ... 20 mA
Max. current input signal
50 mA
Input resistance of voltage input
approx. 100 kΩ
Input resistance current input
approx. 50 Ω
Number of outputs
2
Configurable/programmable
Yes, preconfigured
Non-load voltage
9 V
Current output signal
2x 0 mA ... 20 mA 2x 4 mA ... 20 mA
Max. current output signal
approx. 22 mA
Load/output load current output
≤ 250 Ω (at 20 mA)
Ripple
< 20 mV
Connection method
Screw connection
Stripping length
12 mm
Screw thread
M3
Conductor cross section rigid
0.2 mm² ... 2.5 mm²
Conductor cross section flexible
0.2 mm² ... 2.5 mm²
Conductor cross section AWG
26 ... 12
Width
6.2 mm
Height
93.1 mm
Depth
102.5 mm
Color
green (RAL 6021)
Housing material
PBT
Fire protection for rail vehicles (DIN EN 45545-2) R22
HL 1 - HL 2
Fire protection for rail vehicles (DIN EN 45545-2) R23
HL 1 - HL 2
Fire protection for rail vehicles (DIN EN 45545-2) R24
HL 1 - HL 2
Degree of protection
IP20
Ambient temperature (operation)
-20 °C ... 60 °C
Ambient temperature (storage/transport)
-40 °C ... 85 °C
Permissible humidity (operation)
10 % ... 95 % (non-condensing)
Certificate
CE-compliant
Identification
 II 3 G Ex nA IIC T4 Gc X
Identification
UL 508 Recognized Class I, Div. 2, Groups A, B, C, D T5
Identification
GL EMC 2 D
Electromagnetic compatibility
Conformance with EMC directive
Noise immunity
EN 61000-6-2
Note
When being exposed to interference, there may be minimal deviations.
Noise emission
EN 61000-6-4
Standards/regulations
EN 61000-4-2
Comments
Safety measures must be taken to prevent electrostatic discharge.
Designation
Electromagnetic RF field
Standards/regulations
EN 61000-4-3
Typical deviation from the measuring range final value
5 %
Designation
Fast transients (burst)
Standards/regulations
EN 61000-4-4
Typical deviation from the measuring range final value
5 %
Standards/regulations
EN 61000-4-5
Comments
Criterion B
Designation
Conducted interferences
Standards/regulations
EN 61000-4-6
Typical deviation from the measuring range final value
5 %
Electrical isolation
Basic insulation in accordance with EN 61010
Mounting type
DIN rail mounting
Assembly note
The DIN rail connector can be used for bridging the supply voltage. It can be snapped onto a 35 mm EN 60715 DIN rail.
Mounting position
any

Specifications may be subject to change without notice