Product Model
MINI MCR-TC-UI-NC

Selling Points
- 1Configurable via DIP switches or software for flexible setup.
- 23-way electrical isolation ensures safe and reliable operation.
- 3Wide temperature range from -250°C to 2500°C, accommodating diverse applications.
- 4High accuracy with typical cold point errors less than 2 K.
- 5Compact design with dimensions (W/H/D) 6.2 mm / 93.1 mm / 102.5 mm, ideal for DIN rail mounting.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
EMC note | EMC: class A product, see manufacturer's declaration in the download area | Product type | Temperature transmitter |
Product family | MINI Analog | Configuration | DIP switches
Software |
Article revision | 13 | Overvoltage category | II |
Pollution degree | 2 | Electrical isolation | 3-way isolation |
Typical cold point errors | < 2 K | Cold point error, max. | < 3 K |
Protective circuit | Transient protection | Step response (0–99%) | 400 ms (Highspeed Mode: typ. 150 ms) |
Maximum temperature coefficient | ≤ 0.01 %/K | Transmission error thermocouples | 0.1 % * 600 K / set measuring range; 0.1 % > 600 K (E, J, K, N, T, L, U, M Gost, L Gost)
0.2 % * 600 K / set measuring range; 0.2 % > 600 K (B, R, S, A1, A2, A3)
0.2% * 600 K / set measuring range; 0.2% > 600 K (E, J, K, N, T, L, U, M Gost, L Gost); Highspeed Mode
0.4% * 600 K / set measuring range; 0.4% > 600 K (B, R, S, A1, A2, A3); Highspeed Mode |
Rated insulation voltage | 50 V AC/DC | Test voltage | 1.5 kV AC (50 Hz, 60 s) |
Insulation | Basic insulation in accordance with IEC/EN 61010 | Supply voltage range | 9.6 V DC ... 30 V DC (The DIN rail connector (ME 6,2 TBUS-2 1,5/5-ST-3,81 GN, item no. 2869728) can be used to bridge the supply voltage. It can be snapped onto a 35 mm DIN rail in accordance with EN 60715) |
Typical current consumption | < 27 mA (at 24 V DC) | Max. current consumption | 72 mA |
Power consumption | ≤ 700 mW (at I | Number of inputs | 1 |
Number of inputs | 1 | Configurable/programmable | Yes |
Sensor types that can be used (TC) | B, E, J, K, N, R, S, T, L, U, A-1, A-2, A-3, M, L | Temperature measuring range | -250 °C ... 2500 °C (Range depends on sensor type, range can be set freely via software or in increments from -150°C to 1350°C via DIP switches) |
Temperature measuring range | min. 50 K | Sensor type: | 500 °C ... 1820 °C
-230 °C ... 1000 °C
-210 °C ... 1200 °C
-250 °C ... 1372 °C
-200 °C ... 1300 °C
-50 °C ... 1768 °C
-50 °C ... 1768 °C
-200 °C ... 400 °C
-200 °C ... 900 °C
-200 °C ... 600 °C
0 °C ... 2500 °C
0 °C ... 1800 °C
0 °C ... 1800 °C
-200 °C ... 100 °C
-200 °C ... 800 °C |
Number of outputs | 1 | Configurable/programmable | Yes |
Voltage output signal | 0 V ... 5 V
1 V ... 5 V
0 V ... 10 V
10 V ... 0 V | Max. voltage output signal | approx. 12.3 V |
Non-load voltage | < 17.5 V | Current output signal | 0 mA ... 20 mA
4 mA ... 20 mA
20 mA ... 0 mA
20 mA ... 4 mA |
Max. current output signal | 24.6 mA | Short-circuit current | < 31.5 mA |
Load/output load voltage output | ≥ 10 kΩ | Load/output load current output | < 500 Ω (at 20 mA) |
Ripple | < 20 mV
< 20 mV | Connection method | Screw connection |
Stripping length | 12 mm | Screw thread | M3 |
Conductor cross section rigid | 0.2 mm² ... 2.5 mm² | Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
Conductor cross section AWG | 26 ... 12 | Connection method | S-PORT |
Status display | LED (red) | Width | 6.2 mm |
Height | 93.1 mm | Depth | 101.2 mm |
Color | green (RAL 6021) | Housing material | PBT |
Fire protection for rail vehicles (DIN EN 45545-2) R22 | HL 1 - HL 2 | Fire protection for rail vehicles (DIN EN 45545-2) R23 | HL 1 - HL 2 |
Fire protection for rail vehicles (DIN EN 45545-2) R24 | HL 1 - HL 2 | Degree of protection | IP20 |
Ambient temperature (operation) | -20 °C ... 65 °C | Ambient temperature (storage/transport) | -40 °C ... 85 °C |
Altitude | ≤ 2000 m | Permissible humidity (operation) | 5 % ... 95 % (non-condensing) |
Certificate | CE-compliant | Certificate | UKCA-compliant |
Identification | UL 508 Listed
Class I, Div. 2, Groups A, B, C, D T4
Class I, Zone 2, Group IIC | Certificate | DNV GL TAA00002R0 |
Temperature | B | Humidity | B |
Vibration | B | EMC | A |
Enclosure | Required protection according to the Rules shall be provided upon installation on board | Electromagnetic compatibility | Conformance with EMC directive |
Noise immunity | EN 61000-6-2 | Note | When being exposed to interference, there may be minimal deviations. |
Noise emission | EN 61000-6-4 | Standards/regulations | EN 61000-4-2 |
Comments | Safety measures must be taken to prevent electrostatic discharge. | Designation | Electromagnetic RF field |
Standards/regulations | EN 61000-4-3 | Typical deviation from the measuring range final value | 0.15 % |
Designation | Fast transients (burst) | Standards/regulations | EN 61000-4-4 |
Typical deviation from the measuring range final value | 0.05 % | Standards/regulations | EN 61000-4-5 |
Designation | Conducted interferences | Standards/regulations | EN 61000-4-6 |
Typical deviation from the measuring range final value | 0.02 % | Electrical isolation | 3-way isolation |
Mounting type | DIN rail mounting | Mounting position | any |
Specifications may be subject to change without notice