Product Model

PLC-RSP-120UC/21-21AU

In Stock
Last updated: 2025/4/20
Phoenix Contact PLC-RSP-120UC/21-21AU

Selling Points

  • 1Utilizes V8 adapter for seamless system cabling integration.
  • 2Ensures safe isolation between coil and contact side according to DIN EN 50178.
  • 3RT III sealed relay with integrated input circuit and interference suppression circuit.
  • 4Suitable for universal applications with a 100% operating factor.
  • 5Slim design for easy mounting on DIN rail NS 35/7.5.
Product Details
PLC-RSP-120UC/21-21AU
Phoenix Contact

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
EMC note
EMC: class A product, see manufacturer's declaration in the download area
Product type
Relay Module
Product family
PLC-INTERFACE
Application
Universal
Operating mode
100% operating factor
Mechanical service life
3x 10
Date of last data management
10.10.2023
Insulation
Basic insulation
Overvoltage category
III
Pollution degree
2
Rated surge voltage
6 kV
Nominal input voltage U
120 V AC 110 V DC
Input voltage range
102 V AC/DC ... 168 V AC/DC
Typical input current at U
4.2 mA (at 110 V DC) 4.5 mA (at 120 V AC)
Typical response time
7 ms
Typical release time
10 ms
Protective circuit
Bridge rectifier; Bridge rectifier
Operating voltage display
Yellow LED
Contact switching type
2 changeover contacts
Type of switch contact
Single contact
Contact material
AgNi, hard gold-plated
Maximum switching voltage
30 V AC 36 V DC
Minimum switching voltage
100 mV (at 10 mA)
Limiting continuous current
50 mA
Maximum inrush current
50 mA
Min. switching current
1 mA (at 24 V)
Interrupting rating (ohmic load) max.
1.2 W (at 24 V DC)
Note
Maximum switching voltage
250 V AC/DC
Minimum switching voltage
5 V AC/DC
Limiting continuous current
6 A
Maximum inrush current
15 A (300 ms)
Min. switching current
10 mA
Interrupting rating (ohmic load) max.
140 W (at 24 V DC) 85 W (at 48 V DC) 60 W (at 60 V DC) 44 W (at 110 V DC) 60 W (at 220 V DC) 1500 VA (for 250 V AC)
Switching capacity
2 A (at 24 V, DC13) 0.2 A (at 110 V, DC13) 0.2 A (at 250 V, DC13) 2 A (at 24 V, AC15) 2 A (at 120 V, AC15) 2 A (at 250 V, AC15)
Connection method
Spring-cage connection
Stripping length
8 mm
Conductor cross section rigid
0.14 mm² ... 2.5 mm²
Conductor cross section flexible
0.14 mm² ... 2.5 mm²
Conductor cross section AWG
26 ... 14
Connection method
Spring-cage connection
Stripping length
8 mm
Conductor cross section rigid
0.14 mm² ... 2.5 mm²
Conductor cross section flexible
0.14 mm² ... 2.5 mm²
Conductor cross section AWG
26 ... 14
Width
14 mm
Height
80 mm
Depth
94 mm
Color
green (RAL 6021)
Flammability rating according to UL 94
V0 (Housing)
Degree of protection (Relay)
RT III (Relay)
Degree of protection (Relay base)
IP20 (Relay base)
Ambient temperature (operation)
-40 °C ... 60 °C
Ambient temperature (storage/transport)
-40 °C ... 85 °C
Standards/regulations
IEC 60664 IEC 60947-5-1
Mounting type
DIN rail mounting
Assembly note
in rows with zero spacing
Mounting position
any

Specifications may be subject to change without notice