Selling Points

  • 1Efficient Control Solutions: Operates at 48V DC with a typical input current of 19 mA.
  • 2Fast Response Time: Typical response time of 6 ms and release time of 10 ms.
  • 3Durable Construction: Mechanical service life of 5x 10^6 cycles and AgNi contacts.
  • 4Safe Isolation: Safe isolation and reinforced insulation for reliable operation.
  • 5Versatile Mounting: DIN rail mounting with push-in connections for easy installation.
Product Details
PLC-RPT- 48DC/21-21/MS
Phoenix Contact

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Product type
Relay Module
Product family
PLC-INTERFACE
Application
Palm switch
Operating mode
100% operating factor
Mechanical service life
5x 10
Date of last data management
30.10.2024
Article revision
03
Insulation
Safe isolation, reinforced insulation
Overvoltage category
III
Pollution degree
2
Maximum power dissipation for nominal condition
0.92 W
Test voltage (Winding/contact)
4 kV
Test voltage (Changeover contact/changeover contact)
2.5 kV
Rated insulation voltage
250 V AC
Rated surge voltage
6 kV
Nominal input voltage U
48 V DC
Input voltage range
40.3 V DC ... 62.4 V DC (20 °C)
Nominal voltage (plugged-in electromechanical relay)
24 V DC
Drive and function
monostable
Drive (polarity)
polarized
Typical input current at U
19 mA
Typical response time
6 ms
Typical release time
10 ms
Protective circuit
Bridge rectifier
Operating voltage display
Yellow LED
Contact switching type
2 changeover contacts
Type of switch contact
Single contact
Contact material
AgNi
Maximum switching voltage
250 V AC/DC (The separating plate PLC-ATP should be installed for voltages larger than 250 V (L1, L2, L3) between identical terminal blocks in adjacent modules. Potential bridging is then carried out with FBST 8-PLC... or ...FBST 500...)
Minimum switching voltage
12 V (10 mA)
Limiting continuous current
6 A
Maximum inrush current
12 A (20 ms)
Min. switching current
10 mA (12 V)
Interrupting rating (ohmic load) max.
192 W (24 V DC) 62 W (48 V DC) 42 W (60 V DC) 55 W (110 V DC) 66 W (220 V DC) 2000 VA (250 V AC)
Switching capacity
1 A (24 V, DC13) 1.5 A (230 V, AC15)
Connection method
Push-in connection
Stripping length
10 mm
Conductor cross section rigid
0.14 mm² ... 2.5 mm²
Conductor cross section flexible
0.14 mm² ... 2.5 mm² 0.2 mm² ... 2.5 mm² (Single ferrule) 2x 0.5 mm² ... 1 mm² (TWIN ferrule)
Conductor cross section AWG
26 ... 14
Width
14 mm
Height
80 mm
Depth
104 mm
Color
gray (RAL 7042)
Flammability rating according to UL 94
V0 (Housing)
Degree of protection (Relay)
RT II (Relay)
Degree of protection (Relay base)
IP20 (Relay base)
Degree of protection (Installation location)
≥ IP54 (Installation location)
Ambient temperature (operation)
-20 °C ... 60 °C
Ambient temperature (storage/transport)
-20 °C ... 85 °C
Altitude
≤ 2000 m
Certificate
CE-compliant
Certificate
UKCA-compliant
Identification
UL 508 UL 508 Recognized
Identification
UL 508 UL 508 Recognized
Certificate
TAE0000196
Identification
ISA-S71.04. G3 Harsh Group EN 60068-2-60
Temperature
D
Humidity
A
Vibration
B/C
EMC
B
Enclosure
Required protection according to the Rules shall be provided upon installation on board
Electromagnetic compatibility
Conformance with EMC directive
Low Voltage Directive
Conformance with Low Voltage Directive
Standards/regulations
EN 50178
Mounting type
DIN rail mounting
Assembly note
in rows with zero spacing
Mounting position
any

Specifications may be subject to change without notice