Product Model
PLC-RSP-230UC/ 1AU/SEN

Selling Points
- 1Efficient Connection: Connects seamlessly to system cabling using V8 adapters.
- 2Safe Isolation: Ensures safe isolation between coil and contact sides according to DIN EN 50178.
- 3High Reliability: Operates with a 100% operating factor and mechanical service life of 2 x 10^7 cycles.
- 4Compact Design: Slim design for space-saving installations on DIN rail NS 35/7.5.
- 5Versatile Applications: Suitable for various industrial applications, including railway and general use.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
EMC note | EMC: class A product, see manufacturer's declaration in the download area | Product type | Relay Module |
Product family | PLC-INTERFACE | Application | Input function |
Operating mode | 100% operating factor | Mechanical service life | 2x 10 |
Date of last data management | 20.04.2023 | Overvoltage category | III |
Pollution degree | 3 | Maximum power dissipation for nominal condition | 0.74 W |
Test voltage (Winding/contact) | 4 kV AC (50 Hz, 1 min., winding/contact) | Nominal input voltage U | 230 V AC
220 V DC |
Input voltage range | 179.4 V AC/DC ... 264.5 V AC/DC | Typical input current at U | 3.2 mA |
Typical response time | 7 ms | Typical release time | 15 ms |
Protective circuit | Bridge rectifier; Bridge rectifier | Operating voltage display | Yellow LED |
Contact switching type | 1 N/O contact | Type of switch contact | Single contact |
Contact material | AgSnO, hard gold-plated | Maximum switching voltage | 30 V AC
36 V DC |
Minimum switching voltage | 100 mV (at 10 mA) | Limiting continuous current | 50 mA |
Maximum inrush current | 50 mA | Min. switching current | 1 mA (at 24 V) |
Interrupting rating (ohmic load) max. | 1 W (at 24 V DC) | Note | — |
Maximum switching voltage | 250 V AC/DC | Minimum switching voltage | 5 V (at 100 mA) |
Limiting continuous current | 6 A | Min. switching current | 10 mA (at 12 V) |
Interrupting rating (ohmic load) max. | 140 W (at 24 V DC)
20 W (at 48 V DC)
18 W (at 60 V DC)
23 W (at 110 V DC)
40 W (at 220 V DC)
1500 VA (for 250 V AC) | Switching capacity | 2 A (at 24 V, DC13)
0.2 A (at 110 V, DC13)
0.1 A (at 220 V, DC13)
3 A (at 24 V, AC15)
3 A (at 120 V, AC15)
3 A (at 230 V, AC15) |
Connection method | Spring-cage connection | Stripping length | 8 mm |
Conductor cross section rigid | 0.14 mm² ... 2.5 mm² | Conductor cross section flexible | 0.14 mm² ... 2.5 mm² |
Conductor cross section AWG | 26 ... 14 | Connection method | Spring-cage connection |
Stripping length | 8 mm | Conductor cross section rigid | 0.14 mm² ... 2.5 mm² |
Conductor cross section flexible | 0.14 mm² ... 2.5 mm² | Conductor cross section AWG | 26 ... 14 |
Width | 6.2 mm | Height | 80 mm |
Depth | 94 mm | Color | green (RAL 6021) |
Flammability rating according to UL 94 | V0 (Housing) | Degree of protection (Relay base) | IP20 (Relay base) |
Ambient temperature (operation) | -40 °C ... 55 °C | Ambient temperature (storage/transport) | -40 °C ... 85 °C |
Standards/regulations | IEC 60664
EN 50178 | Assembly note | in rows with zero spacing |
Mounting position | any |
Specifications may be subject to change without notice