Product Model

MINI-PS- 10- 42AC/15-60DC/3

In Stock
Last updated: 2025/4/24
Phoenix Contact MINI-PS- 10- 42AC/15-60DC/3

Selling Points

  • 1Compact design with a width of just 22.5 mm.
  • 2Wide input voltage range: 10 V AC to 42 V AC.
  • 3High efficiency: >95.7% for 42 V AC and nominal values.
  • 4Reliable operation with MTBF >18,175,000 hours at 40 °C.
  • 5Versatile output voltage range: 15 V DC to 60 V DC.
Product Details
MINI-PS- 10- 42AC/15-60DC/3
Phoenix Contact

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Product type
Power module
MTBF (IEC 61709, SN 29500)
> 18175000 h (40 °C)
Article revision
00
Protection class
III
Degree of pollution
2
Number of phases
1.00
Input voltage
24 V AC
Nominal input voltage range
10 V AC ... 42 V AC
Input voltage range
10 V AC ... 42 V AC
Wide-range input
yes
Input voltage range AC
0 V AC ... 42 V AC
Voltage type of supply voltage
AC
Inrush current
< 45 A (typical)
Inrush current integral (I
8 A
AC frequency range
45 Hz ... 65 Hz
Current consumption
6.5 A
Permissible backup fuse
C16 1 x circuit breaker
Recommended breaker for input protection
16 A (Characteristic C)
Efficiency
> 95.7 % (For 42 V AC and nominal values)
Nominal output voltage
28 V DC ±1 % 60 V DC
Output voltage range
15 V DC ... 60 V DC
Nominal output current (I
3 A (-25 °C ... 60 °C)
Derating
60 °C ... 70 °C (2.5 %/K)
Residual ripple
< 3.6 V
Output power
72 W
Maximum no-load power dissipation
< 0.04 W
Power loss nominal load max.
< 6.9 W
Connection in series
no
Connection method
Pluggable screw connection
Conductor cross section, rigid min.
0.2 mm²
Conductor cross section, rigid max.
2.5 mm²
Conductor cross section flexible min.
0.2 mm²
Conductor cross section flexible max.
2.5 mm²
Conductor cross section AWG min.
24
Conductor cross section AWG max.
12
Stripping length
7 mm
Screw thread
M3
Tightening torque, min
0.5 Nm
Tightening torque max
0.6 Nm
Connection method
Pluggable screw connection
Conductor cross section, rigid min.
0.2 mm²
Conductor cross section, rigid max.
2.5 mm²
Conductor cross section flexible min.
0.2 mm²
Conductor cross section flexible max.
2.5 mm²
Conductor cross section AWG min.
24
Conductor cross section AWG max.
12
Stripping length
7 mm
Screw thread
M3
Tightening torque, min
0.5 Nm
Tightening torque max
0.6 Nm
Width
22.5 mm
Height
99 mm
Depth
107 mm
Installation distance right/left
0 mm / 0 mm (≤ 70 °C)
Installation distance top/bottom
50 mm / 50 mm (≤ 70 °C)
Housing material
Plastic
Housing material
Polyamide (PA)
Type of housing
Polyamide PA, color: green
Degree of protection
IP20
Ambient temperature (operation)
-25 °C ... 70 °C (> 60 °C Derating: 2,5 %/K)
Ambient temperature (storage/transport)
-40 °C ... 85 °C
Climatic class
3K3 (in acc. with EN 60721)
Max. permissible relative humidity (operation)
≤ 95 % (at 25 °C, non-condensing)
Shock
18 ms, 30g, in each space direction (according to IEC 60068-2-27)
Vibration (operation)
< 15 Hz, amplitude ±2.5 mm (according to IEC 60068-2-6) 15 Hz ... 150 Hz, 2.3g
UL approvals
UL/C-UL listed UL 508 UL/C-UL Recognized UL 60950-1
SIL in accordance with IEC 61508
0
Electromagnetic compatibility
Conformance with EMC Directive 2014/30/EU
Low Voltage Directive
Conformance with Low Voltage Directive 2014/35/EC
Noise immunity
EN 61000-6-2:2005
Noise emission
EN 55011 (EN 55022)
Standards/regulations
EN 61000-4-2
Housing
> Level 3
Contact discharge
8 kV (Contact discharge)
Discharge in air
8 kV (Air discharge)
Comments
Criterion B
Standards/regulations
EN 61000-4-3
Frequency range
80 MHz ... 3 GHz
Test field strength
10 V/m
Comments
Criterion A
Standards/regulations
EN 61000-4-4
Input
4 kV (level 4 - asymmetrical: conductor to ground)
Output
2 kV (level 3 - asymmetrical: conductor to ground)
Signal
1 kV (Level 2 - asymmetrical cable to ground)
Comments
Criterion B
Standards/regulations
EN 61000-4-5
Input
2 kV (Level 3) 1 kV (Level 3)
Rail applications
EN 50121-4
Standard – Electronic equipment for use in electrical power installations and their assembly into electrical power installations
EN 50178/VDE 0160 (PELV)
Standard - Electrical safety
EN 60950-1/VDE 0805 (SELV)
Assembly note
alignable: horizontally 0 mm, vertically 50 mm
Mounting position
horizontal DIN rail NS 35, EN 60715
With protective coating
no

Specifications may be subject to change without notice