Phoenix Contact PLC-RPT-230UC/21AU/MS

Selling Points

  • 1Operates at 250 V AC/DC with gold layer intact and 30 V AC/36 V DC with gold layer destroyed.
  • 2Equipped with AgSnO, hard gold-plated contacts for long-lasting performance.
  • 3Mounts on DIN rail NS 35/7,5 for easy installation and space efficiency.
  • 4Typical response time of 7 ms and typical release time of 15 ms.
  • 5Meets EMC Class A standards and is WEEE/RoHS-compliant.
Product Details
PLC-RPT-230UC/21AU/MS
Phoenix Contact

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Product type
Relay Module
Product family
PLC-INTERFACE
Application
Palm switch
Operating mode
100% operating factor
Mechanical service life
2x 10
Date of last data management
05.07.2024
Article revision
03
Maximum power dissipation for nominal condition
0.74 W
Test voltage (Winding/contact)
4 kV AC (50 Hz, 1 min., winding/contact)
Rated insulation voltage
250 V
Rated impulse withstand voltage
6 kV
Overvoltage category
III
Degree of pollution
3
Nominal input voltage U
230 V AC 220 V DC
Input voltage range
179.4 V AC ... 264.5 V AC (20 °C) 171.6 V DC ... 253 V DC (20 °C)
Nominal voltage (plugged-in electromechanical relay)
60 V DC
Drive and function
monostable
Drive (polarity)
polarized
Typical input current at U
3.2 mA (at U 3 mA (at U
Typical response time
7 ms
Typical release time
15 ms
Protective circuit
Bridge rectifier; Bridge rectifier
Operating voltage display
Yellow LED
Contact switching type
1 changeover contact
Type of switch contact
Single contact
Contact material
AgSnO, hard gold-plated
Maximum switching voltage
30 V AC 36 V DC
Minimum switching voltage
100 mV (at 10 mA)
Limiting continuous current
50 mA
Maximum inrush current
50 mA
Min. switching current
1 mA (24 V)
Short-circuit current
200 A (conditional short-circuit current)
Interrupting rating (ohmic load) max.
1.2 W (at 24 V DC)
Output fuse
4 A gL/gG NEOZED
Note
Maximum switching voltage
250 V AC/DC
Minimum switching voltage
5 V (at 100 mA)
Limiting continuous current
6 A
Min. switching current
10 mA (at 12 V)
Interrupting rating (ohmic load) max.
140 W (at 24 V DC) 20 W (at 48 V DC) 18 W (at 60 V DC) 23 W (at 110 V DC) 40 W (at 220 V DC) 1500 VA (for 250 V AC)
Switching capacity
2 A (at 24 V, DC13) 0.2 A (at 110 V, DC13) 0.1 A (at 220 V, DC13) 3 A (at 24 V, AC15) 3 A (at 120 V, AC15) 3 A (at 230 V, AC15)
Connection method
Push-in connection
Stripping length
10 mm
Conductor cross section rigid
0.14 mm² ... 2.5 mm²
Conductor cross section flexible
0.14 mm² ... 2.5 mm² 0.2 mm² ... 2.5 mm² (Single ferrule) 2x 0.5 mm² ... 1 mm² (TWIN ferrule)
Conductor cross section AWG
26 ... 14
Width
6.2 mm
Height
80 mm
Depth
94 mm
Color
gray (RAL 7042)
Flammability rating according to UL 94
V0 (Housing)
Degree of protection (Relay)
RT III (Relay)
Degree of protection (Relay base)
IP20 (Relay base)
Ambient temperature (operation)
-40 °C ... 55 °C
Ambient temperature (storage/transport)
-40 °C ... 85 °C
Certificate
CE-compliant
Certificate
UKCA-compliant
Certificate
TAE0000196
Identification
ISA-S71.04. G3 Harsh Group EN 60068-2-60
Temperature
D
Humidity
A
Vibration
B/C
EMC
B
Enclosure
Required protection according to the Rules shall be provided upon installation on board
Electromagnetic compatibility
Conformance with EMC directive
Low Voltage Directive
Conformance with Low Voltage Directive
Standards/regulations
IEC 60664 IEC 60664A DIN VDE 0110 IEC 60255/DIN VDE 0435 (in relevant parts)
Mounting type
DIN rail mounting
Assembly note
in rows with zero spacing
Mounting position
any

Specifications may be subject to change without notice