Product Model
PLC-PT-ELR W1/ 2-24DC

Selling Points
- 1Solid-State Contactor: Reliable motor protection with a solid-state contactor.
- 2Reverse Motor Protection: Safeguards against reverse motor operation.
- 3Push-In Connection: Easy and secure connection method.
- 4High-Performance Output: Outputs 10-30 V DC/2 A for efficient motor control.
- 5Compact Design: Compact dimensions (12.5 mm x 99 mm x 114.5 mm) for space-saving installations.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
EMC note | EMC: class A product, see manufacturer's declaration in the download area | Product type | Solid-state contactor |
Product family | PLC-INTERFACE | Operating mode | 100% operating factor |
Article revision | 02 | Insulation | Basic insulation |
Overvoltage category | II | Pollution degree | 2 |
Number of phases | 1 | Maximum power dissipation for nominal condition | 0.4 W |
Rated insulation voltage | 50 V | Rated surge voltage | 0.5 kV |
Input name | Device supply | Rated control circuit supply voltage U | 24 V DC |
Control supply voltage range | 19.2 V DC ... 28.8 V DC | Input name | Control input right/left |
Rated actuating voltage U | 24 V DC | Triggering voltage range | 19.2 V DC ... 28.8 V DC |
Rated actuating current I | 3 mA | Typical response time | 200 µs |
Protective circuit | Reverse polarity protection
Surge protection | Surge voltage protection | > 33 V DC |
Transmission frequency | 300 Hz | Switchover time R | 80 ms |
Note | Protect the supply voltage at the output using a suitable fuse. | Rated operating voltage U | 24 V DC |
Operating voltage range | 10 V DC ... 30 V DC | Rated operating current (Load output) | 2 A |
Load current | 2 A | Quiescent current | 10 mA |
Protective circuit | Reverse polarity protection; Polarity protection diode (No continuous protection against polarity reversal)
Surge protection | Surge voltage protection | > 33 V DC |
Note | Short-circuit and overload protection | Continuous load current | 2 A (see derating curve) |
Short-circuit current | 15 A (during braking) | Protective circuit | Surge protection
RC element |
Surge voltage protection | > 33 V DC | Connection method | Push-in connection |
Stripping length | 10 mm | Conductor cross section rigid | 0.14 mm² ... 2.5 mm² |
Conductor cross section flexible | 0.14 mm² ... 2.5 mm²
0.2 mm² ... 2.5 mm² (Single ferrule)
2x 0.5 mm² ... 1 mm² (TWIN ferrule) | Conductor cross section AWG | 26 ... 14 |
Status display | LED (yellow) | Operating voltage display | Green LED |
Width | 6.5 mm | Height | 80 mm |
Depth | 94 mm | Color | gray (RAL 7042) |
Flammability rating according to UL 94 | V0 | Degree of protection | IP20 |
Ambient temperature (operation) | -25 °C ... 60 °C | Ambient temperature (storage/transport) | -40 °C ... 85 °C |
Certificate | UKCA-compliant | Certificate | CE-compliant |
Standards/regulations | IEC 60664
EN 50178 | Mounting type | DIN rail mounting |
Assembly note | in rows with zero spacing | Mounting position | Vertical (horizontal DIN rail) |
Specifications may be subject to change without notice