Phoenix Contact PLC-OPT- 24DC/230AC/1

Selling Points

  • 1High Reliability: Designed for industrial control systems with a robust construction.
  • 2Versatile Voltage Range: Operates with a 24V DC input and outputs 24-253V AC.
  • 3Efficient Energy Consumption: Typical input current at 8 mA ensures efficient energy usage.
  • 4Fast Switching Times: Rapid response time of 10 ms and turn-off time of 10 ms for quick switching.
  • 5Comprehensive Protection: Includes reverse polarity protection, free-wheeling diode, and damping diode for safe operation.
Product Details
PLC-OPT- 24DC/230AC/1
Phoenix Contact

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Product type
Solid-state relay module
Product family
PLC-INTERFACE
Application
Universal
Operating mode
100% operating factor
Date of last data management
07.05.2024
Article revision
05
Insulation
Basic insulation
Overvoltage category
III
Pollution degree
2
Maximum power dissipation for nominal condition
0.19 W
Test voltage (Input/output)
2.5 kV (50 Hz, 1 min., input/output)
Nominal input voltage U
24 V DC
Nominal voltage (plugged-in solid-state relay)
24 V DC
Input voltage range in reference to U
0.8 ... 1.2
Input voltage range
19.2 V DC ... 28.8 V DC
Switching threshold "0" signal in reference to U
≤ 0.25
Switching threshold "1" signal in reference to U
≥ 0.8
Typical input current at U
8 mA
Typical response time
10 ms (at U
Typical turn-off time
10 ms (at U
Operating voltage display
Yellow LED
Protective circuit
Reverse polarity protection; Polarity protection diode Freewheeling diode; Freewheeling diode
Transmission frequency
10 Hz
Contact switching type
1 N/O contact
Design of digital output
electronic
Contact connection type
Power contact
Output voltage range
24 V AC ... 253 V AC
Limiting continuous current
750 mA (see derating curve)
Maximum inrush current
30 A (10 ms)
Min. load current
10 mA
Leakage current
< 1 mA (in off state)
Phase angle cos phi min
0.5
Max. load value
4.5 A
Voltage drop at max. limiting continuous current
< 1 V
Output circuit
2-conductor, floating
Protective circuit
RCV circuit
Connection method
Push-in connection
Stripping length
10 mm
Conductor cross section rigid
0.14 mm² ... 2.5 mm²
Conductor cross section flexible
0.14 mm² ... 2.5 mm² 0.2 mm² ... 2.5 mm² (Single ferrule) 2x 0.5 mm² ... 1 mm² (TWIN ferrule)
Conductor cross section AWG
26 ... 14
Width
6.2 mm
Height
80 mm
Depth
94 mm
Color
gray (RAL 7042)
Flammability rating according to UL 94
V0 (Housing)
Ambient temperature (operation)
-25 °C ... 60 °C
Ambient temperature (storage/transport)
-25 °C ... 70 °C
Certificate
CE-compliant
Certificate
UKCA-compliant
Certificate
TAE0000196
Identification
ISA-S71.04. G3 Harsh Group EN 60068-2-60
Temperature
D
Humidity
A
Vibration
B/C
EMC
B
Enclosure
Required protection according to the Rules shall be provided upon installation on board
Electromagnetic compatibility
Conformance with EMC directive
Low Voltage Directive
Conformance with Low Voltage Directive
Standards/regulations
IEC 60947-5-1
Mounting type
DIN rail mounting
Assembly note
in rows with zero spacing
Mounting position
any

Specifications may be subject to change without notice