Phoenix Contact PLC-HSC-24DC/230AC/10

Selling Points

  • 1Compact Design: 14 mm width, 80 mm height, and 94 mm depth for easy DIN rail mounting.
  • 2High Reliability: 100% operating factor with reverse polarity and surge protection.
  • 3Versatile Output: 24 V AC to 253 V AC output with 10 A continuous current.
  • 4Efficient Control: 14 mA (low) and 19 mA (high) control supply current for precise control.
  • 5Durable Construction: IP20 protection, safe isolation, and overvoltage category III for robust operation.
Product Details
PLC-HSC-24DC/230AC/10
Phoenix Contact

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Product type
Solid-state relay module
Product family
PLC-INTERFACE
Application
Output function
Operating mode
100% operating factor
Date of last data management
07.05.2024
Article revision
04
Insulation
safe isolation
Overvoltage category
III
Pollution degree
2
Test voltage
4 kV
Rated insulation voltage
260 V AC
Rated surge voltage
6 kV
Rated control circuit supply voltage U
24 V DC
Voltage range with reference to U
0.8 ... 1.2
Rated control supply current I
≤ 19 mA
Rated actuating voltage U
24 V DC
Voltage range with reference to U
0.8 ... 1.2
Rated actuating current I
6.8 mA
Nominal voltage (plugged-in solid-state relay)
24 V DC
"0" signal switching threshold in reference to U
< 0.4
"1" signal switching threshold in reference to U
> 0.8
Typical response time
30 ms
Typical turn-off time
20 ms
Status display
LED (yellow)
Protective circuit
Reverse polarity protection Surge protection
Surge voltage protection
> 33 V DC
Transmission frequency
1 Hz
Designation
AC hybrid output
Contact switching type
1 N/O contact
Design of digital output
electronic
Output voltage range
24 V AC ... 253 V AC (50/60 Hz)
Limiting continuous current
10 A (see derating curve)
Min. load current
100 mA
Leakage current
< 1 mA
Surge current
250 A (tp = 20 ms, at 25 °C)
Max. load value
350 A
Surge voltage protection
> 275 V
Output circuit
2-conductor, floating
Protective circuit
Varistor
Connection method
Screw connection
Stripping length
8 mm
Screw thread
M3
Conductor cross section rigid
0.14 mm² ... 2.5 mm²
Conductor cross section flexible
0.14 mm² ... 2.5 mm² 0.2 mm² ... 2.5 mm² (Single ferrule) 2x 0.5 mm² ... 1.5 mm² (TWIN ferrule)
Conductor cross section AWG
26 ... 14
Tightening torque
0.45 Nm ... 0.55 Nm (Usually these terminal blocks must be supported during conductor connection (held by one hand, supported on the housing))
Width
14 mm
Height
80 mm
Depth
94 mm
Color
gray (RAL 7042)
Degree of protection (Relay base)
IP20 (Relay base)
Degree of protection (Relay)
RT II (Relay)
Degree of protection (Installation location)
IP54 (Installation location)
Ambient temperature (operation)
-25 °C ... 60 °C
Ambient temperature (storage/transport)
-40 °C ... 85 °C
Altitude
≤ 2000 m
Identification
ISA-S71.04. G3 Harsh Group EN 60068-2-60
Standards/regulations
IEC 60947-5-1
Mounting type
DIN rail mounting
Assembly note
See derating curve
Mounting position
any

Specifications may be subject to change without notice