Product Model
PLC-RSC- 24DC/PMC T200/21HC

Selling Points
- 1100% operating factor ensures consistent performance.
- 2Reinforced insulation with safe isolation between adjacent modules.
- 3Compatible with 19.2 V DC to 26.4 V DC input voltage range.
- 4Typical response time of 7 ms for quick switching.
- 5Equipped with surge protection and freewheeling diode for reliability.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Product type | Relay Module | Product family | PLC-INTERFACE |
Operating mode | 100% operating factor | Mechanical service life | approx. 2x 10 |
Date of last data management | 08.07.2024 | Article revision | 09 |
Insulation | Safe isolation, reinforced insulation (partition plate PLC-ATP should be installed for safe isolation between adjacent modules). | Overvoltage category | III |
Pollution degree | 3 | Maximum power dissipation for nominal condition | 0.4 W |
Nominal input voltage U | 24 V DC | Input voltage range | 19.2 V DC ... 26.4 V DC (20 °C) |
Nominal voltage (plugged-in electromechanical relay) | 24 V DC | Typical input current at U | 15 mA (Relay ON)
4.3 mA (Relay OFF) |
Typical response time | 7 ms | Typical release time | 200 ms +130 ms (Typical interval time at U |
Protective circuit | Surge protection; Freewheeling diode | Operating voltage display | Yellow LED |
Contact switching type | Single contact, 1 changeover contact | Type of switch contact | Single contact |
Contact material | AgNi, hard gold-plated | Maximum switching voltage | 250 V AC/DC (Separating plate PLC-ATP must be installed for voltages larger than 250 V (L1, L2, L3) between identical terminal blocks in adjacent modules.) |
Minimum switching voltage | 12 V AC/DC | Limiting continuous current | 10 A |
Maximum inrush current | 16 A | Min. switching current | 100 mA |
Interrupting rating (ohmic load) max. | 240 W (at 24 V DC)
144 W (at 48 V DC)
48 W (at 60 V DC)
50 W (at 110 V DC)
80 W (at 220 V DC)
4000 W (for 250 V AC) | Connection method | Screw connection |
Stripping length | 8 mm | Screw thread | M3 |
Conductor cross section rigid | 0.14 mm² ... 2.5 mm² | Conductor cross section flexible | 0.14 mm² ... 2.5 mm²
0.2 mm² ... 2.5 mm² (Single ferrule)
2x 0.5 mm² ... 1.5 mm² (TWIN ferrule) |
Conductor cross section AWG | 26 ... 14 | Tightening torque | 0.45 Nm ... 0.55 Nm (Usually these terminal blocks must be supported during conductor connection (held by one hand, supported on the housing)) |
Width | 14 mm | Height | 80 mm |
Depth | 94 mm | Color | green (RAL 6021) |
Flammability rating according to UL 94 | V0 (Housing) | Degree of protection | IP20 |
Ambient temperature (operation) | -20 °C ... 50 °C | Identification | ISA-S71.04. G3 Harsh Group
EN 60068-2-60 |
Standards/regulations | DIN EN 50178 | Mounting type | DIN rail mounting |
Assembly note | in rows with zero spacing | Mounting position | any |
Specifications may be subject to change without notice