Product Model
PLC-ASC-UI-OUT

Selling Points
- 1Supports 4-20 mA, 0-20 mA, 0-10 V, and 2-10 V analog signals.
- 2Maximum output voltage of 12.3 V with < 20 mVPP ripple.
- 3IP20 degree of protection, suitable for industrial environments.
- 4Configurable via DIP switch for flexible setup options.
- 5Operating temperature range of -20 °C to 50 °C, ensuring stable performance in various conditions.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Notes on operation | For proper use, the specifications of the installation directive (see Downloads) must be observed. For applications or use with third-party products, the specifications, and the safety and warning instructions of the respective third-party manufacturer must also be met. | Product type | Extension module |
Product family | PLC logic | Operating mode | 100% operating factor |
Article revision | 04 | Insulation | Basic insulation |
Overvoltage category | III | Pollution degree | 2 |
Rated insulation voltage | 50 V | Rated surge voltage | 0.5 kV |
Rated control circuit supply voltage U | 24 V DC | Rated control supply voltage range with reference to U | 0.8 ... 1.1 |
Rated control supply current I | ≤ 28 mA | Protective circuit | Reverse polarity protection
Surge protection |
Rated actuating voltage U | 24 V DC | Rated actuating current I | ≤ 1 mA |
Output name | Analog voltage output | Number of outputs | 1 |
Voltage output signal | 0 V ... 10 V
2 V ... 10 V | Maximum output voltage | 12.3 V |
Ripple | < 20 mV | Load/output load voltage output | 10 kΩ |
Surge voltage protection | > 33 V | Maximum transmission error | 1 % |
Resolution | 10 bit (scaled to 0 to 1000) | Protective circuit | Surge protection |
Output name | Analog output for current | Number of outputs | 1 |
Current output signal | 0 mA ... 20 mA
4 mA ... 20 mA | Maximum output current | 24.6 mA |
Load/output load current output | 500 Ω (20 mA) | Surge voltage protection | > 33 V |
Maximum transmission error | 1 % | Resolution | 10 bit |
Protective circuit | Surge protection | Connection method | Screw connection |
Stripping length | 8 mm | Screw thread | M3 |
Conductor cross section rigid | 0.14 mm² ... 2.5 mm² | Conductor cross section flexible | 0.14 mm² ... 2.5 mm²
0.2 mm² ... 2.5 mm² (Single ferrule)
2x 0.5 mm² ... 1.5 mm² (TWIN ferrule) |
Conductor cross section AWG | 26 ... 14 | Tightening torque | 0.45 Nm ... 0.55 Nm (Usually these terminal blocks must be supported during conductor connection (held by one hand, supported on the housing)) |
Operating voltage display | Green LED | Error indication | Red LED |
Width | 6.2 mm | Height | 80 mm |
Depth | 94 mm | Color | gray (RAL 7042) |
Degree of protection | IP20 | Ambient temperature (operation) | -20 °C ... 50 °C |
Ambient temperature (storage/transport) | -20 °C ... 70 °C | Certificate | CE-compliant |
Identification | UL 508 Listed | Standards/regulations | DIN EN 50178 |
Mounting type | DIN rail mounting | Assembly note | in rows with zero spacing |
Mounting position | any |
Specifications may be subject to change without notice