Product Model

MINI MCR-SL-U-U-SP

In Stock
Last updated: 2025/4/19
Phoenix Contact MINI MCR-SL-U-U-SP

Selling Points

  • 1DIN Rail Mounting: Easily integrate into industrial settings with DIN rail mounting.
  • 2Robust Temperature Range: Operates from -20°C to +60°C, ensuring reliability in various environments.
  • 3Versatile Output Signals: Provides both current and voltage output signals for diverse applications.
  • 4Compact Design: Highly compact design for space-efficient installations.
  • 5Integrated Optical Diagnostics: Includes integrated optical diagnostics for enhanced performance and diagnostics.
Product Details
MINI MCR-SL-U-U-SP
Phoenix Contact

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Product type
Signal conditioner
Product family
MINI Analog
No. of channels
1
Article revision
10
Overvoltage category
II
Pollution degree
2
Rated insulation voltage
50 V AC/DC
Electrical isolation
Basic insulation in accordance with EN 61010
Electrical isolation between input and output
yes
Limit frequency (3 dB)
approx. 100 Hz
Maximum power dissipation for nominal condition
224 mW
Test voltage, input/output/supply
1.5 kV AC (50 Hz, 60 s)
Protective circuit
Transient protection
Step response (10-90%)
approx. 3.2 ms
Maximum temperature coefficient
< 0.01 %/K
Temperature coefficient, typical
< 0.002 %/K
Maximum transmission error
≤ 0.1 % (of final value)
Nominal supply voltage
24 V DC
Supply voltage range
19.2 V DC ... 30 V DC (The DIN rail connector (ME 6,2 TBUS-2 1,5/5-ST-3,81 GN, item no. 2869728) can be used to bridge the supply voltage. It can be snapped onto a 35 mm DIN rail in accordance with EN 60715)
Max. current consumption
< 9 mA
Power consumption
< 200 mW (at 24 V DC)
Number of inputs
1
Configurable/programmable
no
Voltage input signal
0 V ... 10 V -10 V ... 10 V
Max. voltage input signal
30 V
Input resistance of voltage input
approx. 100 kΩ
Number of outputs
1
Configurable/programmable
no
Voltage output signal
0 V ... 10 V -10 V ... 10 V
Max. voltage output signal
12.5 V
Short-circuit current
approx. 2 mA
Load/output load voltage output
≥ 10 kΩ
Ripple
< 20 mV
Connection method
Spring-cage connection
Stripping length
8 mm
Conductor cross section rigid
0.2 mm² ... 2.5 mm²
Conductor cross section flexible
0.2 mm² ... 2.5 mm²
Conductor cross section AWG
24 ... 12
Width
6.2 mm
Height
93.1 mm
Depth
102.5 mm
Color
green (RAL 6021)
Housing material
PBT
Fire protection for rail vehicles (DIN EN 45545-2) R22
HL 1 - HL 2
Fire protection for rail vehicles (DIN EN 45545-2) R23
HL 1 - HL 2
Fire protection for rail vehicles (DIN EN 45545-2) R24
HL 1 - HL 2
Degree of protection
IP20
Ambient temperature (operation)
-20 °C ... 65 °C
Ambient temperature (storage/transport)
-40 °C ... 85 °C
Certificate
CE-compliant
Identification
 II 3 G Ex nA IIC T4 Gc X
Identification
UL 508 Recognized Class I, Div. 2, Groups A, B, C, D T5
Identification
GL EMC 2 D
Electromagnetic compatibility
Conformance with EMC directive
Noise immunity
EN 61000-6-2
Note
When being exposed to interference, there may be minimal deviations.
Noise emission
EN 61000-6-4
Comments
Safety measures must be taken to prevent electrostatic discharge.
Designation
Electromagnetic RF field
Standards/regulations
EN 61000-4-3
Typical deviation from the measuring range final value
15 %
Designation
Fast transients (burst)
Standards/regulations
EN 61000-4-4
Typical deviation from the measuring range final value
15 %
Designation
Conducted interferences
Standards/regulations
EN 61000-4-6
Typical deviation from the measuring range final value
15 %
Electrical isolation
Basic insulation in accordance with EN 61010
Mounting type
DIN rail mounting
Assembly note
The DIN rail connector can be used for bridging the supply voltage. It can be snapped onto a 35 mm EN 60715 DIN rail.
Mounting position
any