Phoenix Contact PLC-OSC- 24DC/ 24DC/  2/ACT

Selling Points

  • 1Directly connect to system cabling using the V8 adapter for streamlined setup.
  • 2Achieve quick switching times with a typical response time of 20 µs and turn-off time of 300 µs.
  • 3Ensure reliable operation with reverse polarity protection, free-wheeling diode, and surge protection.
  • 4Operate within a wide input voltage range of 19.2 V DC to 28.8 V DC.
  • 5Compact dimensions (6.2 mm x 80 mm x 94 mm) for easy integration into industrial settings.
Product Details
PLC-OSC- 24DC/ 24DC/ 2/ACT
Phoenix Contact

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Product type
Solid-state relay module
Product family
PLC-INTERFACE
Application
Output function
Operating mode
100% operating factor
Date of last data management
07.05.2024
Article revision
10
Insulation
Basic insulation
Overvoltage category
III
Pollution degree
2
Maximum power dissipation for nominal condition
0.2 W
Test voltage (Input/output)
2.5 kV (50 Hz, 1 min., input/output)
Nominal input voltage U
24 V DC
Nominal voltage (plugged-in solid-state relay)
24 V DC
Input voltage range in reference to U
0.8 ... 1.2
Input voltage range
19.2 V DC ... 28.8 V DC
Switching threshold "0" signal in reference to U
≤ 0.4
Switching threshold "1" signal in reference to U
≥ 0.8
Typical input current at U
8.5 mA
Typical response time
20 µs (at U
Typical turn-off time
300 µs (at U
Operating voltage display
Yellow LED
Protective circuit
Reverse polarity protection; Polarity protection diode Freewheeling diode; Freewheeling diode
Transmission frequency
300 Hz
Contact switching type
1 N/O contact
Design of digital output
electronic
Contact connection type
Power contact
Output voltage range
3 V DC ... 33 V DC
Limiting continuous current
3 A (see derating curve)
Maximum inrush current
15 A (10 ms)
Voltage drop at max. limiting continuous current
≤ 200 mV
Output circuit
2-conductor, floating
Protective circuit
Reverse polarity protection; Polarity protection diode Surge protection
Connection method
Screw connection
Stripping length
8 mm
Screw thread
M3
Conductor cross section rigid
0.14 mm² ... 2.5 mm²
Conductor cross section flexible
0.14 mm² ... 2.5 mm² 0.2 mm² ... 2.5 mm² (Single ferrule) 2x 0.5 mm² ... 1.5 mm² (TWIN ferrule)
Conductor cross section AWG
26 ... 14
Tightening torque
0.6 Nm ... 0.8 Nm
Width
6.2 mm
Height
80 mm
Depth
94 mm
Flammability rating according to UL 94
V0 (Housing)
Ambient temperature (operation)
-25 °C ... 60 °C
Ambient temperature (storage/transport)
-25 °C ... 70 °C
Certificate
CE-compliant
Certificate
UKCA-compliant
Certificate
TAE0000196
Identification
ISA-S71.04. G3 Harsh Group EN 60068-2-60
Temperature
D
Humidity
A
Vibration
B/C
EMC
B
Enclosure
Required protection according to the Rules shall be provided upon installation on board
Electromagnetic compatibility
Conformance with EMC directive
Low Voltage Directive
Conformance with Low Voltage Directive
Standards/regulations
IEC 60947-5-1
Mounting type
DIN rail mounting
Assembly note
in rows with zero spacing
Mounting position
any

Specifications may be subject to change without notice