PLC-BSP-120UC/ 1/SEN/SO46
Phoenix Contact

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
EMC note
EMC: class A product, see manufacturer's declaration in the download area
Product type
Relay socket
Product family
PLC-INTERFACE
Application
Filter to prevent interference
Operating mode
100% operating factor
Compatible components
Miniature relay, REL-MR-60DC/21AU, REL-MR-60DC/21; miniature optocoupler, OPT-60DC/48DC/100, OPT-60DC/24DC/2, OPT-60DC/230AC/1
Protective circuit
Bridge rectifier; Bridge rectifier RCZ filter; RCZ filter
Nominal input voltage U
120 V AC 120 V AC
Nominal input voltage U
120 V AC
Input voltage range in reference to U
0.8 ... 1.4
Typical input current at U
7 mA (50 Hz) 8 mA (60 Hz)
Typical response time
7 ms
Typical release time
20 ms
Typical release voltage
50 V AC
Operating voltage display
Yellow LED
Protective circuit
Bridge rectifier; Bridge rectifier Filter; Filter
Nominal input voltage U
120 V AC
Input voltage range in reference to U
0.85 ... 1.1
Typical input current at U
7 mA 8 mA
Switching threshold "0" signal in reference to U
≤ 0.4
Typical response time
6 ms
Typical release time
10 ms
Operating voltage display
Yellow LED
Protective circuit
Bridge rectifier; Bridge rectifier Filter; Filter
Compatible components
Miniature relay, REL-MR-60DC/21AU, REL-MR-60DC/21; miniature optocoupler, OPT-60DC/48DC/100, OPT-60DC/24DC/2, OPT-60DC/230AC/1
Maximum switching voltage
48 V DC
Minimum switching voltage
3 V DC
Limiting continuous current
100 mA
Voltage drop at max. limiting continuous current
< 1 V DC
Output circuit
2-conductor, floating
Protective circuit
Reverse polarity protection Surge protection
Maximum switching voltage
30 V DC
Minimum switching voltage
3 V DC
Limiting continuous current
3 A
Voltage drop at max. limiting continuous current
< 200 mV
Maximum inrush current
15 A (10 ms)
Output circuit
2-conductor, floating
Protective circuit
Reverse polarity protection Surge protection
Maximum switching voltage
253 V AC (Partition plate PLC-ATP must be installed for voltages larger than 250 V (L1, L2, L3) between identical terminal points in adjacent modules. Potential bridging is then carried out with FBST 8-PLC... or ...FBST 500...)
Minimum switching voltage
24 V AC
Limiting continuous current
0.75 A
Voltage drop at max. limiting continuous current
< 1 V AC
Maximum inrush current
30 A (10 ms)
Output circuit
2-conductor, floating
Protective circuit
RCV circuit
Leakage current
< 1 mA
Phase angle cos phi min
0.5
Max. load value
4.5 A
Connection method
Spring-cage connection
Stripping length
8 mm
Conductor cross section rigid
0.14 mm² ... 2.5 mm²
Conductor cross section flexible
0.14 mm² ... 2.5 mm²
Conductor cross section AWG
26 ... 14
Connection method
Spring-cage connection
Stripping length
8 mm
Conductor cross section rigid
0.14 mm² ... 2.5 mm²
Conductor cross section flexible
0.14 mm² ... 2.5 mm²
Conductor cross section AWG
26 ... 14
Status display
LED
Width
6.2 mm
Height
80 mm
Depth
94 mm
Color
green (RAL 6021)
Flammability rating according to UL 94
V0 (Housing)
Ambient temperature (operation)
-25 °C ... 55 °C
Ambient temperature (storage/transport)
-40 °C ... 85 °C
Mounting type
DIN rail mounting
Assembly note
in rows with zero spacing
Mounting position
any

Specifications may be subject to change without notice